ScreenTronic ST3134 Specification sheet

ST3134
KNX Blind Actuator SC 4-fold
Operation and Installation Manual
Date: 2.1.2019

ST3134 Operation and Installation Manual
2
Contents
Contents
Contents ..................................................................................................................................................................2
Introduction.............................................................................................................................................................3
Wiring Diagram........................................................................................................................................................4
Group Objects..........................................................................................................................................................5
Parameters ..............................................................................................................................................................7
General ................................................................................................................................................................7
Positions ............................................................................................................................................................12
Automatic* ........................................................................................................................................................13
Blind 1 to 4.........................................................................................................................................................14
Technical Support..................................................................................................................................................16

ST3134 Operation and Installation Manual
3
Introduction
The ST3134 KNX Blind Actuator SC 4-fold is a special control for blinds with SC 3-wire connection (SL MB
blinds). Due to the fully digital and bidirectional communication between ST3134 and the motor control unit
(inside the blind) the ST3134 realize precise position control and feedback and therefore allows perfect sun
tracking and integration into building management systems.
Without any analog timing or manual operations, the blinds can easily be controlled to any target position
(height and angle). Smart homes and buildings can integrate blinds controlled by ST3134 perfectly with visual
user interface and scenes.
IMPORTANT NOTICE:
* The marked group objects and parameters are not supported at this time or only on request available for
special blinds types or projects or must be confirmed from control and blind manufacturer and need in any
case detailed knowledge of the entire blind system. Please contact control and blind supplier for details.

ST3134 Operation and Installation Manual
4
Wiring Diagram
SL2712

ST3134 Operation and Installation Manual
5
Group Objects

ST3134 Operation and Installation Manual
6
The following KNX Group Objects are supported: (channel 1)
10
Blind 1 Up/Down
1 Bit
W
up/down
11
Blind 1 Stop/Step
1 Bit
W
up/down
13
Blind 1 Height
1 Byte
W
0-255 (0-100%)
14
Blind 1 Slat angle
1 Byte
W
0-255 (0-100%)
15
Blind 1 Position call
1 Byte
W
0 – 5 (position 1 to 6)
23
Blind 1 Status Height
1 Byte
RT
0-255 (0-100%)
24
Blind 1 Status Slat angle
1 Byte
RT
0-255 (0-100%)
26
Blind 1 Status Blind
Communication error
1 Bit
RT
on/off
and same for blind channel 2, 3 and 4.

ST3134 Operation and Installation Manual
7
Parameters
General
Power supply of the blinds
Please use in any case Automatic (with automatic blind addressing) except the blind manufacturer
indicates something different.
Automatic:
The power output (+24V DC) for each channel is controlled from the ST3134 on internal requirement.

ST3134 Operation and Installation Manual
8
Together:
The power output for all channels is controlled from the ST3134 on requirement, but all 4 outputs are
powered in any case in same way.
Permanent:
The power output (+24V DC) for all channels is ON at any time.
Automatic blind addressing:
After KNX Power on or KNX application programming the addressing of the blinds is automatically
performed from the ST3134 with the addresses 1 to 4 (for channel 1 to 4).
Manual blind addressing:
Blind addresses must be set manually for each blind using CTS for Blinds software (special
knowledge about the blind system is necessary).
Blind type
Indicates the blind type connected to all channels as indicated from the blind supplier.
Following Control*
Allows to control from KNX side blinds over each other in same way as a single blind. E.g. 1 + 2
means that the blind on channel 1 is mounted over blind on channel 2. Both blinds are controlled from
KNX side with group objects for channel 1 and group objects for channel 2 do not exist.

ST3134 Operation and Installation Manual
9
Transmission of status position*
Status position is transmitted cyclically with fixed timing.
Group objects 23 and 24 (and corresponding objects for channel 2 to 4) Status Height and Status Slat
Angle.
Transmission of status blind*
Status blind (object 26) is transmitted cyclically with fixed timing.
Group objects 25, 26 and 27 (and corresponding objects for channel 2 to 4) Status Blind, Status Blind
Communication Error, Status Blind Error.
Time for cyclic transmission (min)*
Transmission interval for changes (s) *
Movement after full tilting*
Group object 12 Slat Tilting: Dimming control from switch.

ST3134 Operation and Installation Manual
10
Enable tilting during active disable manual control commands object*
Group object 16 Disable Manual Control Commands is in case of “active” not performed for the
Objects 11, 12 and 14.
Stop on activation of disable manual control commands object*
Stops actual moving blinds 1 on receiving a “1” on group object 16 (and corresponding objects for
channel 2 to 4). Manual control commands are blocked and blind is stopped.
Enable tilting during active disable blind object*
Group object 22 is not performed for group objects 11, 12, 14, 19. Only tilting functions are allowed.
Stop on activation of disable blind object*
Stops actual moving blind on receiving a “1” on group object 22. So all control commands are blocked
and blind is stopped.
Follow-up on deactivation of disable blind object*
After receiving “0” on group object 22 the blind start moving to the latest expected position.
Typical Application: Closing windows frame.
Follow-up on deactivation of security*
After receiving “0” on group object 1 the blind start moving to the latest expected position (if last
command was moving, slat angle or height).

ST3134 Operation and Installation Manual
11
Security position*
After receiving “1” on group object 1 all 4 blinds (channel 1 to 4) reacts like the parameter.
Typical application: Fire alarm moves all blinds in upper position
Monitoring time security object (min)*
After receiving not a “0” within this time the Security function is activated.
0=Monitoring of the security object is deactivated.

ST3134 Operation and Installation Manual
12
Positions
Allows to define 6 different positions (height and angle) to be called for each channel with group
object 15 Position call (or corresponding group object for channel 2 to 4).
Position set allowed*
Receiving byte value 0 to 5 calls the defined positions 1 to 6.

Automatic (example for blind 1)
Automatic object function
After receiving “1” on group object 20, automatic function is activated and object groups 17, 18
and 19 are deactivated.
Status Feedback
Object group 20 is set by actuator status feedback.
Automatic switching
Object group 20 is set by external group address.
Status Feedback & Automatic switching
Object group 20 is set by actuator status feedback or by external group address.
Time until automatic activation (10-minute step) deactivation by automatic object
After receiving “0” on group object 20, timer starts immediately for the set point time.
Deactivation by manual operation
Yes
No
Time until automatic activation (10-minute step) deactivation by manual operation
The timer starts as soon as a manual command (object groups 10..15) is received; when the timer
expires the system resumes the Automatic mode.
Menu Blind1
In order to allow the automatic operation of blind 1, set the “Automatic function” parameter to “Yes”

ST3134 Operation and Installation Manual
14
Blind 1 to 4
Blind connection*
Option must be set to Permanent connection.
Tilting area (encoder pulses)*
Do not change this value which is defined by the internal blind parameters from blind manufacturer!
Modification can be done with separate CTS software!
Number of tilt steps*
Do not change this value which is defined by the internal blind parameters from blind manufacturer!
Modification can be done with separate CTS software!

ST3134 Operation and Installation Manual
15
Shaking free after down movement *
Do not change this value which is defined by the internal blind parameters from blind manufacturer!
Modification can be done with separate CTS software!
Tilting up after down movement *
Do not change this value which is defined by the internal blind parameters from blind manufacturer!
Modification can be done with separate CTS software!
Automatic function*
Automatic must be deactivated and any automatic operation and sun tracking is performed by ST413x
or ST414x Blind Control Center or by group objects 13 and 14 (and corresponding group objects for
channels 2 to 4) with byte values for height and angle from any BMS Build Automation System with
KNX communication.

ST3134 Operation and Installation Manual
16
Technical Support
For technical support please contact:
CONTROLtronic GmbH
Schragenhofstr. 35
80992 Munich
Germany
e-mail
support@controltronic.com
phone
+49 89 74 55 66 77
© 2019 CONTROLtronic GmbH
ScreenTronic®is a registered trademark of CONTROLtronic GmbH.
Information presented enclosed is subject to change as product enhancements are made regularly.
Pellini S.p.A.
via Fusari, 19
26845 Codogno (LO)
ITALY
+39 0377 466411
Table of contents
Other ScreenTronic Controllers manuals
Popular Controllers manuals by other brands

Renesas
Renesas RA6T2 Application note

Whelen Engineering Company
Whelen Engineering Company MPC02 operating guide

Extron electronics
Extron electronics MEDIALINK MLC 206 Setup guide

Immergas
Immergas 3.021523 manual

Texas Instruments
Texas Instruments TMS320C2000 quick start guide

Traxxas
Traxxas XL-5 instructions