VAMP VAMP 150 Quick guide

VAMP 150
Motor protection relay
Operation and configuration
instructions
Technical description

VAMP 150
Motor protection relay
Operation and Configuration
VAMP Ltd
2
Vamp 24h support phone : +358 (0)20 753 3264
V 150.EN005

VAMP Ltd Motor protection relay
Operation and Configuration
VAMP 150
V 150.EN005 Vamp 24h support phone : +358 (0)20 753 3264
3
Table of Content
1.
General ............................................................................ 5
1.1. Relay features......................................................................5
1.2. Operating safety .................................................................6
2.
User interface ..................................................................
2.1. General.................................................................................7
2.2. Local panel ..........................................................................7
2.2.1. Display .........................................................................8
2.2.2. Key pad.......................................................................8
2.2.3. Indicators ....................................................................9
3.
Communication via local panel................................. 10
3.1. Navigation in the menus..................................................10
3.2. Function menu quick reference .....................................11
3.2.1. Basic menu structure of protection functions .....13
3.3. Operating levels ................................................................13
3.3.1. Opening operating levels ......................................14
3.3.2. Changing of passwords..........................................14
4.
Operating measures..................................................... 15
4.1. Operation via the local I ...........................................15
4.1.1. easured data........................................................15
4.1.2. Operation indicators ...............................................16
4.1.3. Reading of event register.......................................16
4.1.4. Forced control (Force)............................................17
4.1.5. Setting range limits ..................................................18
4.1.6. Adjusting display contrast and scroll speed........18
4.1.7. Setting date and time.............................................18
5.
Configuration and setting of parameters...................19
5.1. Principle of parameter setting ........................................20
5.2. Enabling and disabling protection functions (ENABLE)
.............................................................................................21
5.3. Setting protection function parameters........................21
5.4. Scaling of measuring transformers .................................22
5.5. Configuring digital outputs DOUT...................................22
5.6. Configuring blocking matrix BLOCKING........................22
5.7. Configuring the digital input DIGITAL IN........................22
5.8. Configuring communication protocols CO ..............23
5.9. Analog output mA OUTPUT .............................................24
5.10. Service menu SERVICE.....................................................24
6.
PC software....................................................................25
6.1. PC user interface...............................................................25
6.1.1. Using the VA PSET program..................................25
6.2. Remote control connections ..........................................25
.
Commissioning configuration ..................................... 26
7.1. Factory settings..................................................................26
7.1.1. Configuration during commissioning....................26
7.1.2. Configuration examples.........................................27

VAMP 150
Motor protection relay
Operation and Configuration
VAMP Ltd
4
Vamp 24h support phone : +358 (0)20 753 3264
V 150.EN005

VAMP Ltd Motor protection relay
Operation and Configuration
VAMP 150
V 150.EN005 Vamp 24h support phone : +358 (0)20 753 3264
5
1. General
This part of the manual describes the general functions of the
motor protection relay VAMP 150 and includes the relay
operation instructions. It also includes instructions on
parameterization and configuration of the relay and
instructions on changing of settings.
The second part of the publication includes detailed protection
function descriptions as ell as application examples and
technical data sheets.
The Mounting and Operation Instructions are published in a
separate publication, code named VMMC.EN0xx.
1.1. Relay features
The motor protection relay VAMP 150 is a non-directional
current measuring protection relay for internal short-circuit,
internal earth-fault, unbalance, single phasing, overload and
too frequent starting protection. It features the follo ing
protection functions.
•
Thermal overload stage
•
Three overcurrent stages
•
T o earth-fault stages
•
One undercurrent stage
•
Phase unbalance stage
•
Current unbalance stage
•
Frequent starts supervision
•
Start-up supervision and stall protection
•
Circuit breaker failure protection
Further the relay includes a disturbance recorder and is
optionally available ith an arc supervision unit. It is also
equipped ith a current measuring transducer, the output
signal of hich can be ired to an external meter or a SCADA
system.
The relay communicates ith other systems using common
protocols, such as the ModBus RTU, ModBus TCP, Profibus
DP, IEC 60870-5-103 and it can be connected to the fibre-optic
SPA bus.

VAMP 150
Motor protection relay
Operation and Configuration
VAMP Ltd
6
Vamp 24h support phone : +358 (0)20 753 3264
V 150.EN005
1.2. Operating safety
The terminals on the rear panel of the relay may
carry dangerous voltages, although the auxiliary
voltage is s itched off. An alive current transformer
secondary circuit must not be opened.
Disconnecting a live circuit may cause dangerous
Disconnecting a live circuit may cause dangerous Disconnecting a live circuit may cause dangerous
Disconnecting a live circuit may cause dangerous
voltages!
voltages!voltages!
voltages! Any operational measure must be carried
out according to national and local handling
directives and instructions.
Carefully read through the relay operation instructions before
any relay operational measures are carried out.

VAMP Ltd Motor protection relay
Operation and Configuration
VAMP 150
V 150.EN005 Vamp 24h support phone : +358 (0)20 753 3264
7
2. User interface
2.1. General
The VAMP 150 relay can be controlled in three ays:
•
Locally ith the push-buttons on the relay front panel
•
Locally ith a PC connected to the serial port on the relay
front panel
•
Via remote control over the remote control port on the relay
rear panel.
2.2. Local panel
Figure 2.2-1 belo sho s the location of the components of the
local user interface on the front panel of the relay.
Figure 2.2-1 Relay front panel.
1. Alpha-numerical LED display
2. Key pad
3. LED indicators
4. RS 232 serial communication port for a PC

VAMP 150
Motor protection relay
Operation and Configuration
VAMP Ltd
8
Vamp 24h support phone : +358 (0)20 753 3264
V 150.EN005
2.2.1. Display
The VAMP 150 relay is provided ith a clear 10 character
alphanumerical LED display, hich normally sho s a scrolling
text.
Use the SERVICE/Setup/Bright menu to set the brightness of
the display. The display is dimmed after a preset time.
Use the SERVICE/Setup/ScrolDelay menu to set the scrolling
speed of the display text.
2.2.2. Key pad
Use the key pad and the display to navigate through the menus
and to set the required parameters. The keypad comprises the
follo ing keys:
LEFT, RIGHT, UP, DOWN and the ENTER key.
Figure 2.2.2-1 Components of the key pad.
1. Enter and confirmation key (ENTER)
2. UP/DOWN [INCREASE/DECREASE] arro keys
(UP/DOWN)
3. LEFT/RIGHT arro keys [for selection of digit position]
(LEFT/RIGHT)

VAMP Ltd Motor protection relay
Operation and Configuration
VAMP 150
V 150.EN005 Vamp 24h support phone : +358 (0)20 753 3264
9
Key functions
Function:
Function:Function:
Function:
Key:
Key:Key:
Key:
Note:
Note:Note:
Note:
Navigation do n ards in the menu. Decreasing
of setting value/selection of text value in the
setting state
DOWN
Navigation up ards in the menu. Increasing of
number value/selection of text value in the setting
state
UP
Moving to the right in the menu (to submenu, to
parameter). Moving to the right in an adjustable
value, digit by digit
RIGHT
Moving to the left in the menu (to submenu /
main menu). Moving to the left in an adjustable
value, digit by digit
LEFT
Cancellation of change LEFT push > 2 s
Transfer of parameter into the setting state.
Activation of pass ord supply and acceptance of
pass ord hile moving to the setting state.
Saving of setting and exit from setting state.
Resetting of alarm display in normal operating
state (USER level).
ENTER
Resetting of (LED) indicators ENTER
2.2.3. Indicators
The relay front panel holds 4 LED indicators:
toimintamerkit
Figure 2.2.3-1 Relay operation indicators.
Relay operation indicators:
Po er on
Po er onPo er on
Po er on
auxiliary voltage s itched on
Error
ErrorError
Error
self-supervision fault, the self-supervision output relay
operates in parallel ith the indicator
Alarm
AlarmAlarm
Alarm
starting of protection stage
Trip
TripTrip
Trip
tripping of protection stage

VAMP 150
Motor protection relay
Operation and Configuration
VAMP Ltd
10
Vamp 24h support phone : +358 (0)20 753 3264
V 150.EN005
3. Communication via local
panel
The local panel can be used to read measured values, set
parameters and configure relay functions. Ho ever, please note
that some of the parameters can only be set by means of a PC
connected to the local communication port. Further, some
parameters are factory set.
3.1. Navigation in the menus
All setting, resetting, etc. functions are carried out via menu
functions, see Figure 3.1-1:
1. Use UP and DOWN arro keys to move up and do n in the
main menu. The active menu is the one seen in the display.
The menu names are sho n ith their full length or
abbreviated, e.g. IL STATUS = status display for the
different current stages.
2. Use the RIGHT key to move to the function level of the
required menu, e.g. I> Stat.
Use the LEFT key to cancel the selection.
3. Use the RIGHT key to move to the parameter level of the
selected function, e.g. SCntr.
Use the UP and DOWN keys to scroll through the other
parameters on the same function level.
4. Confirm the selection of setting state of the requested
parameter by pushing ENTER and by entering the
pass ord corresponding to the setting level.
5. Push LEFT for at least 2 s to exit from the setting state of a
parameter ithout changing the setting value or,
6. Push ENTER to confirm and store the parameter setting.

VAMP Ltd Motor protection relay
Operation and Configuration
VAMP 150
V 150.EN005 Vamp 24h support phone : +358 (0)20 753 3264
11
MAIN MENU SUBMENUS
menurakenne_100sarja
Figure 3.1-1 The principle of the menu structure and navigation in the
menus.
3.2. Function menu quick reference
The structure of the menu is clear and straightfor ard. The
main menu holds nineteen submenus, each ith varying
numbers of submenus and parameters.

VAMP 150
Motor protection relay
Operation and Configuration
VAMP Ltd
12
Vamp 24h support phone : +358 (0)20 753 3264
V 150.EN005
Figure 3.2-1 Main menu of the VAMP 150 relay.

VAMP Ltd Motor protection relay
Operation and Configuration
VAMP 150
V 150.EN005 Vamp 24h support phone : +358 (0)20 753 3264
13
3.2.1. Basic menu structure of protection functions
Example I>:
IL SETTING / I> SET:
I> 110A Set value of protection function [A]
I> 1.10xImot Set value of protection function [pu]
Type
DT Selection of delay time curve (DT, NI, VI, EI, LTI)
t> 0.30s
IL STATUS I> stat:
SCntr - Start counter
TCntr
- Trip counter
Force
- Enabling and disabling force function (ON/OFF)
Status - -, Start, Trip
3.3. Operating levels
The relay features three operating levels, i.e. the User, the
Operator and the Configuration level. The purpose of the
operating levels is to prevent accidental change of relay
configurations, parameterizations or settings.
USER level
Use: Parameter values, for example, can be read
Opening: Level permanently open
Closing: Closing not possible
OPERATOR level
Use: Settings of prot
ection stages, for example, can
be changed.
Opening: The default pass ord is 0001.
Setting state: On entering the parameter setting state the
relay asks for a pass ord "GIVE Operator
pass ord", then push the key and enter the
pass ord. Then push the key again.
Closing: The level is automatically closed 10 minutes
after a key being pushed last or a setting
being performed via the local port. Closing
can also be performed by giving the pass ord
9999.

VAMP 150
Motor protection relay
Operation and Configuration
VAMP Ltd
14
Vamp 24h support phone : +358 (0)20 753 3264
V 150.EN005
CONFIGURATION level
Use: The configuration level is needed during the
commissioning of the relay. The turns ratios
of the current transformers, for example, can
be set.
Opening: The default pass ord is 0002
Configure state: On entering the configuration state the relay
asks for a pass ord "GIVE Operator pass-
ord", then push the key and enter the
pass ord. Then push the key again.
Closing: The level is automatically closed 10 minutes
after a key being pushed last or a setting be-
ing performed via the local port. Closing can
also be performed by giving the pass ord
9999.
3.3.1. Opening operating levels
1. Move to the item to be changed, e.g. IL SETTING/I>Set/ I>:
1.20 pu. Push the ENTER key t ice on the front panel.
+++0
Figure 3.3.1-1 Opening an operating level
2. Enter the pass ord needed for the desired level: The
pass ord may contain four digits. The digits are supplied
one by one by first moving to the position of the digit using
the RIGHT key and then setting the desired digit value
using the UP key.
3. Push ENTER.
3.3.2. Changing of passwords
The set pass ord can only be changed locally using a PC
connected to the local RS 232 port on the relay. The change is
allo ed/prohibited ith the parameter
ChgP d = 0/1 in the SERVICE/Setup menu.

VAMP Ltd Motor protection relay
Operation and Configuration
VAMP 150
V 150.EN005 Vamp 24h support phone : +358 (0)20 753 3264
15
4. Operating measures
General
Carefully study the operating instructions in Chapters 1
through 3 of this manual before any operating measures are
taken or before any relay settings or functions are changed.
The relay can be controlled by means of the MMI on the relay
front panel, a PC running the VAMPSET soft are, a PC
running suitable terminal soft are or a remote control system.
4.1. Operation via the local MMI
4.1.1. Measured data
The measured values can be read from the MEASURES menu
and its submenus sho n in the figure belo .
Figure 4.1.1-1 Measures menu of VAMP 150 relay.

VAMP 150
Motor protection relay
Operation and Configuration
VAMP Ltd
16
Vamp 24h support phone : +358 (0)20 753 3264
V 150.EN005
4.1.2. Operation indicators
LED indic
LED indicLED indic
LED indica
aa
ators
torstors
tors
Explanat
ExplanatExplanat
Explanation
ionion
ion
Measure/ remarks
Measure/ remarksMeasure/ remarks
Measure/ remarks
Po er LED lit The auxiliary po er
s itched on
Normal operating state
Error LED lit An internal relay fault has
been detected
The relay attempts to
reboot. [REBOOT]. If the
error LED remains lit,
call for maintenance
Alarm LED lit One or several signals of the
output relay matrix have
been assigned to output
Alarm and the output has
been activated by one of the
signals. (see Chapter 5.5)
The LED is s itched off,
hen the signal that
caused output Alarm to
activate, e.g. the START
signal, resets. The
resetting depends on the
type of configuration;
Connected or Latched.
TRIP LED lit One or several signals of the
output relay matrix have
been assigned to output
Trip and the output has
been activated by one of the
signals. (see Chapter 5.5)
The LED is s itched off,
hen the signal that
caused output Trip to
activate, e.g. the TRIP
signal, resets. The
resetting depends on the
type of configuration;
Connected or Latched.
Resetting latched indicators and output relays
The alarm LED and relays (Alarm) as ell as the trip LED and
relays (Trip) are reset in the follo ing ay:
1. Push the ENTER key to reset all latched devices.
Note:
The internal fault (IF) indication cannot be reset.
4.1.3. Reading of event register
The event register can be read from the Events item of the
main menu:
1. Push the RIGHT key once, the displays sho s the Event
info text
2. Push the RIGHT key once, the displays sho s Count: x,
here x = the number of recorded events
3. Push the DOWN key once, the display sho s the ClrEv
text. The event register can no be reset.
4. Push the LEFT key to return to the Event info menu (by
pressing t ice you can return to the main menu)
5. Push the DOWN key to return to the Event list menu:

VAMP Ltd Motor protection relay
Operation and Configuration
VAMP 150
V 150.EN005 Vamp 24h support phone : +358 (0)20 753 3264
17
Figure 4.1.3-1 Event register, example.
6. Push the RIGHT key once to enter the event list, the
display sho s the last Event list text. Scroll the event list
by pushing the UP and DOWN keys.
7. Push the LEFT key t ice to move from the event list to the
main menu.
4.1.4. Forced control (Force)
In the SERVICE menu it is possible to use forced control of the
output relays, e.g. for testing purposes.
To activate the forced control function (see Figure 4.1.4-1):
1. Move to the SERVICE level of the main menu.
2. Push the RIGHT key once to move to the submenu Relays
3. Push the RIGHT key once to move to the output relays’
force setting parameter Force:
SERVICE Relays Force:OFF
Off
On
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
Figure 4.1.4-1 Activation of the Force function.
4. Push the ENTER key hile on the Force: level to be able to
change the setting (the parameter to be set is blinking)
5. Push the UP and DOWN keys to change the OFF text to the
ON text in the display (Force function activated).
6. Push the ENTER key to confirm the setting and to move
back to the Force: level
7. The Force: level has a selection list. Push the UP and
DOWN keys to select the desired output relay, hich is
controlled on and off by forced control:

VAMP 150
Motor protection relay
Operation and Configuration
VAMP Ltd
18
Vamp 24h support phone : +358 (0)20 753 3264
V 150.EN005
8. Push the ENTER key to obtain the setting state, e.g.
Relays/T1.
9. Push the UP or DOWN key to change the selection 0 -> 1.
10. Push the ENTER key to perform a controlled operation of
the output relay (e.g. the T1 is activated) and to return to
the Force: level.
11. Push the LEFT key for more than 2 s to return from the
Force: setting state to the normal Force: state ithout
changing the control state.
12. Push the LEFT key to return from the Force: setting state
to the Relays submenu.
13. Push the LEFT key to return to the main menu.
4.1.5. Setting range limits
Note!
Parameters requiring a numerical setting value can be given
out-of-range settings, but hen the setting is confirmed ith
the ENTER key, a fault message ill be obtained. Adjust the
setting to ithin the permitted setting range.
4.1.6. Adjusting display contrast and scroll speed
The readability of the LCD varies ith the brightness of the
surrounding. When needed the brightness can be adjusted in
the SERVICE/Setup/Bright: menu.
The scroll speed of the text in the display can be adjusted in the
SERVICE/Setup/ScrolDelay: menu.
4.1. . Setting date and time
Date, time and style is set in the SERVICE/Setup/Date, Time
and Style menus.

VAMP Ltd Motor protection relay
Operation and Configuration
VAMP 150
V 150.EN005 Vamp 24h support phone : +358 (0)20 753 3264
19
5. Configuration and setting of
parameters
User level: CONFIGURATION
•
Choose the protection functions in the ENABLE position of
the main menu, see chapter 5.2. NOTE! Protection
functions not enabled ill not be sho n in the submenus.
•
Change the parameters of overcurrent, stall protection,
overload, unbalance, phase sequence, undercurrent and arc
protection functions in the IL SETTING position of the
main menu, see chapter 5.3.
•
Change the parameters of residual current and residual arc
protection functions in the Io SETTING position of the main
menu, see chapter 5.3.
•
Change the parameters of the frequent start protection
function in the N> Set position of the main menu, see
chapter 5.3.
•
Change the parameters of Circuit Breaker Failure
Protection function in the CBFP Set position of the main
menu, see chapter 5.3.
•
Set the current transformer scaling and residual current
scaling (e.g. Imot, CTprim, CTsec, CToprim, etc.) in the
SCALING position of the main menu, see chapter 5.4.
•
Configure the digital outputs in the DOUT position of the
main menu, see chapter 5.5.
•
Configure the interlockings in the BLOCKING position of
the main menu, see chapter 5.6.
•
Configure the digital input in the DIGITAL IN position of
the main menu, see chapter 5.7.
•
Choose and configure the communication buses in the COM
position of the main menu, see chapter 5.8.
•
Configure the analog output in the mA OUTPUT position of
the main menu, see chapter 5.9.
•
Change the parameters of the Disturbance recorder in the
RECORDER position of the main menu.
•
Set the Date and time in the SERVICE position of the main
menu, see chapter 5.10.
NOTE!
Some of the parameters, for instance the pass ord, can only be
altered via the RS 232 serial communication port using a PC.

VAMP 150
Motor protection relay
Operation and Configuration
VAMP Ltd
20
Vamp 24h support phone : +358 (0)20 753 3264
V 150.EN005
5.1. Principle of parameter setting
This example sho s ho to change the scaling of the current
transformers. Same principle is used to change other
parameters, see Figure 5.1-1.
1. Use the DOWN key of the front panel to move to item
SCALING of the main menu.
2. Use the RIGHT key to move one step to the right, the text
CTprim: 100 A appears in the display. Use the DOWN key
to select the CTsec.
3. Use the ENTER key t ice to move to give the operator
pass ord. Use the ENTER key to confirm the pass ord.
4. Use the UP and DOWN key to change the setting value and
use the RIGHT and LEFT key to move from digit to digit.
5. Use the ENTER key to confirm the function or push the
LEFT key for >2 s to cancel the function.
6. Push the LEFT key t ice to return to the main menu.
Figure 5.1-1 Changing parameters.
Table of contents
Other VAMP Relay manuals