WARNING
• This product must be disconnected from the circuit if subjected to any high
voltage or insulation resistance testing. Irreparable damage will occur if this
instruction is not followed
• Recommended routine test procedure in accordance with BS 5266
• Daily check - check that the status GREEN LED indicator is illuminated
• Monthly functional test - simulate a mains supply failure for approx. 30 secs by
operation of a key switch or circuit breaker.Ensure normal supply
is restored after test and the indicator status LED is illuminated.
• Twice yearly conduct a one hour duration test - simulate a mains supply failure
breaker. Ensure normal supply is restored after test and the indicator status LED
is illuminated
• Annual full three hour duration test - conduct a three hour continuous
duration test. Simulate a mains supply failure for three hour continuous test by
r. Ensure normal supply is
restored after test and the indicator status LED is illuminated
•
GENERAL
the correct manner when it reaches the end of its life. Check local authorities for
where facilities exist. Clean with a soft dry cloth only, do not use aggressive cleaning
GENERAL INSTRUCTIONS
These instructions should be read carefully and retained after installation by the end
user for future reference and maintenance.
SAFETY
•
or competent person to the current IEE Wiring Regulations
• Please isolate mains prior to installation/maintenance
•
not exceed the rating of the circuit cable, fuse or circuit breaker
• Please note the IP (Ingress of Protection) rating of this luminaire when deciding
the location for installation
electrician. See overleaf for test record sheet
• Provide power to the required point of installation
•
Mark the loc les and drill the holes ensuring not to infringe with any
joists, gas or water pipes or electrical cables, and mount the fitting
• Connect the battery to the inverter via the plug and socket provided
• Connect the Live and Neutral t terminals on the PCB of the inverter
• Remove the mount plate from the gear tray
Fig 1
• This product can only be used in maintained operation (luminaire constantly on)
Live (brown)
Neutral (Blue)
L
N
INSTALLATION
Fig 1
• Switch on the power supply and ensure the LED indicator is illuminated green. If it is not
illuminated green, there may be a supply or battery fault
• Switch on the power supply and ensure the LED status indicator is illuminated
green to ensure the battery and supply are functioning.
After 36 hours on continuous charge a mains failure should be simulated to ensure
successful operation.
Switch on the power supply and ensure the LED status indicator is illuminated green to
ensure the battery and supply are functioning.
After 36 hours on continuous charge, a full battery discharge should occur. This will
ensure correct battery reset, once batteries are fully depleted, mains power should be
reapplied to the system.
Normal maintenance procedures should occur once mains power has been reapplied.