UniPOS FS5200 User manual

Fire Control Panel
FS5200
INSTRUCTION MANUAL
Revision 8/07.17

UniPOS Fire Control Panel FS5200
Instruction manual Page 2
Revision 8/07.17 of 69
Content
1. Introduction...................................................................................................................................5
2. Terminology...................................................................................................................................5
3. Function.........................................................................................................................................7
4. Technical data ...............................................................................................................................7
4.1. Modules................................................................................................................................................7
4.1.1. Type of modules.............................................................................................................................................7
4.1.2. Basic module..................................................................................................................................................7
4.1.3. Additional module..........................................................................................................................................7
4.2. Physical configuration.........................................................................................................................8
4.3. Fire alarm lines....................................................................................................................................9
4.4. Controllable outputs............................................................................................................................9
4.5. Common purpose relay outputs.........................................................................................................9
4.6. Relay output for fault conditions.......................................................................................................9
4.7. Performance.........................................................................................................................................9
4.8. Indications of registered events........................................................................................................10
4.9. Power supply......................................................................................................................................10
4.9.1. Mains............................................................................................................................................................10
4.9.2. Backup batteries...........................................................................................................................................10
4.9.3. Consumption on backup batteries supply.....................................................................................................10
4.9.4. Power supply to external devices.................................................................................................................10
4.10. Dimensions.......................................................................................................................................11
4.11. Weight ..............................................................................................................................................11
5. Contents of delivery.....................................................................................................................11
5.1. Fire control panel ..............................................................................................................................11
5.2. Additional module.............................................................................................................................11
5.3. Module 5201.......................................................................................................................................11
5.4. Module 5203 or 5204.........................................................................................................................11
6. General information....................................................................................................................11
6.1. Access levels.......................................................................................................................................11
6.1.1. Access level 1...............................................................................................................................................11
6.1.2. Access level 2...............................................................................................................................................12
6.1.3. Access level 3...............................................................................................................................................12
6.1.4. Access level 4...............................................................................................................................................12
6.2. Indications and buttons for control.................................................................................................12
6.3. Function Logical AND of two lines...................................................................................................12
6.4. Conditions of the fire control panel.................................................................................................15
7. Duty Mode....................................................................................................................................15
7.1. Description.........................................................................................................................................15
7.2. Indication ...........................................................................................................................................15
7.2.1. LED and sound indication............................................................................................................................15
7.2.2. Text message................................................................................................................................................15
7.3. Using the keypad...............................................................................................................................15

UniPOS Fire Control Panel FS5200
Instruction manual Page 3
Revision 8/07.17 of 69
8. Fire condition ..............................................................................................................................15
8.1. Description.........................................................................................................................................15
8.2. Indication ...........................................................................................................................................16
8.2.1. LED and sound indication............................................................................................................................16
8.2.2. Text message................................................................................................................................................16
8.3. Using the keypad...............................................................................................................................17
9. Pre-Fire condition.......................................................................................................................18
9.1. Description.........................................................................................................................................18
9.2. Indication ...........................................................................................................................................18
9.2.1. LED and sound indication............................................................................................................................18
9.2.2. Text message................................................................................................................................................18
9.3. Using the keypad...............................................................................................................................18
10. Fault condition ..........................................................................................................................19
10.1. Description.......................................................................................................................................19
10.2. Indication .........................................................................................................................................20
10.2.1. LED and sound indication..........................................................................................................................20
10.2.2. Text messages ............................................................................................................................................20
10.3. Using the keypad.............................................................................................................................23
11. Disabled Component Mode.......................................................................................................23
11.1. Description.......................................................................................................................................23
11.2. Indication .........................................................................................................................................24
11.2.1. LED and sound indication..........................................................................................................................24
11.2.2. Text messages ............................................................................................................................................24
11.3. Using the keypad.............................................................................................................................24
12. Test Mode...................................................................................................................................24
12.1. Description.......................................................................................................................................24
12.2. Indication .........................................................................................................................................24
12.2.1. LED and sound indication..........................................................................................................................24
12.2.2. Text messages ............................................................................................................................................24
12.3. Using the keypad.............................................................................................................................25
13. Information and Control Mode.................................................................................................25
13.1. Description.......................................................................................................................................25
13.2. Menu Faults.....................................................................................................................................26
13.3. Menu Disabled components.............................................................................................................26
13.4. Menu Lines in test............................................................................................................................27
13.5. Menu Status......................................................................................................................................27
13.6. Menu Pre-Fire condition.................................................................................................................28
13.7. Menu System functions....................................................................................................................28
13.7.1. Function LED and sound indicators check up ...........................................................................................28
13.7.2. Menu Current in fire alarm lines ...............................................................................................................29
13.7.3. Menu Mode ................................................................................................................................................29
13.7.4. Menu Setting the clock...............................................................................................................................29
13.7.5. Menu Fire alarm lines test.........................................................................................................................31
13.7.6. Menu Disable fire alarm lines ...................................................................................................................31
13.7.7. Menu Disable controllable outputs............................................................................................................32

UniPOS Fire Control Panel FS5200
Instruction manual Page 4
Revision 8/07.17 of 69
13.7.8. Menu Parameter review.............................................................................................................................32
13.7.9. Menu Set Parameters.................................................................................................................................36
13.7.10. Menu Archive review ...............................................................................................................................36
14. SetUp Mode................................................................................................................................38
14.1. Description.......................................................................................................................................38
14.2. Access to SetUp Mode.....................................................................................................................39
14.3. Menus ...............................................................................................................................................40
14.3.1. Menu Line parameters...............................................................................................................................40
14.3.2. Menu Fire control panel parameters .........................................................................................................43
14.3.3. Menu Adjustment of controllable outputs ..................................................................................................44
14.3.4. Menu Adjustment of relay outputs..............................................................................................................44
14.3.5. Function Default parameters .....................................................................................................................45
14.3.6. Function Clear archive ..............................................................................................................................45
14.3.7. Function Enter new password....................................................................................................................46
15. Remote Control Mode................................................................................................................46
15.1. Description.......................................................................................................................................46
15.2. Indication .........................................................................................................................................46
15.2.1. LED and sound indication..........................................................................................................................46
15.2.2. Text message..............................................................................................................................................46
15.3. Using the keypad.............................................................................................................................46
16. Saving the parameters...............................................................................................................46
17. Labour protection requirements ...............................................................................................47
18. Installation and arrangements..................................................................................................47
18.1. To mount the fire control panel .....................................................................................................47
18.2. Periphery devices assembly............................................................................................................47
18.2.1. Mounting periphery devices to controllable outputs..................................................................................47
18.2.2. Mounting periphery devices to relay outputs .............................................................................................47
18.3. Connecting interface units..............................................................................................................47
18.4. Connecting fire detectors................................................................................................................48
18.5. Connection to power supply...........................................................................................................48
19. Fire control panel start up ........................................................................................................48
20. Change in fire control panel configuration .............................................................................49
20.1. How to add or remove Additional Module....................................................................................49
20.2. Change in Basic Module .................................................................................................................49
20.3. Changes in Additional Module.......................................................................................................50
21. Troubleshooting.........................................................................................................................51
22. Conditions of operation, storage and transportation...............................................................53
22.1. Operation and storage.....................................................................................................................53
22.1.1. Temperature ...............................................................................................................................................53
22.1.2. Relative humidity.......................................................................................................................................53
22.2. Transportation.................................................................................................................................53
23. Warranty....................................................................................................................................53
24. Appendixes.................................................................................................................................54

UniPOS Fire Control Panel FS5200
Instruction manual Page 5
Revision 8/07.17 of 69
1. Introduction
Fire Control Panel FS 5200 is a modern, highly reliable, multifunctional and versatile unit,
providing the user with unexpected potential in the design, installation and operation of conventional
fire alarm systems.
Some of its main features and possibilities are:
Adjustment of operating modes and parameters of each fire alarm line via built in keypad;
User oriented menu dialogue for easy and convenient operation;
LCD for visualization of system checkup and setup modes;
LEDs indication for early warning of a break down or extreme conditions;
Ability to address automatic fire detectors and manual call points in groups;
Energy independent archive memory saving the event type, date and time, allowing for
detailed analysis of the actions of the authorized personnel and of possible problems in the
fire protection process of the area;
User oriented test modes allowing for a total control of the site protected;
Built-in serial interface for connection to second level control devices, ability for connection via
telephone line and standard modem;
System expansion and functional modification (our goal is discontinuous improvement of the
fire alarm equipment features), no additional cabling necessary;
Compatible to random installation design, within the range of fire control panels resources.
All these are realizable via fire control panel’s keypad and after a detailed examination of the
instructions set herewith.
2. Terminology
ACCESS LEVEL –access level to various indications and control functions (see section 6.1).
ASSOCIATED OUTPUT –controllable or relay output, programmed by user to react (separately
in Fire condition I and Fire condition II) in Fire condition via selected fire alarm line.
CONTROLLABLE OUTPUT –potential output that monitors the serviceability of the connection
wires between the fire control panel and the executing device. Follow the special diagram for
connection (Appendix 5 c).
DISABLED CONTROLLABLE OUTPUT –the controllable output is switched off (executing
devices can not be activated) and is not monitored for a fault condition. This feature is user defined.
The indication for a disabled controllable output includes common light indication and text messages
on the LCD display.
DISABLED LINE –a switched off line, without power supply, not controlled for activated fire
detectors and fault condition. This condition is user defined. The indication for a disabled line includes
common light indication and text messages on the LCD display.
FATAL FAULT CONDITION –fault condition that does not allow the fire control panel or the part
providing communication with the user, to continue operation. The fatal fault condition is a System
fault, except for Battery Low. The indication is common light indication, local sound indication and text
messages on the LCD display.
FIRE ALARM LINE (further on it will be referred as LINE) –a combination of automatic fire
detectors and manual call points, physically connected by the means of two-wire connection. The
basic configuration of FS 5200 includes 8 lines; the maximum configuration includes 32 lines. Up to
32 fire detectors can be integrated into one line.

UniPOS Fire Control Panel FS5200
Instruction manual Page 6
Revision 8/07.17 of 69
FIRE CONDITION STAGE I –upon activation of automatic fire detector the fire control panel
enters Fire condition, phase Fire condition stage I until the defined time expires. The common and
local light indicators, local sound signaling and a text message displayed on the LCD display indicate
the phase.
FIRE CONDITION STAGE II –the fire control panel enters Fire condition, phase Fire condition
stage II when: a) the time for Fire condition stage I has expired or b) upon activation of a manual call
point. The common and local light indicators, local sound signaling and a text message displayed on
the LCD display indicate the phase.
FUNCTION “LOGICAL AND” OF TWO LINES – function that allows the fire control panel to enter
Fire condition stage I in two lines upon simultaneous activation of automatic fire detectors (see
section 6.3)
GROUNDS –non-system non-fatal fault condition, due to leakage to a grounded wire.
GROUP ADDRESSING –fire control panel’s ability to make a difference between activation of
automatic fire detector and manual call point, which are in one and the same fire alarm line. For this
purpose the manual call points’ current consumption value shall exceed the threshold value for Fire
condition stage II.
INSPECTION TIME –period of time added to the remaining time, before the system proceeds
from Fire condition stage I to Fire condition stage II, when button is pressed. Usually, this
period of time is long enough for the authorized personnel to check up the indicated premises. The
inspection time is user defined and is equal for all fire alarm lines. Light indicators show adding a
period of time for inspection.
INTERRUPTED LINE OR CONTROLLABLE OUTPUT –non-system non-fatal fault condition due
to current value in a line or in a controllable output lower than the threshold value. The user shall
define the threshold value separately for each line.
LINE IN TEST –line set by the user to Test condition. The line is powered and reset (the power is
cut off for 3 s) periodically every 64 s. The events registered in a line in Test condition are not saved
in the archive and do not trigger the associated outputs nor the light and sound signaling. The
indication for a line in Test condition is common light indication.
LINE STATUS OR CONTROLLABLE OUTPUT STATUS –current status of a line or a
controllable output: normal status; fire conditions stage I or II (for a line only); fault condition and its
type.
LOCAL SOUNDER - sounder built-in the fire control panel.
LOW BATTERY –non-system fatal fault condition due to full discharge of the backup batteries
upon interrupted power supply.
NEW CONFIGURATION –a system fatal fault condition due to detected conflict between the
current physical configuration and the configuration saved in the memory. Usually it occurs when a
module has been added, removed or replaced. In such case adjust the settings in the fire control
panel.
NON-FATAL FAULT CONDITION –fault condition that allows the fire control panel to continue
operation. A non-fatal fault condition is usually a non-system fault condition. The indication is common
light indication, local sound indication and text messages on the LCD display.
PRE-FIRE CONDITION –condition of the fire control panel used by the function Logical AND of
two lines to provide control over simultaneous response of automatic fire detectors in the lines. (see
section 6.3 )

UniPOS Fire Control Panel FS5200
Instruction manual Page 7
Revision 8/07.17 of 69
PROCEEDING FROM FIRE CONDITION STAGE I TO FIRE CONDITION STAGE II –the time is
user defined for each fire alarm line separately. During the phase Fire condition stage I the remaining
time for the selected fire alarm line is indicated on the LCD display. During the remaining time actions
can be taken, for example press or .
RELAY OUTPUT –relay, potential free, switching outputs that control external executive devices.
REMOVED FIRE DETECTOR –non-system non-fatal fault condition due to removed fire detector
in a line. To use this function, the fire detectors shall be connected as in Appendix 5 a.
SHORT CIRCUIT IN A LINE OR IN A CONTROLLABLE OUTPUT –non-system non-fatal fault
condition due to registered current value in a line or in a controllable output that exceeds a specified
threshold value. The threshold value for each line shall be user defined.
SUPRESSED OUTPUT –controllable or relay output which should normally be activated (the fire
alarm line is in the relevant phase Fire condition) but is manually switched off by the user.
SYSTEM FAULT –fatal fault condition due to a fault in a basic component of the fire control panel
(or system). The System fault may be a fatal error or a non-fatal error. The event is indicated by
common light indicators, local sound signaling and a text message displayed on the LCD display.
SYSTEM OPERATION –the fire control panel executes internal operations to set its registers.
This is visualized on the LCD display with a text message for system operations, before the user is
allowed to proceed with his work with FS 5200.
3. Function
Fire control panel FS5200 is designed to operate with conventional automatic fire detectors and
manual call points. The panel has outputs provided for external executive devices. Its modular
structure allows for variable configurations according the specific features of the protected site
4. Technical data
4.1. Modules
4.1.1. Type of modules
Basic module
Additional module
Power supply module
4.1.2. Basic module
Basic module
(Circuit Board 5200Basic and 5200Indication) - 1 controllable output
- 2 relay outputs for fire condition
- 1 relay output for fault conditions
Expansion
Module 5201 - 8 lines
Module 5203 - 8 relay outputs for fire condition
Module 5204 - 16 relay outputs for fire condition
Note: The Basic Module can not be expanded with Module 5203 and Module 5204 at the same
time –you may insert only one of them.
4.1.3. Additional module
Module 5202 - 8 lines
- 1 controllable output
Expansion
Module 5201 - 8 lines

UniPOS Fire Control Panel FS5200
Instruction manual Page 8
Revision 8/07.17 of 69
4.2. Physical configuration
Configuration
Modules
Technical data
Basic
Additional
Basic Module
Module 5201
Module 5203
Module 5204
Module 5202
Module 5201
00
(Configuration
minimum)
х
8 lines
2 relay outputs for fire condition
1 controllable output
1 relay output for fault condition
01
х
х
8 lines
10 relay outputs for fire
condition
1 controllable output
1 relay output for fault condition
02
х
х
8 lines
18 relay outputs for fire
condition
1 controllable output
1 relay output for fault condition
03
х
х
16 lines
2 relay outputs for fire condition
1 controllable output
1 relay output for fault condition
04
х
х
х
16 lines
10 relay outputs for fire
condition
1 controllable output
1 relay output for fault condition
05
х
х
х
16 lines
18 relay outputs for fire
condition
1 controllable output
1 relay output for fault condition
06
х
х
х
24 lines
2 relay outputs for fire condition
2 controllable outputs
1 relay output for fault condition
07
х
х
х
х
24 lines
10 relay outputs for fire
condition
2 controllable outputs
1 relay output for fault condition
08
х
х
х
х
24 lines
18 relay outputs for fire
condition
2 controllable outputs
1 relay output for fault condition

UniPOS Fire Control Panel FS5200
Instruction manual Page 9
Revision 8/07.17 of 69
Configuration
Modules
Technical data
Basic
Additional
Basic Module
Module 5201
Module 5203
Module 5204
Module 5202
Module 5201
09
х
х
х
х
32 lines
2 relay outputs for fire condition
2 controllable outputs
1 relay output for fault condition
10
х
х
х
х
х
32 lines
10 relay outputs for fire
condition
2 controllable outputs
1 relay output for fault condition
11
(Configuration
maximum)
х
х
х
х
х
32 lines
18 relay outputs for fire
condition
2 controllable outputs
1 relay output for fault condition
All configurations include Power Supply Module.
Per customer request Interface Module and Modem Supply Module can be included in each
configuration.
4.3. Fire alarm lines
Maximum number of fire detectors in a line - 32
Connecting line - two-wire
Maximum resistance of a line - 100
Output resistance of a line - 164
4.4. Controllable outputs
Type - potential
Electrical characteristics - (24±5)V/500mA
4.5. Common purpose relay outputs
Type - potential free, switching
Electrical characteristics - 3A/125VAC; 3A/30VDC
4.6. Relay output for fault conditions
Type - potential free, switching
Electrical characteristics - 3A/125VAC; 3A/30VDC
4.7. Performance
Control over fire alarm lines and controllable outputs for fault conditions (short circuit and
interruption) and automatic reset.
Detection of removed fire detector and automatic reset.
Ability to set the lines in dependency of the function “Logical AND”
Group addressing of manual call points and automatic fire detectors
Two phases of Fire condition, programmable time for Fire condition stage I, separately
for each line

UniPOS Fire Control Panel FS5200
Instruction manual Page 10
Revision 8/07.17 of 69
Option to prolong the time period for Fire condition stage I with programmable overall
inspection period
Built-in sounder for fire condition –one tonal, continuous, can be switched off
Built-in sounder for fault condition –one tonal, discontinuous, can be switched off
Built-in real time clock
Set of test modes and options for adjustment :
Setting the clock;
Check up of light and sound indications;
Test of fire alarm lines;
Adjustment of outputs and the integrated external devices;
Measuring the current value in the fire alarm lines;
Programming of parameters and modes of operation;
Remote programming of the parameters from a distant operator control point.
Energy independent archive of registered events with the events type, date and hour –
up to 2500 events
Communication interface for external devices - RS-232 (directly or via modem) or RS-
485.
4.8. Indications of registered events
Light indication - LED
Text messages - LCD display -
4 lines x 20 symbols each,
Latin/Cyrillic characters, backlit
Sound - built-in sounder
4.9. Power supply
4.9.1. Mains
voltage - 220/230V
frequency - 50Hz
4.9.2. Backup batteries
battery type - lead, gel electrolyte
number of batteries - 2 pcs
connection - serial connection
nominal voltage of the backup battery - 24V
nominal capacity C20 - 12Ah
extreme discharge voltage - 21V
charge voltage - 28,2V
4.9.3. Consumption on backup batteries supply
Configuration 00 - < 155mA at 24V
- < 150mA at 26V
Configuration 03 - < 235mA at 24V
- < 225mA at 26V
Configuration 06 - < 320mA at 24V
- < 305mA at 26V
Configuration 09 - < 400mA at 24V
- < 380mA at 26V
4.9.4. Power supply to external devices
voltage - (24±5)V
maximum current value (including current
of controllable outputs) - 1,5А

UniPOS Fire Control Panel FS5200
Instruction manual Page 11
Revision 8/07.17 of 69
4.10. Dimensions
dimensions - 450х355х115mm
4.11. Weight
Backup batteries not included - 6,6kg
5. Contents of delivery
5.1. Fire control panel
Fire control panel FS5200 - 1 pc
Resistors 3,9k/ 0,25W - 8 pcs
Resistors 5,6k/ 0,25W - 1 pc
Jumper for the backup batteries - 1 pc
Fuse 4A - 2 pcs
Instruction manual - 1 pc
Instruction for the authorized staff - 1 pc
Packing - 1 pc
5.2. Additional module
Additional module - 1 pc
Ribbon cable - 1 pc
Earthing cable - 1 pc
Resistors 3,9k/ 0,25W - 8 pcs
Resistor 5,6k/ 0,25W - 1 pc
Special nut - 1 pc
Packing - 1 pc
5.3. Module 5201
Module 5201 - 1 pc
Resistors 3,9k/ 0,25W - 8 pcs
Screw М3 - 2 pcs
Plain washer М3 - 2 pcs
Spring lock washer М3 - 2 pcs
Packing - 1 pc
5.4. Module 5203 or 5204
Module 5203 or 5204 - 1 pc
Screw М3 - 2 pcs
Plain washer М3 - 2 pcs
Spring lock washer М3 - 2 pcs
Packing - 1 pc
6. General information
6.1. Access levels
There are 4 levels of access to the variable indications and control functions of FS5200.
6.1.1. Access level 1
All persons who would presumably find out and react to alarm for fault condition or fire condition
have access to level 1.
The following features are accessible:
Displaying suppressed messages for Fire condition, Pre-fire condition, Fault condition
and Disabled components (see sections 8, 9, 10 and 11);
Entering inspection time period (see section 8);
Forced proceeding from phase Fire condition stage I to phase Fire condition stage II (see
section 8);
Suppressing the local sounder (see sections 8, 9 and 10);
Displaying the status of the lines and of the controllable outputs (see section 13).
All light indicators are visible.

UniPOS Fire Control Panel FS5200
Instruction manual Page 12
Revision 8/07.17 of 69
6.1.2. Access level 2
Level 2 is for the personnel in charge for the fire protection; they shall be trained and authorized
to operate the fire control panel in the following conditions:
Duty Mode;
Fire condition;
Pre-Fire condition;
Fault condition;
Disabled component;
Information and adjustment.
To enter Access level 2, insert the key into the front panel in position .
The following features of the fire control panel are accessible:
All features accessible at Level 1;
Switching off the outputs, activated upon fire condition (see sections 8, 9 and 10);
Exit of Fire condition (see section 8);
System functions of the fire control panel without entering SetUp Mode (see section 13).
6.1.3. Access level 3
Accessible for personnel trained and authorized to:
Reconfigure specific data –of the protected site or of the fire control panel –saved in the
memory;
Maintain the fire control panel.
This level has two sublevels of access - 3A and 3B.
Level 3, sublevel 3A, is accessed through a password, entered at Access level 2. At this sublevel
the functions for reconfiguration of specific data for the protected site or the fire control panel are
accessible (see section 14).
Level 3, sublevel 3B is accessed when the fire control panel is opened. The following features are
accessible:
Replacing a burnt fuse;
Adding, removing and replacing a module;
Connecting fire alarm lines and executive devices.
6.1.4. Access level 4
Accessible for personnel trained and authorized by the Producer to repair the fire control panel
and to modify the software. Special means are required for access to this level.
6.2. Indications and buttons for control
Table 1 gives detail description of the indications for each status, Table 2 presents the basic
means for control. Appendix 1 shows the front panel of Fire control panel FS5200 with its visual
system for indication and control.
6.3. Function Logical AND of two lines
The function Logical AND gives the opportunity to set the following dependence between two
lines in one and the same module (Basic module or Additional module): the fire control panel will
enter Fire condition, phase Fire condition stage I, in each of the line (or in both of them) upon
activation of fire detectors in both lines.
The function does not affect manual call points. Upon activation of a manual call point (value of
the line current between Fire condition stage II and Short circuit) in a line, dependent on function
“Logical AND”, the fire control panel will enter Fire condition stage II in this line.
Upon activation of automatic fire detector (value of the line current between Fire condition stage I
and Fire condition stage II) in a line that is in Logical AND dependency by another line, the fire control
panel will enter
Pre-Fire condition in this line –if there is no activated automatic fire detector or manual call
point in the other line;
Fire condition, phase Fire condition stage I in this line –if there is an activated manual call
point in the other line, i.e. the fire control panel has already entered Fire condition, phase Fire
condition stage II in the other line;

UniPOS Fire Control Panel FS5200
Instruction manual Page 13
Revision 8/07.17 of 69
Fire condition stage I in both lines –if there is an activated automatic fire detector in the other
line, i.e. the fire control panel has already entered Pre-Fire condition in the other line.
Exit from Pre-Fire condition in a line is done automatically only:
Upon activation of automatic fire detector in a line that has settled “Logical AND” dependence
to a particular line, within 60 s after entering Pre-Fire condition, the fire control panel enters
Fire condition stage I in both lines;
Upon activation of manual call point in the line that has settled dependence to a particular line
according the function “Logical AND”, within 60 s after entering Pre-Fire condition, the fire
control panel enters Fire condition stage I in this particular line, and Fire condition stage II in
the first line;
Table 1
Conditions of the fire control panel
Indication
All conditions -
The fire control panel is power supplied
Indicator Power supply –
continuous green light
All conditions
Indicator Day Mode –
continuous yellow light
Fire condition, phase Fire condition stage I
Common indicator Fire condition
stage I –flashing red light
Fire condition, phase Fire condition stage II
Common indicator Fire condition
stage II –flashing red light
Fire condition, phase Fire condition stage I –
inspection time has been entered
Indicator Inspection –
continuous green light
Fire condition and Fault condition -
sounders have been suppressed
Indicator Stop Alarm –
continuous red light
Fire condition -
outputs for fire condition have been suppressed
Indicator Suppressed outputs-
continuous red light
Fault condition -
All faults except for Low battery
Common indicator Fault condition
–flashing yellow light
Fault condition –
System fault and New configuration
Indicator System fault –
continuous yellow light
Fault condition -
Fault in mains supply
Indicator Fault in mains supply -
flashing yellow light
Fault condition -
Fault in the backup batteries or in the charger
Indicator Backup battery fault -
flashing yellow light
Fault condition -
Fault in a controllable output
Indicator Out of order/Disabled
controllable output –
flashing yellow light
Disabled component -
Disabled controllable output
Indicator Out of order/Disabled
controllable output –
continuous yellow light
Disabled component -
Disabled line or controllable output
Indicator Disabled component -
continuous yellow light
Test condition
Indicator Test –
continuous yellow light
Fire condition
Local sounder –continuous signal
Pre-Fire condition
Local sounder –discontinuous signal:
4 sound impulses for 1s, followed by
1s break
Fault condition - All faults except for Low battery
Local sounder –discontinuous signal:
1s sound 1s break
Fault condition -
Low battery
Local sounder –discontinuous signal:
1s sound 3s break

UniPOS Fire Control Panel FS5200
Instruction manual Page 14
Revision 8/07.17 of 69
Table 2
Means of control
Condition of the fire
control panel
Access
level
Operation
Key for access to
Level 2
Level 1
Position
Level 2
Position
Button Reset of
line
Fire condition
Level 2
To exit Fire condition in a line, indicated on
the LDC display
Button Outputs
Fire condition, phase
Fire condition stage I
Level 1
To force proceeding to phase Fire condition
stage II
Fire condition, phase
Fire condition stage I
Level 2
- if activated outputs for fire condition are
available –to suppress the outputs;
- if no activated outputs for fire condition
are available –to force proceeding to
phase Fire condition stage II
Fire condition, phase
Fire condition stage II
Level 2
- if activated outputs for fire condition are
available –to suppress the outputs;
- if activated outputs for fire condition are
not available –to activate any suppressed
outputs
Button Inspection
Fire condition, phase
Fire condition stage I
Levels 1
and 2
To add inspection time
Button Alarm
Fire condition and
Fault condition*
Level 1
To suppress /activate the local sounder
Button Menu
Duty Mode, Fire
condition, Pre-fire
condition, Fault
condition*, Test mode
and Disabled
component
Levels 1
and 2
To enter Information and Control mode
Information and
Control
Levels 1
and 2
- To enter the selected menu
- To execute the selected command
- To save a modified parameter
SetUp
Level 3А
Button Down
Fire condition
Levels 1
and 2
To display the next message for fire
condition
Information and
Control
Levels 1
and 2
- To display the next element of the menu
- To move the cursor
- To modify the selected parameter
SetUp
Level 3А
Button Up
Fire condition
Levels 1
and 2
To display the previous message for fire
condition
Information and
Control
Levels 1
and 2
- To display the previous element of the
menu;
- To modify the selected parameter
SetUp
Level 3А
Button Cancel
Information and
Control
Levels 1
and 2
- To exit a function without saving changes
in the parameter; the command will not be
executed
- To exit the current menu and to move to
an upper hierarchy menu
SetUp
Level 3А
*Not effective in Fault condition (fatal fault condition except for New configuration).

UniPOS Fire Control Panel FS5200
Instruction manual Page 15
Revision 8/07.17 of 69
Upon increased current value in a line within the limits between current values for Fire
condition stage II and Short circuit the fire control panel enters Fire condition stage II in this
line;
Where the 60 s of Pre-Fire condition expire and none of the above mentioned three conditions
is carried out, the fire control panel exits Pre-Fire condition in this line and the line is reset –
the power supply is interrupted for 3 s thus the activated automatic fire detectors in this line
shall be reset.
To settle dependence of two lines on function “Logical AND”, set the parameter “Logical AND” in
one of the lines (see section 14.3.1).
When using the “Logical AND” in two lines, we recommend one of the two methods:
Outputs for fire condition shall be associated to one line only, where manual call points, if
necessary, are already integrated;
The same outputs for fire condition shall be associated to both lines (equal for both Fire
condition stage I and II); in this case manual call points can be integrated in both lines.
6.4. Conditions of the fire control panel
FS5200 monitors the fire alarm lines by consecutively scanning their condition. Depending on the
current value, the line can be in normal condition, in fire condition or in a fault condition (short circuit
or break). Simultaneously, a constant control over the controllable outputs of fault condition (short
circuit or break) is being carried out.
The fire control panel FS5200 operates in nine basic modes: Duty Mode, Fire Condition, Pre-Fire
Condition, Fault Condition, Disabled Component Mode, Test Mode, Information and Control Mode,
SetUp Mode and Remote Control Mode.
In each moment the control panel can be in one or in a random combination of these conditions:
Fire Condition, Pre-Fire Condition, Fault Condition, Disabled Component Mode, Test Mode and
Information and Control Mode, .Duty Mode, SetUp Mode and Remote Control Mode cannot be
combined with another condition:
The fire control panel enters Duty Mode after it has exited all other modes;
When the fire control panel enters SetUp Mode or Remote Control Mode it exits all other
conditions.
7. Duty Mode
7.1. Description
The fire control panel is in Duty Mode, when it is not in any other of the rest 8 possible conditions
7.2. Indication
7.2.1. LED and sound indication
In Duty Mode are active the green LED indicator (Power supply) and the yellow indicator
(Day Mode –it illuminates only when the fire control panel is in Day Mode). The local sounder
is switched off.
7.2.2. Text message
Message DUTY and the current time are displayed on the LCD
display:
7.3. Using the keypad
The only accessible button in Duty Mode is (Menu). Press it and the fire control panel
enters Information and Control Mode.
8. Fire condition
8.1. Description
The fire control panel enters Fire Condition after a fire detector has been activated in one of the
fire alarm lines. In Day Mode the condition has two phases –Fire condition stage I and Fire condition
Duty 17:05:34
Thursday 16-10-2003

UniPOS Fire Control Panel FS5200
Instruction manual Page 16
Revision 8/07.17 of 69
stage II. The time period for Fire condition stage I is limited and is user programmable, separately for
each line (up to 255 seconds). The period can be prolonged with the Inspection time (see section
8.3.1). When Fire condition stage I in one line expires, the fire control panel enters Fire condition
stage II in the same line.
The fire control panel enters Fire condition stage I upon activation of an automatic fire detector
when the current value in the line is between the limits for Fire condition stage I and Fire condition
stage II. The fire control panel enters Fire condition stage II upon activation of a manual call point
when the current in the line is between the limits for Fire condition stage I and Short circuit. All
threshold values are user defined, separately for each line (see sections 14 and 14.3.1). Night Mode
phase Fire condition stage I is ignored. The fire control panel enters Fire condition, phase Fire
condition stage II:
upon activation of an automatic fire detector when the current value in the line is between the
limits for Fire condition stage I and Fire condition stage II, and
upon activation of a manual call point when the current in the line is between the limits for Fire
condition stage I and Short circuit.
The fire control panel can be in Fire Condition in one or more lines. When the fire control panel is
in Day Mode, it can register Fire condition stage I in part of the lines, and Fire condition stage II in the
rest of the lines.
To exit this condition press button at Access level 2 (see section. 8.3.4) for each fire alarm
line in fire condition. If a System fault occurs the operation of Fire condition will suffer changes (see
section 10.1).
8.2. Indication
8.2.1. LED and sound indication
In this condition the common light indicator (Fire condition stage I) and/or (Fire
condition stage II) flash in red.
If the outputs for fire condition are suppressed by button (Outputs), the LED indicator on
the button will illuminate in red.
If Inspection time has been entered, the indicator illuminates in continuous green light
(Inspection).
The local sounder produces continuous signal. If the sound indication has been suppressed by
button (Alarm), the LED indicator on the button illuminates in continuous red light.
8.2.2. Text message
Information for all lines in Fire condition appears on the display:
The display is divided into two text fields each containing two lines. Information on the first line in
Fire condition is visualized in the first (top) field; information on the last line in Fire condition –in the
second (bottom) field.
The first line of each field displays information on the type of the Fire condition:
N1 is the consecutive number of the Fire condition, indicated in the first field;
N2 is the consecutive number of the Fire condition, indicated in the second field (in our case,
this is the last fire condition, so N2 is the total number of fires);
Fire1 / Fire2 is the phase of the Fire condition registered for this line;
NN is the line number
SSS is the remaining time in seconds, before the fire control panel proceeds to Fire condition
stage II (it is indicated only in Fire condition stage I).
The second line of each field displays a text message for the corresponding fire alarm line.
N1 Fire 1 LnNN SSSs
Message 1
N2 Fire 2 LnNN
Message 2

UniPOS Fire Control Panel FS5200
Instruction manual Page 17
Revision 8/07.17 of 69
If there are more than two lines in Fire condition, the rest of the text messages are suppressed.
They can be displayed in the first field by the means of the keypad (see section 8.3.5).
8.3. Using the keypad
8.3.1. Button (Inspection)
When you press the Inspection button, the time period, already programmed by the user, will be
added to the remaining time for all lines in Fire condition stage I before they proceed to Fire condition
stage II.
The button is active when a fire alarm line enters Fire condition stage I.
8.3.2. Button (Alarm)
Press it to:
Switch off the local sounder if it responded to Fire condition/Pre-fire condition or Fault
condition;
Activate the local sounder if the control panel I in Fire condition, Pre-fire condition or Fault
condition and the sounder has been suppressed by previous pressing of the same button.
The LED indicator on the button illuminates if the sounder has been switched off after response to
Fire condition, Pre-fire condition or Fault condition.
The button does not affect and is not cancelled by the following events:
When a new line enters Fire condition or proceeds from Fire condition stage I to Fire condition
stage II, the local sounder will be activated due to Fire condition/Pre-Fire condition;
When a new line enters Pre-Fire condition the local sounder will be activated for Fire
condition/Pre-Fire condition only;
A new Fault condition will trigger the local sounder for Fault condition only.
The LED indicator of the button stays illuminated, if the signalizations and/or the outputs remain off.
The button is active at Access levels 1 and 2.
8.3.3. Button (Outputs)
The button operation depends on the current access level and on the status of the fire control
panel.
At Access level 1 (the key on the front panel is in position ) and some fire alarm lines are in
phase Fire condition stage I, the button will trigger forced proceeding to phase Fire condition stage II
in effect for these particular lines.
At Access level 2 (the key on the front panel is in position ) and some fire alarm lines are in
phase Fire condition stage I, the button has the following operations:
If no activated outputs for fire condition are available –the button will trigger forced proceeding
to Fire condition stage II effective to these lines;
If activated outputs for fire condition are available –the button will suppress the outputs.
At Access level 2 (the key on the front panel is in position ) and no fire alarm lines are in
Fire condition stage I (i.e. the fire control panel is in phase Fire condition stage II) the button has the
following operations:
If activated outputs for fire condition are available - the button will suppress the outputs;
If no activated outputs for fire condition are available –the button will activate the suppressed
outputs, if any.
The LED indicator on the button illuminates if some outputs for fire condition are suppressed.
8.3.4. Button (Reset of line)
It forces the fire control panel to exit Fire condition in the fire alarm line, indicated in the first line of
the LCD display, and resets the line (cuts off the power supply for 3 seconds).
The button is active at Access level 2 (the key on the front panel is in position ).

UniPOS Fire Control Panel FS5200
Instruction manual Page 18
Revision 8/07.17 of 69
8.3.5. Buttons (Down) and (Up)
If there are suppressed messages for fire condition they can be displayed in the first field of the
LCD display using buttons and situated on the front panel.
Press button to display the next text message for fire condition. When the last text
message is reached, press button to display the first message.
Press button to display the previous text message for fire condition. When the first
message is reached press button to display the last message.
If a suppressed message is displayed, 20s after the button is pressed for the last time the first
message for fire condition will restore automatically.
8.3.6. Button (Menu)
Press the button to enter Information and Control Mode.
8.3.7. Button (Cancel)
When Fire condition is combined with Information and Control Mode, press the button
continuously to cancel the Information and Control Mode; the first field will then display information on
the first fire alarm line in Fire condition.
9. Pre-Fire condition
9.1. Description
Pre-Fire condition ensures the correct operation of the Function “Logical AND” for two lines (see
section 6.3).
9.2. Indication
9.2.1. LED and sound indication
The common indicator (Fire condition stage I) illuminates in continuous red light to indicate
the condition.
The local sounder emits discontinuous asymmetrical signal - 4 sound impulses for 1 s, then
pause for 1s. If the sound indication has been suppressed by button (Alarm), the LED indicator
on the button illuminates in steady red light.
9.2.2. Text message
The message DUTY and the real time are displayed on the
LCD display.
This message can be suppressed from the screen for Fire Condition. To display the suppressed
messages enter Information and Control Mode (see section 13.6).
9.3. Using the keypad
9.3.1. Button (Alarm)
Press the button to:
Switch off the local sounder if it responded to Fire condition/Pre-fire condition or Fault
condition;
To activate the local sounder of the fire control panel is in Fire condition/Pre-fire condition or
Fault condition and the local sounder is suppressed by a previous push on the same button;
The LED indicator on the button illuminates if the local sounder is suppressed after response
to Fire condition/Pre-fire condition or Fault condition;
Duty 17:05:34
Thursday 16-10-2003

UniPOS Fire Control Panel FS5200
Instruction manual Page 19
Revision 8/07.17 of 69
The button does not affect nor is its action cancelled by the following events:
When Fire Condition is registered in a new line, or transition from Fire condition stage I to Fire
condition stage II the button shall activate the local sounder for Fire/Pre-Fire condition;
When Pre-Fire Condition is registered in a new line, the button will activate the local sounder
for Fire/Pre-Fire condition;
A new Fault condition shall activate the local sounder for Fault condition only.
The button is active at Access levels 1 and 2.
9.3.2. Button (Menu)
Press the button to enter Information and Control Mode.
10. Fault condition
10.1. Description
The fire control panel enters Fault Condition when any of the events below has been registered:
Fatal System fault, including New configuration;
Battery Low –backup batteries discharged due to interruption in mains supply;
Fault in the program of Linear processor 2;
Fault in the data of Linear processor 2;
Fault in the program of Linear processor 3;
Fault in the data of Linear processor 3;
Failure in the real time clock;
Failure in the external memory;
Wrong record in the external memory;
Fault in a line –removed fire detector, short circuit or break;
Fault in a controllable output –short circuit or break;
Fault in main supply;
Fault in backup batteries power supply;
Short circuit in grounded wire;
Fault in the positive supply to the lines;
Fault in the negative supply to the lines;
Fault in power supply to external devices
Where a Fatal System fault occurs (except for New configuration) the main processor is not able
to continue operation. In this case:
only the linear processors that service the fire alarm lines and the controllable outputs are in
operation;
phase Fire condition stage I is ignored and if an automatic fire detector is activated, the control
panel enters Fire condition, phase Fire condition stage II;
in Fire condition will be activated Relay output 1 and Controllable output 1 (for lines 1 –16) or
Controllable output 2 (for lines 17 –32); the rest of the relay outputs for fire condition do not
function;
if the defected component is the LCD display, the information on it is not correct;
from the LED indication only (Fault condition), (System fault), (Fire
condition stage II) and (Power supply) are functioning;
the buttons do not work.
You can exit the fault condition if you disconnect the control panel from the mains supply and
send it for repairs.
New configuration is a fatal system fault –the fire control panel does not service lines, outputs or
other peripherals. To exit the condition you shall enter SetUp Mode. Such fault condition occurs
usually after modification of the physical configuration of the fire control panel –addition, removal or
replacement of additional module.
Battery Low is a fatal non-system fault –the control panel does not service fire alarm lines or
outputs. The unit enters a specific condition:
Discontinuous sound signal is released - 1s sound, 3s pause, for at least an hour;

UniPOS Fire Control Panel FS5200
Instruction manual Page 20
Revision 8/07.17 of 69
Only the green LED indicator is illuminated (Power supply);
The backlight of the display is extinguished;
Only the power supplies are being controlled.
The fire control panel exits the status automatically 8 s after the mains supply is restored.
All other faults are not fatal and switch off some of the periphery devices only. The fire control
panel exits such conditions automatically 8 s after the breakdown is eliminated.
Upon Short circuit in ground wire occur the following faults:
Fault Condition in a line (fire detector removed) –where the short circuit is in fire alarm line’s
component;
Fault Condition in controllable output (interruption) –where the short circuit is in a component
of a controllable output.
In Fault Condition the relevant messages are shown on the display. Additional information is
acquired form the LED indication.
10.2. Indication
10.2.1. LED and sound indication
In Low Battery no LED indicator is illuminated. The local sounder produces discontinuous sound
(1 s sound, 3 s pause). The backlight of the LCD is off.
In all other fault conditions the indicator (Fault condition) flashes in yellow. Depending on
the type of the fault condition the following indicators are illuminated:
System fault –indicator (System fault) is illuminated in flashing yellow light;
New configuration - indicator (System fault) is illuminated in flashing yellow light
Fault in controllable output - indicator (Out of order / Disabled controllable output)
flashes in yellow light.
Fault in mains supply - indicator (Fault in mains supply) flashes in yellow light;
Fault in backup batteries - indicator (Backup battery fault) flashes in yellow light.
The local sounder is activated and produces discontinuous signal. If the sound indication has been
suppressed by button (Alarm), the LED indicator on the button illuminates in steady red light.
10.2.2. Text messages
The messages for fault condition have a priority order, as ranged in section 10.1. The screens for
fatal errors suppress all other messages. If more than one non-fatal error has been detected, they are
indicated according priority; the message of highest priority suppresses all other messages.
10.2.2.1. The following information screens appear upon detection of fatal errors (except
for New configuration):
System fault (the text message in the third line contains
information for the maintenance and repairs staff).
The screen suppresses all other screens and can not be
suppressed.
Battery low
Тhe screen suppresses all other text messages except
for System fault message, and can not be suppressed.
Battery low
System fault
Message
Table of contents
Other UniPOS Control Panel manuals

UniPOS
UniPOS FS4000 User manual

UniPOS
UniPOS IFS7002 Operating instructions

UniPOS
UniPOS FS5100 User manual

UniPOS
UniPOS FS5200E User manual

UniPOS
UniPOS IFS7002 User manual

UniPOS
UniPOS VIT 01 Operating instructions

UniPOS
UniPOS VIT 01 User manual

UniPOS
UniPOS IFS7002R Operating instructions

UniPOS
UniPOS IFS7002 Operating instructions

UniPOS
UniPOS FS5200E User manual