User Manual PSA3200 10
Monitoring V out : 0 ~ 5 V, Accuracy : 1 % of Vout rated+
Output impedance : 150 / 4 mA maxΩ
I out : 0 ~ 5 V, Accuracy : 1 % of Iout rated+
Output impedance : 150 / 4 mA maxΩ
V reference 5.1 V 15 mV+
Status outputs Power Supply OK Logic 1 (High); AC Fail – Logic 0 (Low)
DC Fail – Logic 0 (Low), for DC fails by 5 % set value+
CV / CC Status : CV :Logic 0 / CC Logic 1
Interlock : Short = Power Supply enabled , Open = Power Supply disabled
DC ON status : ON = Logic 1 , OFF = Logic 0
OVP status Fault : Logic 0, else OK =Logic 1
OTP status Fault : Logic 0, else OK =Logic 1
Remote shutdown +5 V
Front Panel Controls
Indicators
Mains ON/ OFF, Voltage and Current setting with multi-turn potentiometer
(Coarse and fine), OVP Setting
LEDs for : Voltage, Current, CV, CC, Output ON, OVP, ACF, OTP
Protections Over voltage , Over current, Short Circuit, Fold back, Over temperature
Output Terminals Bus bar with M5 bolts
Mains Input AC input, Single phase, 207 to 270 V, 50 / 60 Hz ( 47 ~ 63Hz)
Input connector : IEC320/C14 , EN 60320/14
Internal Fuse L : 20 A, 6.3 x 32 mm ceramic fuse.
Power Factor 0.99 @ full load / 0.98 @ 50% load
Turn On delay 600 ms after mains switched ON
Inrush current <50A
Hold up Time 20 ms
Environment Conditions
Operating Temperature 0 ~ +50°C; with 100% load; derated 75% at 60°C
Storage -40 ~ + 85°C
Humidity max. 95% non condensing at 40°C, max. 75% non condensing at 50°C
Safety Insulation : Input to Output : 3750 V for 1 min
Input to case : 2500 Vrms Output to case : 600 V
Insulation resistance : 100 M at 25°C, 70% RH, 500 Vdc
Dimension W x D x H : 443 x 557 x 87 mm (2U, 19” Rack size) excluding connectors,
terminals, switches, front and back panel controls, handles etc.
Weight 13.5 kg approx.
Cooling Forced variable fan speed
Standard Analog Programing
Accessories Supplied User Manual, Mains Connector
Notes:
1. Subject to change without notice.
2. Sensing at the rear panel of the power supply unit at sense terminals.
3. Unit warm up time is 30 min.
4. Minimum output voltage guaranteed to maximum of 0.2% rated.
5. Minimum output current guaranteed to maximum of 0.4% rated.