SD3 ALPHA 16-248 GBR Operating manual

User and Installation Manual
ALPHA 16 - 248 GBR
Conventional Modular Fire Alarm
Control Panel
Document : MUALPHA16248GB
Index : A
Date : 26/03/07
Page : 1/49
Conventional modular fire alarm panel
ALPHA 16 - 248

User and Installation Manual
ALPHA 16 - 248 GBR
Conventional Modular Fire Alarm
Control Panel
Document : MUALPHA16248GB
Index : A
Date : 26/03/07
Page : 2/49
CONTENTS:
SECTION PAGE
1
1- Alpha 16 - 248 PANEL DATA SHEET...........................................................................................4
1-2 PANEL DEVICES CONSUMPTION TABLE:............................................................................................... 7
2- FIRE DETECTION MICROPROCESSOR PANEL..........................................................................7
2-1 MAIN CHARACTERISTICS: ...................................................................................................................... 7
2-2 OPTIONAL EN54 FUNCTIONS CONTROLLED ......................................................................................... 8
2-3 ACCESSORY FUNCTIONS CONTROLLED .............................................................................................. 9
2-4 POWER SUPPLY GROUP AL224E: .......................................................................................................... 9
2-5 OPERATING AND CONFIGURATION SOFTWARE: .................................................................................. 9
2-6 BLOCK DIAGRAM ALPHA 16 -248 :........................................................................................................ 10
3- DISPLAY AND COMMAND COMPONENTS:..............................................................................12
3-1 MAIN DISPLAY/COMMAND PANEL: ....................................................................................................... 12
3-2 GENERAL SIGNALS AND COMMANDS.................................................................................................. 12
3-3 ALPHANUMERIC DISPLAY AND KEYBOARD......................................................................................... 15
3-4 LEDS FOR STATE OF ZONES 1-32 ........................................................................................................ 16
4- LINE AND ZONE CONTROL, OPERATING FUNCTIONS: ..........................................................17
4-1 PANEL LINES AND ZONES; CONTROL LOGIC....................................................................................... 17
4-2 PREALARM, ALARM AND FAULT:.......................................................................................................... 19
4-3 FUNCTION OF DELAYED ALARM: ......................................................................................................... 19
4-4 FUNCTION OF FIRST ALARM AUTO-RESET:......................................................................................... 20
4-5 TEST ZONE FUNCTION:........................................................................................................................ 20
5- COMMAND FUNCTIONS: ...........................................................................................................20
5-1 OPERATING LEVELS AND 2ND ACCESS LEVEL ACTIVATION: ............................................................... 20
5-2 SILENCE THE BUZZER AND ALARM/FAULT OUTPUTS:........................................................................ 21
5-3 PANEL MEMORY RESET ....................................................................................................................... 21
5-4 ACTIVATION/DEACTIVATION OF ALARM DELAY FUNCTION:............................................................... 22
5-5 DEACTIVATION/ACTIVATION OF ALARM OUTPUTS:............................................................................ 22
5-6 DEACTIVATION/ACTIVATION OF FAULT OUTPUT: ............................................................................... 22
5-7 ZONES/SECTORS SELECTION, DISPLAY AND DEACTIVATION/ACTIVATION: ..................................... 22
5-8 LINES SELECTION, DISPLAY AND DEACTIVATION/ACTIVATION: ........................................................ 23
5-9 SPECIAL SELECTION AND DISPLAY: .................................................................................................... 24
5-10 PANEL GENERAL DISABLE:.............................................................................................................. 24
5-11 LED/DISPLAY TEST:.......................................................................................................................... 24
5-12 DISPLAY/PRINT PANEL EVENTS: ..................................................................................................... 25
5-13 SETUP OF PANEL CLOCK:................................................................................................................ 25
6- CONFIGURATION OF ALPHA 16 - 248: .....................................................................................25
6-1 UNIT CONFIGURATION FROM PANEL................................................................................................... 26
6-1-1 LINES CONFIGURATION:.................................................................................................................................................. 27
6-1-2 ZONES / SECTORS CONFIGURATION:........................................................................................................................... 27
6-1-3 TIMES CONFIGURATION: ................................................................................................................................................. 28
6-1-4 PANEL OPTIONS CONFIGURATION: .............................................................................................................................. 29
6-1-5 CONFIGURATION OF MODULES CONNECTED TO THE PANEL:................................................................................32
6-2 PANEL CONFIGURATION BY PC: .......................................................................................................... 32
7- PANEL MAINTENANCE..............................................................................................................33
8- MODULE PLANS AND CONNECTION DIAGRAMS....................................................................33
8-1 LOCAL PANEL FOR PANEL CONTROL (RAIK-P).................................................................................... 33
CONNECTION TERMINAL STRIPS AND CONNECTORS RAIK-P ............................................................................................... 34
8-2 96 LED MODULE TO DISPLAY STATE OF ZONES/SECTORS (RAIK-2L)................................................ 34
8-2-1 SETTINGS AND INDICATIONS ......................................................................................................................................... 34
8-3 POWER SUPPLY MODULE (AL224E) ..................................................................................................... 34
8-3-1 CONNECTION TERMINAL STRIPS AND CONNECTORS AL224E. ...............................................................................35
8-4 MICROPROCESSOR BASIC MODULE RAIK-A....................................................................................... 36
8-4-1 CONNECTION TERMINAL STRIPS AND CONNECTORS .............................................................................................. 36
8-5 COMMON INPUT OUTPUT MODULE RAIK-B.......................................................................................... 37
8-5-1 STRIPS AND CONNECTORS CONNECTION TERMINAL .............................................................................................. 37
8-5-2 ACOUSTIC DEVICE CONNECTION.................................................................................................................................. 38
8-5-3 OPTIC/ACOUSTIC DEVICE CONNECTION ..................................................................................................................... 39
8-6 EIGHT INPUT MODULE (RAIK-I OR EX8Z)............................................................................................... 40

User and Installation Manual
ALPHA 16 - 248 GBR
Conventional Modular Fire Alarm
Control Panel
Document : MUALPHA16248GB
Index : A
Date : 26/03/07
Page : 3/49
8-6-1 CONNECTION TERMINAL STRIPS AND CONNECTORS RAIK-I. ................................................................................. 40
8-6-2 SETTINGS AND INDICATIONS ......................................................................................................................................... 41
8-6-3 Conventional detectors connection to RAIK-I module. ...................................................................................................... 42
8-7 EIGHT OUTPUTS RELAY MODULE (RAIK-U OR EX8R)........................................................................... 43
8-7-2 TERMINAL STRIPS, CONNECTORS AND JUMPERS FOR THE MODULE RAIK-U..................................................... 43
8-7-3 SETTINGS AND INDICATIONS ......................................................................................................................................... 44
8-7-4 IMPORTANT NOTES ON THE CONNECTION OF THE ACTUATORS TO THE OUTPUT RELAYS ............................ 45
8-8 CABLES FOR CONNECTION TO THE PANEL /PC AND PANEL /MODEM............................................... 47

User and Installation Manual
ALPHA 16 - 248 GBR
Conventional Modular Fire Alarm
Control Panel
Document : MUALPHA16248GB
Index : A
Date : 26/03/07
Page : 4/49
1- Alpha 16 - 248 PANEL DATA SHEET
GENERAL SPECIFICATIONS:
SYSTEM NAME ALPHA 16 - 248
CONSTRUCTION CHARACTERISTICS In accordance with EN 54-2 (panel) and EN 54-4 (power supply group)
EXTERNAL ENVIRONMENTAL
CONDITIONS -5 °C ±3 °C .... 40 °C ±2 °C, humidity max 93% not condensed.
BOX Metal painted with epoxy resin dust paint, degree of protection IP30,
dimensions: H420 x L500 x P210.
NOMINAL SYSTEM POWER VOLTAGE 230 V +10%/-15% ~ 50 Hz
MAXIMUM ABSORBED CURRENT < 300 mA.
SYSTEM OPERATING VOLTAGE min. 20,5V= max 30V=.
INTERNAL POWER SUPPLY GROUP:
MAIN POWER SUPPLY:
INPUT VOLTAGE 230 V +10%/-15% ~ 50 Hz
SAFETY TRANSFORMER 70VA.
TYPE Switching PWM with mains safety transformer.
NOMINAL OUTPUT VOLTAGE 27.5V (at 20°C, with batteries disconnected).
The output voltage is stabilized and balanced out in temperature, in
accordance with the features of battery recharging.
VOLTAGE RIPPLE < 100 mV PP
CURRENT AVAILABLE FOR 1.2A.
PANEL + EXTERNAL LOADS ÍNOTE: To guarantee autonomous working for 24h when there is no
mains power (battery power) refer to the consumption data listed in the next
section.
MIN/MAX OUTPUT VOLTAGE min=21V max=28.5V (output voltage available in different operating modes
for powering panel, external loads and battery recharge).
STAND-BY POWER SUPPLY:
TYPE 2 Pb type sealed batteries YUASA NP17-12 of 12V 17Ah.
CURRENT AVAILABLE FOR 700mA at 24V nominal .
PANEL + EXTERNAL LOADS (max. current available for panel and external loads to guarantee autonomy
WITHOUT MAIN POWER SUPPLY for 24h)
DURATION RECHARGING PERIOD 24h for 80%, 48h for 100% of nominal capacity.
RECOMMENDED REPLACEMENT 3 years.
PERIOD
POWER SUPPLY GROUP INPUT Battery test control input. Usually kept at ground. If on, it starts lowering the
voltage and leads to the batteries coming on, allowing them to be tested.

User and Installation Manual
ALPHA 16 - 248 GBR
Conventional Modular Fire Alarm
Control Panel
Document : MUALPHA16248GB
Index : A
Date : 26/03/07
Page : 5/49
POWER SUPPLY GROUP OUTPUT - Separate power supply outputs for panel/external loads and battery
recharge.
- Mains power signal output.
PROTECTION 1A T fuse on mains power input, 5A T fuse for battery protection, switching
regulator with thermal protection and current limitation.
BASIC I/O PANEL MODULE RAIK-A + RAIK-B (CPU A + CPU B):
ALARM OUTPUT - Balanced alarm output for powered sounder in accordance with EN54-2;
supplies 27.5V (nominal) max. 5A for alarm (for short periods). The balance
is obtained with end of line resistance of 4.7 Kohm ¼ W.
- Service alarm output, available on free power contact of 5A / 30V=.
- Service alarm output, with retractable positive. When in standby state, it
supplies voltage of 27.5V (nominal) which stops when the alarm comes on.
The maximum current which can be picked up from this output must be in
accordance with the specifications indicated for the power supply group.
The alarm outputs may be deactivated from the main panel using the
appropriate command key.
FAULT OUTPUT - Fault output on relay normally excited, can be selected as free contact N.C.
or N.A. able to commutate max 1A a 30V=.
The output may be deactivated from the main panel using the appropriate
command key.
PROGRAMMABLE OUTPUTS 1-6 Programmable electronic outputs 1-6. They repeat the state of the first 6
programmable outputs on the panel. Outputs 1-4 can be selected by jumpers
as an alternative to auxiliary inputs 1-4.
The outputs are usually open, close to negative if activated and can drive a
max. load of 0.2A at 30V=.
AUXILIARY OUTPUT Programmable auxiliary relay output available in free power contact from
5A 30V=.
CONTROL/COMMAND INPUTS Power system control input, supply ok/supply fault control input, supply fault
due to auxiliary panel control input, deactivation/external reset command
input, input for external 2nd access level activation (jumper).
AUXILIARY INPUTS 1-4 Auxiliary inputs 1-4, usable in panel programmable logic for controlling
personalised functions. They can be selected using jumpers as an alternative
to programmable local electronic outputs 1-4.
EXTENSION CONNECTIONS - SPI local bus for connection of input and output concentrator modules.
- Serial line available with interface RS232 and/or RS485 for connecting a PC
for control/setting.
SIGNALING COMPONENTS LED, alphanumeric display and buzzer to signal: states of operation,
functionality, power supply, deactivations, faults, alarms.
COMMAND COMPONENTS - Keys on panel always enabled for immediate function of stopping buzzer and
alarm.
- Keys protected by 2nd access level for functions of deactivation, reset, test
and stopping outputs.
- PC connected to local serial port, with /command software installed.
PROGRAMMING COMPONENTS - Display/LED/keys on panel active in configuration mode (protected at level 3,
can only be activated by opening the panel case).
- PC connected to local serial port, with CFGRAIK configuration software
installed.

User and Installation Manual
ALPHA 16 - 248 GBR
Conventional Modular Fire Alarm
Control Panel
Document : MUALPHA16248GB
Index : A
Date : 26/03/07
Page : 6/49
ACCESS LEVELS - Access level 1, always on. Access level 1 makes available all light displays,
the buzzer off command and immediate alarm command.
- Access level 2 can be activated by code or external key. It allows access to
reset command, stopping the outputs, deactivation and tests.
- Access levels 3,4, can be reached by opening the panel case and using
specific means/procedures. Use them for panel configuration operations.
ZONE/SECTOR/LINE CONTROL The panel can control up to a maximum of 32 zones/sectors for each of
which it makes available, through LED, the signalling of alarms, faults,
deactivation/tests. The lines can be freely linked with a single zone. Using
extension modules it can be reached an overall maximum of 248 collective
lines.
ÍNOTE:To meet the requirements of standard EN54-2 it should however
be taken into account that:
a) Each zone must not control a number of detector greater
than 32 (see UNI 9795/1999).
b) In consideration of the fact that the panel can run up to 248
collective lines and that every collective line can theoretically
run up to 32 detectors, bear in mind that the total number of
detectors connected to the panel must not be greater than
512.
INPUT COLLECTIVE CONCENTRATOR MODULES RAIK-I (EX8Z : 8 line expansion boards):
ÍNOTE: 2 modules RAIK-I are the default configuration on the ALPHA 16-248 panel.
INPUTS FOR DETECTORS 8 inputs for 27V two-wire lines with current consumption control and
balancing through 4.7Kohm ¼W end of line resistance.
TYPE/NUMBER OF DETECTORS RUN Max. 32 consumption detectors or 32 buttons N.A. with resistance
resistance FOR EACH LINE 680 ohm 1W limitation series .
The detectors must operate correctly in a range of voltages between 12V and
30V= inclusive and current consumption when standby less than 60µA.
LINE DETECTION THRESHOLDS Standby: min. 4 mA, max 8 mA.
Total consumption detectors + Prealarm, if programmed:
balancing at 27V - with dip sel. threshold OFF (see plans): min 12 mA, max 18mA
- with dip sel. threshold ON: min 21 mA, max 32 mA.
Alarm, if prealarm not programmed:
- with dip sel. threshold OFF (see plans): min 12 mA, max 60 mA
- with dip sel. threshold ON: min 21 mA, max 60 mA.
Alarm, if prealarm programmed:
- with dip sel. threshold OFF (see plans): min 21 mA, max 60 mA
- with dip sel. threshold ON: min 36 mA, max 60 mA.
Fault: <3 mA or > 65mA (fault if Vline < 3V).
CONNECTION TO THE PANEL The concentrator modules with 8 inputs can be connected to the panel by
SPI local bus.
OUTPUT CONCENTRATOR MODULES RAIK-U (EX8R: 8 ways relay module):
ÍNOTE: modules RAIK-U are optional modules.
OUTPUTS 8 relay outputs programmable in the panel or by PC with CFGRAIK software,
for repetition of signalling alarms, faults, panel operating states etc.
OUTPUTS MAX. LOAD The relay contacts can drive a maximum load of 5A at 30V.
CONNECTION TO PANEL The concentrator modules can be connected to the panel by SPI local bus.

User and Installation Manual
ALPHA 16 - 248 GBR
Conventional Modular Fire Alarm
Control Panel
Document : MUALPHA16248GB
Index : A
Date : 26/03/07
Page : 7/49
1-2 PANEL DEVICES CONSUMPTION TABLE:
Device: Description:
Nominal
consumption at 24V:
RAIK-A + RAIK-B +
RAIK-P
Base module with microprocessor + base module I/O + local control
panel, in standby state (only the supply ok LED on and backlighting of
display off).
135mA
RAIK-2L 96 LED panel to display 32 zones, in standby state (LED off). 15mA
RAIK-I (EX8Z)Input concentrator module with 8 collective lines, in standby state with
lines balanced. 65mA
RAIK-U (EX8R)8 relay output concentrator module + 8 electronic outputs, in standby
state with de-energized relays (each relay approx. 20 mA). 10mA
2- FIRE DETECTION MICROPROCESSOR PANEL
ALPHA 16 – 248 is a flexible panel, designed in accordance with the content of recent standards UNI EN 54-2, 54-4 for
conventional detection and signalisation of fires.
The internal structure of the panel consists of two input collective concentrator modules RAIK-I which are placed side by
side attached by DIN bar, electrically interconnected by flat cable.
Extra Input modules RAIK-I and/or output modules RAIK-U can be added to the same way to the panel allowing to
increase the number of lines and/or number of output programmable relays.
The expansion of the system is made by steps of 8 lines per module RAIK-I and/or 8 output relays per module RAIK-U.
This type of set-up gives the system notable qualities of compactness, flexibility, ease of extension and maintenance.
Thanks to the module system, the panels can be fitted and configured in the factory to meet the specific needs of the user
to a maximum of 248 conventional lines and/or 64 output relays.
2-1 MAIN CHARACTERISTICS:
The basic panel consists of:
a) Case: (H420 x L500 x P210).
Metal case with panel fitted on hinged front door (remove two screws to open) which can house,
besides the basic panel, 12 extension modules and 2 batteries type YUASA NP17-12.
b) Power supply AL224E with 27.5V 2A.
c) Basic module with microprocessor RAIK-A.
It uses flat cable connectors for connecting the local panel and input/output module. There are also connections for
linking to a PC for command//configuration or for modem link.
Module RAIK-A carries: panel firmware, configuration data and event memory.
d) Input/output module RAIK-B.
It uses terminal strips for connecting the alarm actuators and control devices.
The module also has the connector for power supply to the panel, power supply protection fuses, flat cable connector
for connection to the basic module and connector for connecting the extension modules (SPI local bus).
The module incorporates a 12V 1A switching voltage reducer for power supply to the 12V devices (local devices, etc.).
e) Locally-controlled panel RAIK-P, with general signal LED, control buttons and letter-number display with 16 x 2
characters. It is connected to module RAIK-A by flat cable.
The panel with 96 LED RAIK-2L to display the state of the panel zones/sectors is connected to the local panel by flat
cable.
f) Panel with 96 LED RAIK-2L to display states of alarm, faults, deactivation/tests for 32 panel zones/sectors.
As indicated in points a)-f), the basic panel has the following characteristics:
Inputs:
- Input for external command of DEACTIVATION/RESET panel.
- Input for power supply control and presence of mains power.
- Auxiliary inputs 1-4 for programmable logics (can be selected as an alternative to local programmable outputs 1-4).
- Input/output RS232 for connection of a PC for local /configuration or a modem.
- Input/output RS485 to use as an alternative to input RS232 for connection of a remote PC.

User and Installation Manual
ALPHA 16 - 248 GBR
Conventional Modular Fire Alarm
Control Panel
Document : MUALPHA16248GB
Index : A
Date : 26/03/07
Page : 8/49
Outputs:
- Balanced alarm output for powered sounders, with signalling of fault for cut/short circuit.
- Service alarm output available on free power contact and service alarm output with retractable positive.
- Positive safety fault output (relay normally charged) which can be selected as free contact N.C. or N.A.
- Aux programmable output available on free power contact.
- Programmable electronic outputs 1-6 (outputs 1-4 can be selected as an alternative to auxiliary inputs 1-4).
Light signals:
- Green LED to signal MAIN POWER SUPPLY OK.
- Yellow LED to signal general FAULT.
- Yellow LED to signal general DEACTIVATION.
- Red LED to signal general ALARM.
- Yellow LED to signal POWER SUPPLY FAULT, EARTH FAULT, SOUNDER FAULT, CPU FAULT, FUSE FAULT.
- Yellow LED to signal ALARM ACTIVATION DELAY.
- Yellow LED to signal DEACTIVATION SOUNDERS/GENERAL ALARM RELAY.
- Yellow LED to signal DEACTIVATION GENERAL FAULT RELAY.
- Green LED to signal 2ND ACCESS LEVEL ACTIVATED.
- Yellow LED to signal general TEST ACTIVATED.
- Yellow LED to signal BUZZER OFF FAULT/ALARM.
- Red LED to signal PREALARM/ALARM for each single zone.
- Yellow LED to signal FAULT for each single zone.
- Yellow LED to signal DEACTIVATION/TESTS for each single zone.
Alphanumeric display:
- 16 x 2 character alphanumeric display for auxiliary visualization of: panel's status, details of zones/sectors and lines
status, events and to control the stages of local configuration etc.
For each of the 248 lines and 32 zones/sectors, it is possible to configure a personalised message of 16 characters
which will be displayed on the relative panel.
Acoustic signals on piezoelectric buzzer:
- Continuous stoppable sound to signal FAULT/PREALARM/ALARM.
- Impulse sound for feedback pressing enabled keys.
Commands:
- Numerical keyboard + function keys to type in level 2 activation code to run selections of lines and zones/sectors,
special functions, to control the functions of specific deactivation/activation, for functions of set-up, display, LED test etc.
- Keys enabled at access level 2 for: MEMORY RESET, GENERAL ALARM RELAY ON/OFF, GENERAL FAULT RELAY
ON/OFF, ON/OFF TEST.
- Key to silence buzzer, activated when the buzzer sounds.
This function automatically reverses if the faulty condition which activated the buzzer returns.
The key allows the alarm output to be stopped at access level 2 if set at the configuration stage.
- IMMEDIATE ALARM key to annul delay and directly activate the alarm. It is always ready, but effectively only operates
when the alarm delay is being counted or when there is a state of stopped alarm output.
Expandability:
- A max. of 31 collective concentrators with 8 inputs (RAIK-l) can be run for a total of 248 individually controlled lines .
Each of the input lines of the collective concentrators can run a max. of 32 manual call points or conventional detectors
or single gas detection detectors.
ÍNOTE: Although it is possible to run up to 32 detectors per line and up to 248 lines, the total maximum number of
detectors run by the panel must not exceed 512, a limit imposed on the ALPHA 16-248 panel to conform with
standard EN54-2.
- Option of connecting up to a max. of 8 programmable relay modules (RAIK-U or EX8R) for a total of 64 programmable
outputs.
2-2 OPTIONAL EN54 FUNCTIONS CONTROLLED
- Option of running TEST of individual zones, activated from access level 2.
- Option of setting delay alarm controls for individual lines .
- Control of output stops (if applicable to the configuration).

User and Installation Manual
ALPHA 16 - 248 GBR
Conventional Modular Fire Alarm
Control Panel
Document : MUALPHA16248GB
Index : A
Date : 26/03/07
Page : 9/49
2-3 ACCESSORY FUNCTIONS CONTROLLED
- Control of 16x2 character alphanumeric display to show the details of the state of the panel, zones/sectors, lines , to
control the functions of deactivation/tests and zones, to display events and for the functions of local configuration.
- Control of serial port for connecting a PC for control//configuration.
- Control of an internal circular buffer which records the last 800 events in the panel (log). The events can be recalled and
displayed at level 2 both using the keypad/alphanumeric display.
- Control of logics programmable by user (functional blocks) to control the relay module outputs.
The programmable logics can be set at access level 3 using a PC and are configured using ‘functional blocks’ which
can be linked to the relay module physical outputs. The panel can run a maximum of 80 ‘functional blocks’, each of
which can be defined by type (AND/OR or AND threshold), can run up to 31 programming inputs, can use a timer for
activation or deactivation and can be put in cascade on other blocks (programming at several levels). All the main panel
resources are available as input conditions for the function blocks (state of lines, zones/sectors, general relays, auxiliary
inputs, time channels etc.).
The function blocks may also be used to control the deactivation/activation of the suitably programmed panel
zones/sectors.
- Internal clock/programmer with hour/week/year functions with control of holiday days and periods and automatic clock
change twice a year. It controls 8 time channels (bands) and up to 12 programmes for each day of the week. The eight
channels can be used in programming the ‘functional blocks’ to control the activation/deactivation of the panel zones in
different time bands.
- Option of enabling function of auto-reset of first alarm for each individual line (the alarm only comes on and activates the
actuators if it registers on at least two lines, or if it repeats twice on the same line within a certain time).
- Option of enabling the control of the prealarm threshold on each line (AND control of 2 alarms or prealarm control by
analog or consumption lines).
- Option of configuring ‘passive’ zones/sectors to control lines which do not activate the sounders in a state of alarm
(technological points).
- Option of activating access level 2 using electro-mechanical key (access level 2 is normally obtained by typing in a
code).
- Option of activating/deactivating the general state of being out of service (general disable) by external control of relevant
input.
2-4 POWER SUPPLY GROUP AL224E:
The panel has a power supply group which can supply a stabilized and temperature-compensated output voltage in
accordance with the characteristics of battery recharging (min20.5V, max 28.5V).
The power supply is switching PWM type with mains power decoupling through 70VA safety transformer and is
dimensioned to supply the panel, suitably charging the battery and supplying current to the external loads.
The maximum available current is 2A, of which 800mA are used for recharging the batteries and 1.2A are available for
powering the panel and external loads.
The power supply group is made in accordance with the requirements of EN54-4 and is constantly controlled by the
panel electronics to signal faults in cases of:
- battery cut or battery fuse fault
- inefficient battery
- inefficient battery recharge
- mains power supply voltage absent or irregular
The maximum battery capacity which can be run, in accordance with the content of standard EN54-4 (recharge to 80% of
nominal capacity in 24h and 100% in 48h) is 17Ah.
Power supply AL224E, if combined with control card SC1-24, can also be used as an autonomous device.
2-5 OPERATING AND CONFIGURATION SOFTWARE:
A series of software applications is available which makes it possible to carry out operations to configure and control the
panel using a PC.
The following applications are available:
CFGRAIK:
Panel configuration software.

User and Installation Manual
ALPHA 16 - 248 GBR
Conventional Modular Fire Alarm
Control Panel
Document : MUALPHA16248GB
Index : A
Date : 26/03/07
Page : 10/49
It can either work directly in line with the panel or on file and makes it possible to display, modify, print and save on disk
all the configuration details.
a) Configure the type and logic of lines and zones/sectors.
b) Configure the panel times.
c) Configure the panel options.
d) Modify/set personalized messages.
e) Set/program internal clock/programmer.
f) Program the functional blocks and associated programmable outputs.
ÍNOTE: The operations indicated in a),b),c) can either be manually carried out on the panel panel or by PC, while
the operations for points ,d),e),f) are only possible by PC.
2-6 BLOCK DIAGRAM ALPHA 16 - 248 :
B
U
S
L
O
C
A
L
E
S
P
I
1
2
5
3
LOCAL CONTROL PANEL + ZONE
LEDS PANEL
CONTAINER
POWER SUPPLY
RELAY: ALARM, FAULT, AUX PROGR.
PORT RS-232/RS485 FOR PC OR
MODEM
RAIK-I
(EX8Z)
RAIK-
A
7RAIK-P
COMMAND ABILITATION INPUT
INPUT FOR TOTAL BLOCK
RAIK
–
U
(EX8R)
6
8 CONVENTIONNAL LINES
MAX 248 INPUT LINES ON
LOCAL AND/OR REMOTE
CONCENTRATORS
(two modules on panel
Default configuration)
6 PROGRAMMABLE ELECTRONIC OUTPUTS
OR 2 OUTPUTS + 4 AUXILIARY INPUTS
RAIK-I
(EX8Z)
5
5RAIK-I
(EX8Z)
4RAIK-B
8RAIK-2L
AUX. POW ER SUPPLY FAULT INPUT
8 PROGRAMMABLE RELAY
OUTPUTS
6
6
RAIK-U
(EX8R)
RAIK-U
(
EX8R
)
MAX 64
PROGR.
OUTPUTS
(optionnal
modules)
8 PROGRAMMABLE RELAY
OUTPUTS
8 PROGRAMMABLE RELAY
OUTPUTS
CONFIGURATION INPUT
A
LPHA 16 - 248
A
L224E
8 CONVENTIONNAL LINES
8 CONVENTIONNAL LINES
Block diagram key:
1- CASE Metal case (H420 x L500 x P210). Contains all the main panel and power supply group
components.
It is made of metal covered in epoxy resin dust paint and has IP30 protection.
2- POWER SUPPLY Switching power supply module AL224E of 24V ,2A designed in accordance with UNI EN54-4.
3- RAIK-A Basic microprocessor module with 4K E²PROM, 32K RAM buffer, 128K EPROM, interface
RS232/RS485.
4- RAIK-B Basic I/O module with output relay, terminal strips for connection, SPI local bus interface
connector, panel power supply connector, panel protection fuses.
5- RAIK-I (EX8Z) Collective fire detection concentrator. It has 8 inputs for consumption, balanced two-wire.

User and Installation Manual
ALPHA 16 - 248 GBR
Conventional Modular Fire Alarm
Control Panel
Document : MUALPHA16248GB
Index : A
Date : 26/03/07
Page : 11/49
The module is connected locally to SPI bus. The panel runs a max. of 31 local RAIK-l
concentrators
(ALPHA 16 – 248 case can contain a maximum of 12 RAIK-I to a maximum number of lines up to
96 detection lines. To obtain the maximum total of 31 RAIK-I modules to a maximum of 248
detection lines a second metal case is required) .
6- RAIK-U (EX8R) Output concentrator with 8 output relays. The module is used for the programmable outputs and is
connected locally to SPI bus. The panel runs a max. of 64 programmable outputs (8 RAIK-U
modules )
7- RAIK-P Local panel control panel, with general signal LED, 16x2 character alphanumeric display and
command buttons.
The RAIK-2L module with 96 LED is connected to the local panel to signal the state of the zones
(total of 32 zones/sectors).
Through LED and buttons the panel runs all the signals and command functions provided for by
standard EN54. The alphanumeric display also makes it possible to visualize the individual
alarms/faults and system events.
8- RAIK-2L Panel with 96 LED to display state of 32 zones/sectors.

User and Installation Manual
ALPHA 16 - 248 GBR
Conventional Modular Fire Alarm
Control Panel
Document : MUALPHA16248GB
Index : A
Date : 26/03/07
Page : 12/49
3- DISPLAY AND COMMAND COMPONENTS:
3-1 MAIN DISPLAY/COMMAND PANEL:
The panel has a basic panel which houses all the compulsory signalling and command functions provided for by
standards UNI EN54-2 and 54-4.
Using the panel unit it is also possible to control the auxiliary command and display functions and control the configuration
of the panel (at access level 3).
The panel groups the signals and commands into three logical sections (see Fig.1):
The part on the left (A) houses all the general signals and commands, the central part (B), consisting of an alphanumeric
display and a keyboard, makes it possible to carry out detailed displays and control specific commands (display details,
control zone/line deactivation etc.), and finally the part on the right (C) displays the state of the 32 zones/sectors which
can be controlled from the panel.
Fig.1: Panel panel; logical layout of display and command components
Key:
1=LED for general state of panel 8=LED and button to silence buzzer
2=LED to signal specific faults 9=button for memory reset
3=LED and button to activate/deactivate alarm delay 10=button to annul delay and activate alarm
4=LED and button to activate/deactivate alarm output 11=alphanumeric display
5=LED and button to activate/deactivate fault output 12=keyboard for selection/command
6=LED to signal 2nd level enabled 13=LED for state of zones 1-32
7=LED and button to activate/deactivate test function
3-2 GENERAL SIGNALS AND COMMANDS
(Ref. fig.1, section 3-1)
= SYSTEM STATE LED; indicate the general state of the main panel functions, which are:
POWER SUPPLY OK LED
Permanently ON when the panel is powered by the main source (mains power on) and off when the panel is powered
by the stand-by source (battery). It flashes when the panel is powered by the main source but there is a fault on the
panel power supply group (inefficient battery or incorrect power supply voltage).
1
ALWAIS
ENABLED
KEY
S
Sounders
S
y
stem
Fuse
A
larm
Dela
y
Hooters
Sounders
locked
Fault
locked
Test
Enabled
Buzzer
off
Immediate
alarm
2° level
enabled
SYST EM
STAT US
14
SHOW
7
TEST LED
2
5
SELECT 8
0
3
6
LOCK
9
*
*
*
*
RESET
Gruond
Su
pp
l
y
ZONE
3
2
ZONE
31
ZONE
30
ZONE
29
ZONE
28
ZONE
27
ZONE
26
ZONE
25
ZONE
24
ZONE
23
ZONE
22
ZONE
21
ZONE
20
ZONE
19
ZONE
18
ZONE
17
ZONE
16
ZONE
15
ZONE
14
ZONE
13
ZONE
12
ZONE
11
ZONE
10
ZONE 9
ZONE 8
ZONE 7
ZONE 6
ZONE 5
ZONE 4
ZONE 3
ZONE 2
ZONE 1
FAULTS
ALARM
LOCK
FAULT
POWER.
SUPPLY
1 2
12
13
11
3 4 5
6
8
9
10
7
A BC

User and Installation Manual
ALPHA 16 - 248 GBR
Conventional Modular Fire Alarm
Control Panel
Document : MUALPHA16248GB
Index : A
Date : 26/03/07
Page : 13/49
FAULT LED
When ON, this indicates there is a fault in the panel and the corresponding output is on (apart from specific
deactivation).
The details on fault occurring are indicated by other LED on the panel and/or alphanumeric display.
LOCK (DEACTIVATION) LED
When ON, this indicates that there is a general state of deactivation in the panel (zones/sounders or another part
deactivated).
The details on deactivation may be displayed by other LED or may be visualized on the display by using the keyboard
when in access level 2.
ALARM LED.
When permanently ON, this indicates that there is a state of alarm in the panel and that the corresponding main
output is on (apart from specific deactivation).
If it flashes on for a long time and off briefly, it indicates that the alarm delay stage is in progress.
When the general alarm LED is ON, it is accompanied by one or more of the corresponding zone LED for the origins
of the alarm. The display also visualizes lines in the state of alarm.
= FAULTS LED; indicate specific panel faults as required by standards UNI EN 54-2 and 54-4, which are:
Power supply fault LED.
When permanently ON, it indicates that the panel power supply or supplementary power supply group (if applicable) is
irregular and that there is one of the following abnormal states:
- mains power lacking for more than 20 minutes
- output voltage of power supply is outside adjustment limits (<22.5V or >29.5V)
- the battery is disconnected or inefficient
- there is a fault on the battery recharge circuit
The flashing LED indicates that the power supply is regular but there has previously been an abnormal state
(memorized signal).
Earth fault LED.
When permanently ON, it indicates that there is a state of low isolation between one of the electric parts on the
system and earth. If it flashes, it indicates that the current state is regular but there has previously been an abnormal
state (memorized signal).
Sounders fault LED.
When permanently ON, it indicates that there is a fault on a balanced line which controls the alarm actuators
(sounders line balance not ok). If it flashes, it indicates that the current state of the line is regular but there has
previously been a state of fault (memorized signal).
System fault LED.
This can indicate different system faults, namely:
a) The panel microprocessor is temporarily or permanently out of control. This type of fault may be caused by strong
interference of an electrostatic nature, by a sudden drop in the power supply voltage or by a physical fault in the
panel card. In the latter case the signal can be stopped but not reset.
This type of fault, unless there is a serious physical card fault, is indicated on the display with one of the following
messages: CPU/MEMORY FAULT, WRONG CPU RESET FAULT.
b) One or more of the input or output concentrator modules are temporarily or permanently out of service. Also in this
case the fault may be caused by strong interference, by a sudden drop in the power supply voltage or by a physical
fault in the concentrator or communication line (short circuit/cut).
This type of fault can also be indicated on the display as INTERFAC.COMUNIC. FAULT and as a fault relative to the
zones linked to the concentrators out of service.
c) The content of the panel memory or firmware of an extension module has been altered.
In this case the display can visualise one of the following messages: WRONG CONFIGUR., MEMORY DATA ERR.,
CPU / MEM. FAULT.
2

User and Installation Manual
ALPHA 16 - 248 GBR
Conventional Modular Fire Alarm
Control Panel
Document : MUALPHA16248GB
Index : A
Date : 26/03/07
Page : 14/49
6
Fuse fault LED.
When ON, this indicates a fault in one of the panel fuses or extension modules.
A fuse fault is indicated on the display with the message: FUSES FAULT.
= Alarm delay LED and button
When the LED is ON, it indicates that the alarm delay function is on. In this situation, the occurrence of conditions for
activating the alarm starts, if set (relative Linesconfigured for delay function), the internal delay count after which the
alarm/sounder outputs are activated. On the contrary, when the LED is off, the alarm is activated immediately.
During the delay count, it is possible to annul the function and activate the alarm immediately by pressing the
IMMEDIATE ALARM key (10).
Press the ON/OFF button when in the 2nd access level (LED 6 on) to activate or deactivate the alarm delay function.
= Sounders locked LED and button
When the LED is ON, it indicates that the general alarm outputs have been deactivated.
Press the ON/OFF button when in the 2nd access level (LED 6 on) to deactivate the alarm outputs or reset them to
operating function.
= Fault locked LED and button
When the LED is ON, it indicates that the general fault output has been deactivated.
Press the ON/OFF button when in the 2nd access level (LED 6 on) to deactivate the output or reset it to operating
function.
= 2nd Level enabled LED
When ON, this indicates that 2nd access level has been activated, thus setting up the commands for reset,
deactivation, test and all the command functions which can be controlled from the keyboard when in level 2.
Level 2 can be activated by typing in the access code (see panel operating functions) or by using a mechanical key
(optional).
= Test enabled LED and button
When permanently ON, this LED indicates that the panel is in test mode (see panel operating functions).
On the contrary, if the LED flashes along with the deactivation LED (1), it indicates that the configuration stage is
activated on the panel.
To activate the test function, press the relative ON/OFF button when in access level 2 and then select the zones in
which the function is to be activated (the test can be activated for individual zones).
The test deactivates automatically by timeout or can be deactivated by pressing the ON/OFF button again.
= Buzzer/alarm off LED and button
The button is always ready (access level 1) and makes it possible to silence the buzzer after it has been activated
following a state of alarm or fault.
The relative LED comes on when an acoustic signal has been stopped.
The panel can be set so that this function also applies to the alarm and fault physical outputs in access level 2.
The function deactivates automatically after a reset.
= Reset button
This makes it possible to reset the memorized alarm/fault conditions but only works in access level 2.
The reset stage is timed and is indicated by the deactivation LED flashing and a message on the display.
3
4
5
7
8
9

User and Installation Manual
ALPHA 16 - 248 GBR
Conventional Modular Fire Alarm
Control Panel
Document : MUALPHA16248GB
Index : A
Date : 26/03/07
Page : 15/49
= Immediate alarm button
If pressed in access level 1or 2 with the alarm delay on, it immediately activates the outputs.
If pressed in access level 2 with the prealarm/alarm outputs stopped, they are reactivated.
3-3 ALPHANUMERIC DISPLAY AND KEYBOARD
(Ref. fig.1, section 3-1)
= 2 line x 16 character alphanumeric display + numerical command keyboard + function keys.
The display visualizes different information relating to the state of the panel and the command operations carried out.
In a standby state (level 2 not enabled and no alarm/fault present), a set message (which can be personalized) is
visualized on the top line of the display e.g.: > ALPHA 16 - 248 EN54 <
The bottom line displays the current time and date.
If a state of prealarm, alarm or fault occurs, the panel buzzer starts sounding and the general and/or zone LED relative to
the fault in course are ON.
At the same time the alphanumeric display shows the details of the fault in course and in the event of more than one state
present, these are displayed cyclically.
Relative to the alarms/faults originating from lines, the display visualizes the associated description on the first line (16
characters set by PC) and the number of the detectors and fault in course on the second line; e.g.: 001 alarm
When level 2 is not active (relative LED off), the keyboard can only be operated by typing in the access code (see
sections further on). When it is active however, different display and command operations can be carried out, in particular:
- Display the state of the lines, display the analog value and intervention thresholds.
- Display the state of the zones/sectors.
- Exclude/activate the Lines and zones.
- Activate/deactivate the test function on the zones.
- Display/modify the state of some special panel resources ( code, timer prog. etc.).
- Display and print the events (if connected to a serial printer).
- Carry out set-up of panel time and date.
- Carry out test of all LED for panel, display and buzzer.
In access level 3 (activated by opening the panel and inserting configuration jumpers) it is possible to display and set the
panel configuration with regard to lines, zones, times and operational options (programming the functional
blocks/programmable outputs and setting the internal timer programmer can only be carried out by PC using the
CFGRAIK application).
When access level 2 is enabled keys 4, 5, 6, 7 have a second function, namely:
- Key 4 (SHOW.) makes it possible to manually display any fault or deactivation conditions in the panel (the next state is
displayed by pressing the key).
If pressed when in a standby state (no state of alarm/fault and no deactivation present), key 4 has no effect.
- Key 5 (SELECT) makes it possible to select one of the panel devices (line or zone etc.) to display the state and carry
out deactivation operations.
Each time it is pressed, the display offers a selection of different categories, with the choice between: selection lines,
selection zones/sectors,
The selection is finished by setting the desired device number and typing in as many characters as there are dashes in
the displayed selection (e.g. 001 for line 1 or 01 for zone/sector 1).
After selection, the display shows the description and state of the device with which, if applicable, it will be possible to
carry out deactivation/activation operations using key 6 (see charter 5).
- Key 6 (DEACT.) only works after selecting a device using key 5 and makes it possible, if applicable, to deactivate or
activate it.
- Key 7 (TEST LED) makes it possible to test all the LED for the panel, buzzer and display.
Keys F1, F2, F3, F4 operate in access level 2 as follows:
- F1 : for access to MENU FUNCTIONS, selecting the next function each time the key is pressed as follows:
10
11 12

User and Installation Manual
ALPHA 16 - 248 GBR
Conventional Modular Fire Alarm
Control Panel
Document : MUALPHA16248GB
Index : A
Date : 26/03/07
Page : 16/49
ÆEVENTS SHOW ÆEVENTS PRINT ÆTIME/DATE ÆExit from menu
- F2, F3 : have different functions depending on the active menu selection.
- during display of events use F2 to select the next event (ADV) and F3 to select the previous one (BACK).
- during printing of events use F2 to set the NUMBER OF EVENTS TO PRINT
- in the clock menu F2 controls the function of SHOW CLOCK while F3 controls the SET CLOCK function.
See chapter 5 for details on the different command and display functions which can be controlled by keyboard and
display.
3-4 LEDS FOR STATE OF ZONES 1-32
(Ref. fig.1, section 3-1)
There are 3 LED on the panel unit for each of the 32 potential panel zones or sectors for displaying their state as required
by standard UNI EN 54-2.
The 3 LED are only active for the zones which have been configured on the panel (the LED for non-configured zones are
always off and only come on during the LED test) and respectively indicate the states of: FAULT, ALARM and
DEACTIVATION/TEST with the following meanings:
Zone fault yellow LED
When permanently ON, it indicates that the line associated with the zone is in a state of fault (inefficient detector,
corresponding line open/in short circuit, relative concentrator broken or off line).
If it flashes regularly, it indicates that the relative zone is currently in a standby state but previously registered a state of
fault (memorized signal).
The details of the lines which are causing or have caused the fault are visualized on the panel display.
Zone prealarm/alarm red LED
When permanently ON, it indicates that the line associated with the zone is in a state of alarm (state of smoke/fire
present).
If it flashes on for a long time and off briefly, it indicates that there is a state of prealarm in the zone. A state of prealarm is
activated when the established threshold is exceeded on a previously set line without reaching the alarm threshold (e.g.
alarm on an individual sensor on an consumption line.
If the zone prealarm/alarm LED flashes regularly, it indicates that the zone is in a standby state, but previously registered
a state of prealarm or alarm (memorized signal).
The details of the lines which are causing or have caused the prealarm or alarm are visualized on the panel display.
Zone lock or test yellow LED
When permanently ON, it indicates that the relative zone and therefore all the configured in it are deactivated (the panel
ignores alarms/faults in Lines and the zone).
If it flashes on for a long time and off briefly, it indicates that the zone is in TEST phase (the test is also signalled by the
relative general LED coming on and the display).
If it flashes regularly, it indicates that the zone is in the reset phase (temporary deactivation).
The states of deactivation/activation/zone test can be obtained by using the keyboard and display as shown further on.

User and Installation Manual
ALPHA 16 - 248 GBR
Conventional Modular Fire Alarm
Control Panel
Document : MUALPHA16248GB
Index : A
Date : 26/03/07
Page : 17/49
4- LINE AND ZONE CONTROL, OPERATING FUNCTIONS:
4-1 PANEL LINES AND ZONES; CONTROL LOGIC
The panel can control up to 32 logical zones/sectors to which 1 input lines can be freely associated during the
configuration stage.
ÍNOTE: To meet the requirements set by standard UNI EN 54-2, bear in mind that the total number of or buttons
associated with a zone must not be greater than 32.
The input lines, are physically controlled by two-wire consumption lines.
The panel reads the state of the system lines by communicating with the concentrator modules and receiving the relevant
information from them.
If one or more of the sensor is in a state of alarm or fault, the panel activates the corresponding state on the zones to
which the corresponding line of the detector have been linked.
Finally, based on the state of the zones, the panel controls the activation of the alarm and general fault outputs and the
main displays.
The following block diagram gives an example showing the acquisition and processing logic described above.
INPUT
CONCENTRATOR
RAIK-I SET UP FOR
CONTROL OF LINES
1 - 8
LOCAL/REMOTE BUS FOR
COMMUNICATION
CONCENTRATORS/UNIT
UNIT LOGIC
LINE 1
LINE 8
ACQUISITION
STATE OF
LINES 1 - 8
CONTROL OF
STATE OF
LINES ON
BASIS OF
CONFIGURA-
TION
ESTABLISHED
FOR EACH
ONE AND
PRESENCE OF
ANY
DEACTIVA-
TION
UPDATE STATE
OF ZONES 1-32
ON BASIS OF
STATE OF
LINES
CONTROL OF
ZONE STATE
ON BASIS OF
CONFIGURA-
TION
ESTABLISHED
FOR EACH
ONE AND
PRESENCE OF
ANY
DEACTIVA-
TION
COMMAND OF
ALARM/FAULT
ACTUATORS
CONTROL OF
DISPLAYS
CONTROL OF
ACTUATORS
AND GENERAL
DISPLAYS ON
BASIS OF ZONE
STATE,
CONFIGURA-
TION SET AND
PRESENCE OF
ANY
DEACTIVATION
COMMANDS
FOR
DEACTIVATION
AND CONTROL
Fig. 3: block diagram for panel acquisition and processing logic.
The panel zones are not controlled directly by an actual input panel but are rather an overall logic of physical lines
established in an arbitrary way during the configuration stage.
It is therefore theoretically possible, even if illogical and against the standard, to create zones which include lines coming
from different input concentrators which are located at distance.
ÍNOTE: It is not possible to link the same line to more than one panel zone.
Each individual panel line, regardless of the zone to which it has been linked, can also be set during the configuration
stage (access level 3) independently, on the basis of the type and logic of control it is to be submitted to.
To be precise, each individual line can be configured as follows:
- Delayable fire/gas: general fire detector, does not control the prealarm threshold and if the panel delay is on, it
activates the general alarm with the delay function.
- Instantaneous fire/gas: general fire detector, does not control the prealarm threshold and always activates the
general alarm immediately. Typical configuration for manual alarm buttons.
- Fire/gas with prealarm threshold: general fire or gas detector, controls prealarm threshold, and if the delay is on, it
activates the general alarm with the delay function. Typical configuration for gas detectors with 2 thresholds.
- Fire/gas with two prealarm thresholds: general fire or gas detector, controls two prealarm thresholds (only if
compatible with input concentrator module), and if the delay is on, it activates the general alarm with the delay
function.

User and Installation Manual
ALPHA 16 - 248 GBR
Conventional Modular Fire Alarm
Control Panel
Document : MUALPHA16248GB
Index : A
Date : 26/03/07
Page : 18/49
- Fire/gas with auto-reset of first alarm: general fire or gas detector, does not control the prealarm threshold and is
subject to the auto-reset logic of the first alarm (see paragraph 4-4). Typical configuration for smoke detector in
environments where false alarms are likely.
The zones (logical groups of lines, also defined as “sectors”) can also be configured independently and to be precise can
be set as follows:
- Fire/gas: type of general zone which follows the general panel logic. Typical configuration for fire/gas detectors.
- passive prealarm/alarm: zone on which the prealarms/alarms of the relative lines do not lead to the general relays
and buzzer being activated (unless otherwise set) or memorising, but to the activation of visual signals which remain
for as long as the cause of activation remains. Typical configuration for technological detectors.
- Fire/gas disable by functional block: type of zone which follows the general panel logic but can be deactivated if
the corresponding programmable logic is on. Typical configuration for fire/gas detectors which must be periodically
deactivated, for example in time bands.
- passive prealarm/alarm disable by functional block: behaves like the “passive prealarm/alarm” zone type, but can
be deactivated if the corresponding programmable logic is on. Typical configuration for technological detectors which
must be periodically deactivated, for example in time bands.

User and Installation Manual
ALPHA 16 - 248 GBR
Conventional Modular Fire Alarm
Control Panel
Document : MUALPHA16248GB
Index : A
Date : 26/03/07
Page : 19/49
4-2 PREALARM, ALARM AND FAULT:
The ALPHA 16 - 248 panel monitors and signals three panel states: PREALARM, ALARM, FAULT.
PREALARM:
It is activated if a reading is picked up by a detector configured to monitor this state.
For example the prealarm can be activated by:
- exceeding the first threshold on a gas detector.
- alarm on one detector on an consumption line.
ÍNOTE: If one of the indicated conditions occurs on a line which is not configured for prealarm control, the alarm is
activated directly.
The prealarm, unless configured otherwise, does not activate the general alarm outputs but only sets off an acoustic
signal, a special flashing of the LED for the corresponding zone (on for a long time, briefly off) and the display of the line
which caused the signal.
The panel does not have a physical output dedicated to prealarm, but it is possible to associate one of the programmable
outputs with it.
In the configuration stage (access level 3), it is possible to set the panel so that the alarm delay count (if applicable)
comes on following a prealarm, at the end of which the general outputs are activated.
ÍNOTE: If the zone associated with the line which caused the prealarm has been configured as “passive”, the
signals and general prealarm/alarm outputs are not activated.
ALARM:
It is activated if a reading is detected by one or more lines and triggers the activation of the general outputs (if not
deactivated by relative command) and specific signals. To be precise, the panel buzzer comes on, the corresponding
zone LED is ON permanently and the general alarm LED is ON.
If the detector has been configured as “delayable” and the general delay function is on, the alarm outputs are not
activated immediately but follow the period set.
ÍNOTE: If the zone associated with the which caused the alarm has been configured as “passive”, the signals and
general outputs are not activated and only information relating to the detector and zone is displayed.
FAULT:
This can originate from different conditions: faults due to lines, faults on communication lines, loss of isolation at earth,
broken fuse, malfunction of a power supply panel, malfunction caused by interference, electrical problems in panel
components.
The different types of fault are shown by corresponding yellow LED coming on and specific messages which appear on
the display. The faults which directly relate to a line (e.g. short circuit of an consumption detection line) lead to the fault
LED being ON for the zone to which the detector is associated.
In the event of a fault, the panel buzzer, general signalling and relevant output are also activated (if not deactivated by
specific command).
If the general fault LED is permanently on, it indicates the active presence of a fault, while if it flashes it indicates a
memorized condition (fault no longer present).
4-3 FUNCTION OF DELAYED ALARM:
The panel has a function that puts a delay on the activation of general alarm outputs following an alarm signalled by lines.
ÍNOTE: The alarm delay only applies to general outputs; optical and acoustic signals on the panel unit are activated
immediately.
For the delay function to work, individual lines (not zones/sectors) must be set accordingly during the configuration stage.
The alarm delay LED on the panel unit must also be on, showing the delay function is activated (the delay function can be
activated/deactivated in access level 2 using the relevant ON/OFF key).
The activation of the alarm delay time is indicated by the general alarm LED flashing. It is ON permanently as soon as the
count finishes and the outputs are activated.
During the alarm delay stage it is possible to stop the function and instantly activate the outputs by pressing the
Immediate alarm key.
ÍNOTE: Pressing the immediate alarm key in access level 2 when the prealarm/alarm outputs are stopped, the latter
are immediately reset.

User and Installation Manual
ALPHA 16 - 248 GBR
Conventional Modular Fire Alarm
Control Panel
Document : MUALPHA16248GB
Index : A
Date : 26/03/07
Page : 20/49
ÍNOTE: Alarms originating from lines configured as instant do not trigger the alarm delay count but immediately
generate the activation of the outputs.
4-4 FUNCTION OF FIRST ALARM AUTO-RESET:
At the configuration stage it is possible to set the lines for the function of auto-reset of the first alarm.
Auto-reset of the first alarm is a filter function which makes it possible to ignore suspect alarm conditions.
The auto-reset logic is as follows:
a) If an alarm condition is detected by a detector on a line set for auto-reset, it does not trigger the alarm in the
corresponding zone but activates an internal delay of 3 seconds.
b) If an alarm condition is detected in this period by another detector, it is recognised by the panel as true (AND of two
alarms generate the true alarm).
On the contrary, at the end of the 3 seconds, the panel activates the auto-reset of the lines for a few seconds (reset
time programmed during configuration), thus allowing the physical reset of the line which caused the starting condition.
ÍNOTE: The auto-reset does not cancel any signals of alarm/fault previously memorized on the panel LED and
display, but in any case intervenes at a global level, temporarily removing the power supply from all panel
consumption lines to allow the physical reset.
c) After the auto-reset time, the panel starts a 5-minute internal count.
If another state of alarm occurs during this time on any line (including the one which caused the starting condition), the
panel triggers a true alarm and starts the 5-minute internal count again. On the contrary, at the end of this period, the
alarm filter function is reset as in point a).
4-5 TEST ZONE FUNCTION:
The TEST function makes it possible to try out the system without activating the alarm actuators.
On the ALPHA 16 - 248 panel, the test can also be activated for individual zones, as required by UNI EN54-2.
To activate/deactivate the test function press the ON/OFF button beside the ‘Test enabled’ LED when in access level 2
(the test mode state is indicated by the LED coming on and a message on the display). The individual zones to be tested
(see section 5-7) must then be selected using the numerical keyboard and display and confirmed with key 9. If key 9 is
pressed without selecting a zone, the test is activated globally across all zones.
The zones are being tested when the yellow LOCK/TEST LED flash on and off (the on time is longer than off time).
All alarms originating from lines which are controlled by zones selected for testing are treated by the panel with the
following logic:
a) The panel buzzer is activated.
b) Each alarm is signalled on the display and memorized on the relative zone LED.
c) A few seconds after an alarm is activated, the panel carries out an automatic reset of the detector lines without deleting
the memory on the LED/display.
ÍNOTE: The zones not selected for testing remain fully operational and in the event of an alarm activate the relative
signalling/command components (sounders).
The test function deactivates automatically after 30 minutes if no command operations are carried out, or can be instantly
deactivated by pressing the ON/OFF button again located next to the Test enabled LED.
ÍNOTE: While the test function is on, access level 2 also remains on.
5- COMMAND FUNCTIONS:
5-1 OPERATING LEVELS AND 2nd ACCESS LEVEL ACTIVATION:
As provided for by standard UNI EN 54-2, the panel controls several operating levels for carrying out command and
configuration operations.
The operating levels follows:
- Level 1 (commands not enabled):
The most basic operating level, always ready and intended for the public or those who have general surveillance duties.
Table of contents