Ceasefire CFX-Plus Pro-Sense 8 Guide

PR®-SENSE

Ceasefire Industries Private Limited, E6, UPSIDC Industrial Area, Selaqui, Dehradun,
Uttarakhand, India, Pin 248001
Model Number LPCB Ref No.
CFX-Plus Pro-Sense 8 zone conventional panel: TI-002308 810a/10
CFX-Plus Pro-Sense 12 zone conventional panel: TI-002309 810a/11
European Standard EN54-2 : 1997 + A1 : 2006
Control and indicating equipment for fire detection and fire alarm systems for buildings.
Provided Options (with requirements):
Output to fire alarm devices, dependency types ‘A’, ‘B’ & ‘C’, delays to outputs, test condition
European Standard EN54-4 : 1997 + A1 : 2002 + A2 : 2006
Power supply equipment for fire detection and fire alarm systems for buildings.
IMPORTANT NOTE
PLEASE READ THIS MANUAL BEFORE HANDLING THE EQUIPMENT AND
OBSERVE ALL ADVICE GIVEN IN IT
THIS PARTICULARLY APPLIES TO THE PRECAUTIONS NECESSARY TO
AVOID E.S.D
IMPORTANT SAFETY NOTES ATTENTION
The panel is safe to operate provided it has been installed in compliance with the manufacturer’s instructions
and used in accordance with this manual.
Hazardous voltages are present inside the panel—DO NOT open it unless you are qualified and authorized
to do so. There is no need to open the panel’s enclosure except to carry out commissioning, maintenance
and remedial work. This work must only be carried out by competent service personnel who are fully
conversant with the contents of the panel’s installation manual and have the necessary skills for maintaining
this equipment.
This fire alarm system requires periodic checks as specified in BS 5839 Part 1 It is the responsibility of the
system user to ensure it is regularly serviced and maintained in good working order.
Disclaimer
No responsibility can be accepted by the manufacturer or distributors of this fire alarm panel for any
misinterpretation of an instruction or guidance note or for the compliance of the system as a whole. The
manufacturer’s policy is one of continuous improvement and we reserve the right to make changes to
product specifications at our discretion and without prior notice. E & O E.
!
2831‐CPR‐F2803
CPR Number
2831‐CPR‐F2803

CFX-Plus Pro-Sense 8-12 Installation, Commissioning & Operating Manual
Approved Document Ref: UI-CFX-Plus-PS-02 Issue 1.0
1
CONTENTS
Page
ABOUT THIS PANEL 2
PRODUCT OVERVIEW 2
CABINET DETAILS 3
CIRCUIT BOARDS 4
MAIN PCB TERMINALS 6
ZONE CARD TERMINALS 7
TECHNICAL SPECIFICATION 8
POWER SUPPLY MODULE 9
DESIGN CONSIDERATIONS 10
SYSTEM DESIGN & PLANNING 10
GENERAL DETECTION CIRCUIT SCHEMATIC 12
GENERAL SOUNDER CIRCUIT SCHEMATIC 13
INSTALLATION 14
SAFETY 14
ESD PRECAUTIONS 15
GENERAL 15
MOUNTING THE CABINET 15
MAINS CONNECTIONS 16
CONNECTING THE BATTERIES 17
SETUP & PROGRAMMING 18
NETWORK PANELS SETUP 18
ZONE INTERFACE FUNCTION 20
LEVEL 3 ENGINEERING MODE 21
LEVEL 3 ENGINEERING OPTIONS INDEX 22
OPERATING 52
PANEL CONTROLS &INDICATIONS 52
DISABLE MODE 54
TEST MODE 55
FAULT DIAGNOSIS 56
FUNCTIONALITY DURING A SYSTEM FAULT 57
SERVICE & MAINTENANCE 58
DUTIES OF THE RESPONSIBLE PERSON 58
ROUTINE MAINTENANCE & TESTING 58
SCHEDULE OF TESTING LOG BOOK 60
FALSE ALARMS, FAULTS & ENGINEER VISIT LOG BOOK 66
USER INSTRUCTIONS 69

CFX-Plus Pro-Sense 8-12 Installation, Commissioning & Operating Manual
Approved Document Ref: UI-CFX-Plus-PS-02 Issue 1.0
2
ABOUT THIS PANEL
PRODUCT OVERVIEW
The CFX-Plus Pro-Sense 8 to 12 zone is a conventional control panel with integral power supply & space for
standby batteries.
CFX-Plus Pro-Sense panels are fully approved to European standards EN54-2 & 4, Fire Detection and Alarm
Systems - Control & Indicating Equipment.
The control panel comprises of a sheet steel enclosure suitable for wall mounting with a hinged, lockable
front access door. It can be semi recessed, using a suitable recessing bezel. Cable entry is via 20mm
‘knockouts’ located at the top and rear of the cabinet.
An eight button keypad is used to control the system and allow access to the function options. The three
main buttons, ‘RESOUND’ (red), ‘SILENCE’ (blue) and ‘RESET’ (green) being much larger and colour
coded to assist the end users.
Eight or twelve fire zone circuits are provided plus four monitored sounder circuits. Fire & fault VFCO
relays, fire & fault switched negative outputs, class change and an alert input are also included.
CFX-Plus Pro-Sense panels support a large range of conventional detectors.
The panels are supplied with a 3.0 amp internal power supply module. This module complies with the
requirements of EN54-4 : 1988 and provides temperature compensated battery management charging.
Quiescent and alarm current details for standby battery calculations
Models Standby Current Alarm Current
TI-002308 139mA 220mA
TI-002309 182mA 267mA
TPCA04-S 4 zone ext card, standard 43mA 47mA
TPCA04-H 4 zone ext card, high spec 49mA 87mA
TPCA05 comms card 5.2mA N/A

CFX-Plus Pro-Sense 8-12 Installation, Commissioning & Operating Manual
Approved Document Ref: UI-CFX-Plus-PS-02 Issue 1.0
3
ABOUT THIS PANEL
CABINET
Fire Detection System
NN
NN
NN
NN
NNNN

CFX-Plus Pro-Sense 8-12 Installation, Commissioning & Operating Manual
Approved Document Ref: UI-CFX-Plus-PS-02 Issue 1.0
4
ABOUT THIS PANEL
CIRCUIT BOARDS
CFX-Plus Pro-Sense 8-12 panels comprise of two main circuit boards plus optional ancillary boards
TPCA01-X2/X4 - Master PCB
TPCA03 - LED Display & Controls PCB
+ -
BATTERY
/0%
1%2%3%4%5%6% 7%%%%%
@
PSU
+
-
28V 0V
+-
FIRE
C NC NO
FAULT
C NC NO
FR FLT
-OP -OP
CC PUL SNDR1 SNDR2
-IP -IP + -+ -
ZONE1
+ -
ZONE2 ZONE3 ZONE4
+ - + -+ -
!"#!$%
&' %(%)%
$!*!#%*+,!"-!%$!*./"0%

CFX-Plus Pro-Sense 8-12 Installation, Commissioning & Operating Manual
Approved Document Ref: UI-CFX-Plus-PS-02 Issue 1.0
5
ABOUT THIS PANEL
ANCILLARY CIRCUIT BOARDS
TPCA05 - Comms PCB
•
Piggy backs on Main PCB for
connection to network & repeater
panels
•
6 programmable switch -ve outputs
TPCA04-S - Std spec 4 zone extension card TPCA04-H - High spec 4 zone extension card
!
4 x conventional zone circuits.
!
4 x conventional zone circuits.
!
2 x switched -ve outputs
!
1 x Aux relay output
!
2 x monitored sounder circuits
TWIN
D
C
B
A
+-
SNDR B
+-
SNDR A
NO
A
UX
C
- -
OPAOPB
ZONE D
+-
C
-
ZONE
+
ZONE B
+-
ZONE A
+-
ON
1 2 3 4
TWIN
D
C
B
A
ZONE D
+-
E C
-
ZON
+
ZONE B
+-
ZONE A
+-
ON
1 2 3 4
COMS ACOMS A B 28 SW -ve OUTPUTS
+ -+ - V+ 1111 2 4 5 6
ADDRESS
ON
1 2 3 4

Esento 8-12 Installation, Commissioning & Operating Manual
PANEL
ABOUT THIS 3$1(/
MAIN PCB TERMINALS
6
CFX-Plus Pro-Sense Installation, Commissioning & Operating Manual
Approved Document Ref: UI-CF-Plus-PS-02 Issue 1.0
PSU
28V 0V FIRE
C NO
FAULT
NCC NO
FR
-OP -IP -IP
FLT CC
PUL SNDR1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4
@@
-
-
+ -
+ -
+ -
+ -
+ -
+ -
+
NC -OP
ON
+ -
BATTERY
1 2 3 4 5 6 7

7
CFX-Plus Pro-Sense 8-12 Installation, Commissioning & Operating Manual
Approved Document Ref: UI-CFX-Plus-PS-02 Issue 1.0
ABOUT THIS PANEL
ZONE CARD TERMINALS
Drawing shows the high spec version of the
zone extension PCB (TPCA04-H).
The std version does not contain the additional
outputs or sounder circuits shown at the
bottom.
$POWFOUJPOBMGJSF[POF
DJSDVJUTGVTFE!N"
ZONE A ZONE B ZONE C ZONE D
+ -+ - +-+ -
AUX SNDR A
+ -
SNDR B
+ -
C NO
- -
OPA OPB
D
C
B
A
TWIN
ON
1 2 3 4

8
CFX-Plus Pro-Sense 8-12 Installation, Commissioning & Operating Manual
Approved Document Ref: UI-CFX-Plus-PS-02 Issue 1.0
ABOUT THIS PANEL
TECHNICAL SPECIFICATION
Electrical Specification Inputs & Outputs - TPCA01-X2/X4 Main PCB
Terminal capacity 0.5mm2to 2.5mm2solid or stranded wire.
PSU @ output Power supply voltage control line. For temperature compensation control.
PSU Input + - 28V DC supply input. Diode protected
for reversal and independent short
circuit. Max current 3 amps.
Max input current 3 amps. Input voltage
22V DC to 32V DC.
28V+, 0V- power output 28V DC supply output for fire alarm
accessory relays etc. Max continuous
use = 400mA.
Fused @ 500mA. Fuse =
500mA resettable fuse.
Common fire relay Fire relay contact. Clean C/O.
Max 3A @ 30V DC.
Unfused
Common fault relay Maintained fault relay contact. Clean C/O
Max 3A @ 30V DC.
Unfused
Outputs; FR, FLT Switched -ve voltage outputs for relay
control.
Overload voltage protected to 52V DC.
Current limited 680R. Max load = 40mA
Inputs; CC, PUL Switched -ve inputs, connect to 0v to
trigger. Max input voltage = 28V DC. Non-
latching, max resistance 100R.
Protected via 10K Ohm impedance, 3v6
Zener diode.
SNDR 1 - 2 28V DC polarity reversal monitored
sounder outputs to fire alarm devices.
4K7 Ohm 5% 0.25W EOL resistor.
Monitoring current limit 28mA, fused @
500mA. Typical max load 22 devices @
18mA each per circuit. Ensure 2.4A is not
exceeded.
Zone 1 - 4 Fire alarm zone circuits. Conventionally
wired detection circuit. 4K7 Ohm 5%
0.25W EOL resistor.
Monitoring current limit 50mA, fused
@ 500mA. Typical max load 22 alarm
devices @ 18mA each per circuit. Ensure
2.4A is not exceeded.
Electrical Specification Inputs & Outputs - TPCA04-S/H zone cards
Terminal capacity 0.5mm2to 2.5mm2solid or stranded wire.
Zone A - D Fire alarm zone circuits. Conventionally
wired detection circuit. 4K7 Ohm 5%
0.25W EOL resistor.
Monitoring current limit 50mA, fused
@ 500mA. Typical max load 22 alarm
devices @ 18mA each per circuit. Ensure
2.4A is not exceeded.
Programmable outputs OP A & OP B Switched -ve voltage outputs for relay
control.
Overload voltage protected to 52V DC.
Current limited 680R. Max load = 40mA
Programmable relay output Fire relay contact. Clean C/O, C & N/O
Max 3A @ 30V DC.
Unfused
SNDR A - B 28V DC polarity reversal monitored
sounder outputs to fire alarm devices.
4K7 Ohm 5% 0.25W EOL resistor.
Monitoring current limit 28mA, fused @
500mA. Typical max load 22 devices @
18mA each per circuit. Ensure 2.4A is not
exceeded.
Electrical Specification Inputs & Outputs - TPCA05 comms PCB
Comms A - B RS485 Repeater Comms, fused @ 20mA
28V Supply output Fused @ 500mA
Programmable outputs 1 - 6 Switched -ve outputs Overload voltage protected to 52V
DC Current limited 680R
Max load = 40mA

9
CFX-Plus Pro-Sense 8-12 Installation, Commissioning & Operating Manual
Approved Document Ref: UI-CFX-Plus-PS-02 Issue 1.0
ABOUT THIS PANEL
General Specification
Enclosure Steel IP30. Epoxy powder coated Interpon Radon, silver grey
Cabling Fire resistant screened cable, minimum size 1mm2. Max cable length
1Km (20 Ohm). FireBurn, FP200 or equivalent (max capacitance
1uF, max inductance 1 millihenry).
Temperature range -5 deg C to +40 deg C max RH 95%
Number of conventional/Twin Wire detection circuits 2 - 12
Conventional/Twin Wire detector compatibility Ceasefire: CFX-Plus Pro-Sense
POWER SUPPLY MODULE
Power Supply Specification
Mains supply 230V AC +10% / -15% 50Hz max
current 1.2A
Mains supply fuse 4 Amp (F4A 250V) Not accessible for servicing. Internal to
switch mode power unit
Internal power supply rating 3.0 Amps total including battery charging Maximum load shared between outputs
= 2.4A
Power supply output voltage 21.27 - 29.68V DC Tolerance +/- 0.1%
Maximum continuous load for battery
standby (ImaxA)
ImaxA = 610mA ImaxB not specified
Minimum current drawn by panel
(example)
4 Zone
I min = 90mA
12 Zone
I min = 188mA
Maximum ripple 120 mV p-p Supply and charger fault monitored
Min/max battery size and type 2 x 7.0Ah 12volt VRLA
Use Yuasa NP range batteries
Other equivalent batteries may be
used but have not been tested for the
purposes of EN54 approval.
Battery charging voltage 27.3 V DC nominal at 20 deg C Temperature compensated
Battery charging output current 3.0A PSU 1.34A
Current limited 4.7 Ohms
Battery high impedance fault (Batt Hi Z) Resistance = 1 Ohm or greater 1 Hour reporting time
Max current drawn from batteries 3.15 Amps with main power source
disconnected. Battery fuse 3.15A LBC
20mm.
017PMUBHFBEKVTU
EFGBVMUTFUUJOHWBUP$
5FNQFSBUVSFDPNQFOTBUJPOJOQVU
GSPN!UFSNJOBMPONBJO1$#
7WFPVUQVU
!"#
!$#
%#
&#
'#
PVU
7
Q
VU
WF
&BSUI
.BJOTJOQVU
/FVUSBM
-JWF

10
CFX-Plus Pro-Sense 8-12 Installation, Commissioning & Operating Manual
Approved Document Ref: UI-CFX-Plus-PS-02 Issue 1.0
DESIGN CONSIDERATIONS
SYSTEM DESIGN & PLANNING - A few handy tips
What is a detection zone?
In order to direct those responding to a fire alarm signal, particularly the fire service, to the area of a fire, all
buildings, other than very small buildings, need to be divided into detection zones. Detection zones need to
be small enough for a fire to be located quickly.
•
If the total floor area of the building is greater than 300m2, each zone should be restricted to a single
storey.
•
If the total floor area of the building is less than 300m2a zone may cover more than a single storey.
•
For voids above or below the floor area of a room, these may be included within the same zone of the
room, provided that the void and the room constitute a single fire compartment
•
The floor area of a single zone should not exceed 2000m2.
Detectors
•
A person searching a zone for a fire in a non-addressable fire system should not have to travel more
than 60m to identify the source of a fire
•
The sensing element of a smoke detection device should not be less than 25mm and not more than
600mm below ceiling
•
The sensing element of a heat detector should not be less than 25mm and not more than 150mm
below ceiling
•
When mounted on a flat ceiling, smoke detection devices have an individual coverage of 7.5m radius.
However these radii must overlap to ensure there are no ‘blind spots’. Therefore individual coverage
can be represented by a square measuring 10.6m x 10.6m giving an actual coverage of 112m2per
device
•
When mounted on a flat ceiling, heat detection devices have an individual coverage of 5.3m radius.
However these radii must overlap to ensure there are no ‘blind spots’. Therefore individual coverage
can be represented by a square measuring 7.5m x 7.5m giving an actual coverage of 56.3m2per
device.
Call Points
•
A person should not have to travel more than 45m along an escape route to reach a Manual Call Point
(25m if disabled person to operate, or rapid-fire development is likely). Manual Call Points should be
sited at all stair wells and exits from the building.
•
The frangible element of the manual call point should be positioned 1.4m (+/-200mm) from the floor
level. (Unless a wheelchair user is likely to be the first person to raise the alarm).
Sounders
•
Sounder device cabling should be arranged so that in the event of a fault, at least one sounder will
remain operational during a fire condition.
•
The minimum sound level should be 65dB(A) or 5dB(A) above a background noise which is louder
than 60dB(A) (if lasting more than 30 seconds) and at a frequency of between 500Hz and 1000Hz.
The maximum sound level should not be greater than 120dB(A) at any normally accessible point. This
may be reduced to 60dB(A) in stairways, enclosures up to 60m2and specific points of limitedextent.
•
For areas where people are sleeping, sounder devices should produce a minimum 75dB(A) at the
bed-head with all doors shut. In buildings providing sleeping accommodation for a significant number
of people, all bedrooms should have both audible and visual alarms.
This guide is intended as an aid to
designers and installers of fire
detection systems. It is NOT to be
used as a substitute to BS5839
which should be read in full.

11
CFX-Plus Pro-Sense 8-12 Installation, Commissioning & Operating Manual
Approved Document Ref: UI-CFX-Plus-PS-02 Issue 1.0
DESIGN CONSIDERATIONS
Beacons
•
Visual alarms such as beacons, should always be mounted at a minimum height of 2.1m from floor
level.
General
•
Fire Alarm Control Panels should be installed at a location appropriate for staff and fire fighters
•
All mains supply isolators must be double pole and suitably marked
•
All joints to be fire resisting, junction boxes to be labelled ‘FIRE ALARM’.
•
All cables to be fire resisting with a minimum cross-sectional area of 1mm2.
•
Cable using trunking as a means of containment must be clipped using fire resistant supports WITHIN
THE TRUNKING.
•
Zone charts should be fitted in all appropriate locations (adjacent to control equipment and repeaters).
CABLE TYPES & LIMITATIONS
To comply with EMC (Electro Magnetic Compatibility) regulations and to reduce the risk of electrical
interference in the system wiring, we recommend the use of screened cables throughout the installation.
Acceptable, commonly available, screened cables, which can be used on both the sounder and detector
circuits include, NoBurn™ FP200™, Firetuff™, Firecel™, MICC (Pyro™) or any other cable complying
with BS 6387 categories C, W, Z. Refer to BS 5839 pt1 clause 26 for detailed information on cables wiring
and interconnections.
CABLING
Suitable cables should be brought into the cabinet using the knockouts provided via a suitable cable gland
recommended for use with that cable. The screen or drain wire of circuits should be bonded to earth at
one location only, and should be continuous throughout the circuit. Drain wires should be terminated in the
cabinet using the earthing terminal provided.
CABLE LENGTHS
The maximum recommended cable length for a zone or sounder circuit is 1Km. This, however, is highly
dependent on the number and type of devices connected.
If in doubt, cable load and resistance calculations should be undertaken to ensure devices are working
within specified limits.
MAINS PROVISION
The mains supply to the fire alarm panel should be hard wired, using suitable three core cable (no less
than 1.0 mm² and no more than 2.5mm²) or a suitable three conductor system that meets the appropriate
national wiring regulations. The panel should be fed from an isolating switched fused spur, supplied directly
from the Main Distribution Board, fused at 3A. This should be secure from unauthorized operation and be
marked ‘FIRE ALARM’.
The mains supply must be exclusive to the fire panel.
As an alternative to a switched fused spur, an appropriately fused double pole isolating device may be
used providing it meets the appropriate national wiring regulations.
All system wiring should be installed to meet BS5839 Pt 1 : 2002 and BS7671
(Wiring Regulations). Other national standards of installation should be used where
applicable.

12
CFX-Plus Pro-Sense 8-12 Installation, Commissioning & Operating Manual
Approved Document Ref: UI-CFX-Plus-PS-02 Issue 1.0
DESIGN CONSIDERATIONS
GENERAL DETECTION CIRCUIT SCHEMATIC
4K7 OHM
END OF LINE
RESISTOR
TI-002270 BASE
45681-201
RL2
IN
L1
OUT
MANUAL CALL POINT
TI-002269
470
_ _ + +
1 2 3 4
TI-002270 BASE
45681-201
RL2
IN
L1
OUT
TI-002270 BASE
45681-201
RL2
IN
L1
OUT
ZONE 1
+ -
_
REMOTE INDICATOR
RIL58

13
CFX-Plus Pro-Sense 8-12 Installation, Commissioning & Operating Manual
Approved Document Ref: UI-CFX-Plus-PS-02 Issue 1.0
DESIGN CONSIDERATIONS
GENERAL SOUNDER CIRCUIT SCHEMATIC
4K7 OHM
END OF LINE
RESISTOR
-VE
-VE
-VE
-VE
MOTORISED BELL
POLARISED
+VE
MOTORISED BELL
POLARISED
+VE
ELECTRONIC SOUNDER
POLARISED
+VE
ELECTRONIC SOUNDER
POLARISED
+VE
SNDR1
+ -

14
CFX-Plus Pro-Sense 8-12 Installation, Commissioning & Operating Manual
Approved Document Ref: UI-CFX-Plus-PS-02 Issue 1.0
INSTALLATION
SAFETY
Suppliers of articles for use at work are required under section 6 of the Health and Safety at Work Act 1974
to ensure as reasonably as is practical that the article will be safe and without risk to health when properly
used. An article is not regarded as properly used if it is used “without regard to any relevant information or
advice” relating to its use made available by the supplier.
It is assumed that the system, of which this control panel is a part, has been designed by a competent fire
alarm system designer in accordance with BS 5839 Part 1 and with regard to BS EN 54 parts 2 and 4 in
the case of control equipment and power supplies. Design drawings should be provided to clearly show
the position of any field devices and ancillary equipment.
This product should be installed, commissioned and maintained by, or under the supervision of, competent
persons according to good engineering practice and,
(i) BS 7671 (IEE wiring regulations for electrical installations)
(ii) Codes of Practice
(iii) Statutory requirements
(iv) Any instructions specifically advised by the manufacturer
According to the provisions of the Act you are therefore requested to take such steps as are necessary to
ensure that any appropriate information about this product is made available by you to anyone concerned
with its use.
This equipment is designed to be operated from 230V AC 50/60 Hz mains supplies and is of Class I
construction. As such it must be connected to a protective earthing conductor in the fixed wiring of the
installation. Failure to ensure that all conductive accessible parts of this equipment are adequately bonded
to the protective earth will render the equipment unsafe.
These panels are designed to comply with the requirements of EN 54 part 2.
Installation of the panel should only be carried out by qualified personnel. The electronic components
within the panel can be damaged by static charge. Suitable precautions must be taken when handling
circuit boards. Never insert or remove boards or components, or connect cables, with the mains power
on or batteries connected.
THIS IS A PIECE OF CLASS 1 EQUIPMENT AND MUST BE EARTHED
This equipment must only be installed and maintained by a suitably skilled and technically
competent person.
!
Equipment Guarantee
This equipment is not guaranteed unless the complete system is installed and commissioned in accordance with the laid
down national standards by an approved and competent person or organization.
This product has been manufactured in conformance with the requirements of all applicable EU Council
Directives

15
CFX-Plus Pro-Sense 8-12 Installation, Commissioning & Operating Manual
Approved Document Ref: UI-CFX-Plus-PS-02 Issue 1.0
INSTALLATION
ESD PRECAUTION
Electronic components are vulnerable to damage by Electrostatic Discharges (ESD). An ESD wrist strap,
suitably grounded, should be worn at all times when handling PCB’s. These wrist straps are designed to
prevent the build-up of static charges, not only within a persons body, but on many other materials.
ESD damage is not always evident immediately, faults can manifest themselves at any time in the future.
All PCB’s should be stored in static shielded bags (silvered) for safe keeping, when not mounted in the
control panel.
GENERAL
Care should be taken with regards to avoiding the close proximity of high voltage cables or areas likely to
induce electrical interference. Earth links should be maintained on all system cables and grounded in the
control panel. The detection and sounder circuit cabling is classed as extra low voltage and must be
segregated away from mains voltage.
•
Any junction boxes used should be clearly labelled FIRE ALARM.
•
Any ancillary devices, e.g. door retaining magnets, must be powered from a separate power source.
•
Any coils or solenoids used in the system must be suppressed, to avoid damage to the control
equipment.
MOUNTING THE CABINET
The site chosen for the location of the panel should be clean, dry and not subject to shock or vibration.
Damp, salt air or environments where water ingress or extremes of temperature may affect the panel must
be avoided. The temperature should be in the range -5° to +40°C, and the relative humidity should not
exceed 95%.
Before mounting the cabinet remove the main PCB.
Remove the power supply module connecting wires from the main PCB, taking care to note where to re-
connect them. The main PCB can then be carefully pulled off it’s mounting clips.
Secure the cabinet to the wall using the four indented holes in the back box. Ensure the box is mounted
level and in a convenient location where it may be easily operated and serviced.
External cables should be glanded via preformed knockouts at the top and rear of the cabinet. Remove
any knockouts and ensure the cabinet is clear of swarf etc. prior to refitting the PCB. Always ensure that if
a knockout is removed, the hole is filled with a good quality cable gland. Any unused knockouts must be
securely blanked off.
Knockouts should be removed with a sharp tap at the
rim of the knockout using a flat 6mm broad bladed
screwdriver.
Use of excessive force will damage the enclosure
around the knockout.

16
CFX-Plus Pro-Sense 8-12 Installation, Commissioning & Operating Manual
Approved Document Ref: UI-CFX-Plus-PS-02 Issue 1.0
INSTALLATION
Typical panel layout
Drawing shows typical internal layout of a 12 zone panel with two 7.0Ah, 12v batteries fitted
MAINS CONNECTIONS
Do not connect the mains supply to the panel
until you are fully conversant with the layout
and features of the equipment.
A rating plate is attached to the power supply
module describing the nature of the supply
permitted.
The incoming mains supply should be brought
into the panel via one of the knockouts
provided.
A suitable cable gland must be used to secure
the outer sheath of the cable used. The earth
must first be connected to the primary earth
stud (peg) marked with a symbol, using
the ring crimp provided.
Sufficient earth lead should be left to allow Live and Neutral connections to be accidentally pulled from the
terminal block while leaving the earth connection intact.
ZONE A ZONE B ZONE C ZONE D ZONE A ZONE B ZONE C ZONE D
PSU
28V 0V FIRE FAULT FR FLT CC PUL SNDR1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4
@ + -+ -C NC NO C NC NO -OP -OP -IP -IP + -+ -+ -+ -+ -+ - + - + - + - + -+ - + - + - + -
+ -
BATTERY
!"#
$#%#&#
TWIN
D
C
B
A
TWIN
D
C
B
A
-- C NO + -+ -
OPA OPB AUX SNDR A SNDR B
$%A#)U57B#A1/7#6733,1[#$%A#)U57B#A1/7#6733,1[#
!"#
$#%#&#'#######
!"#
$#%#&#'#######
!"#
!$#
%#
&#
'#

17
CFX-Plus Pro-Sense 8-12 Installation, Commissioning & Operating Manual
Approved Document Ref: UI-CFX-Plus-PS-02 Issue 1.0
INSTALLATION
CONNECTING THE BATTERIES
Batteries of even very small capacity are capable of delivering very high currents which can cause fire or
injury, therefore battery connections should be done with caution.
The panel is supplied with battery leads already connected to the battery terminals on the main PCB.
These leads are coloured red for +ve and black for -ve.
2 x 12v batteries should be connected in series
using the white jumper lead provided. See
diagram.
To optimize the service life of the batteries, the
battery charger output voltage varies with
temperature.
N.B.
In the event of mains failure, the battery charger
circuit will protect the batteries from full discharge
by disconnecting them when they reach below
19v. When the mains supply is restored the
batteries will be automatically reconnected.
NOTE:
If the mains is connected before the batteries, the panel will show a Power Supply fault for up to 1 minute
until the monitoring cyclehas finished polling. This is normal. If the fault doesn’t clear after 1 minute, check
connections.
BATTERY CHARGING VOLTAGE CHECKS
The battery charging voltage is factory calibrated to 27.3V DC +/- 0.2V @ 20oC. This should not normally
require adjustment. Where battery problems are experienced, the following information should be
considered.
a) If a battery is disconnected from the charger, no voltage will appear on the output leads or terminals,
due to intelligent battery controls.
b) Check the power supply voltage at the 28V& 0Vsupply output terminals. With the batteries
disconnected the voltage should be 27.6V DC +/- 0.2V @ between 11oC-40oC.
c) To test the batteries, turn off the mains and see if the system will run on the batteries. Check the
battery voltage, should be 26.8v for a good battery or 22v for a flat battery.
d) The power supply voltage can be adjusted using the potentiometer on the power supply module (see
page 9), checking at the 28v & 0v output terminals with a calibrated volt meter. Batteries should be
disconnected and the Access Level 3 DIL switch should be set to ‘ON’ (see page 20), which will
override the temperature compensation controls. Carefully adjust the voltage to 27.6vdc +/-0.2v.
When completed, switch off Access Level 3 DIL switch and re-connect the batteries.
e) When the panel is re-charging a low battery, it should be possible to see the voltage across the
batteries increase gradually. If this is not occurring, the batteries or the panel may be faulty.
!"#
+ -
BATTERY
$#%#& #
4XE @XE
$%X#2/7#6PKKETN#$%X#2/7#6PKKETN#

18
CFX-Plus Pro-Sense 8-12 Installation, Commissioning & Operating Manual
Approved Document Ref: UI-CFX-Plus-PS-02 Issue 1.0
SETUP & PROGRAMMING
NETWORK PANELS SETUP
The system can support up to 8 networked control panels, 1 x Master and up to 7 x Slaves.
Comms PCB
To run a network, a Comms PCB (TPCA05) must be fitted to each control panel. Any medium or large
CFX-Plus Pro-Sense panel from 8 to 32 zones with software version 4.0 and above may be used.
The Comms PCB fits into the control panel on top of the main circuit board where the ribbon cable from
the display board comms is normally plugged.
To fit the Comms PCB, power down the panel, un-plug the display board ribbon cable from the main circuit
board and plug the Comms PCB into the socket instead.
A socket is provided on the top of the Comms PCB to re-connect the display board ribbon cable.
Each panel to be included in the network is defined by setting a switch on the main PCB. In the case of the
CFX-Plus Pro-Sense 8-12 this is switch 7 on the 7 way DIL switch. OFF = Stand Alone mode, ON =
Network/Repeater mode.
With this switch in the ON position the panel will automatically recognise & operate the Comms PCB
(TPCA05).
4 5 6
+-
+
-
V+
COMS A COMS B 28
SW -
ve OUTPUTS
2 3
!"#
$#######%#######&##'#####
ADDRESS
!"#!"#
$#######%#######&####'#######8#######9##)#####
%JTDPOOFDUEJTQMBZCPBSESJCCPODBCMF
XBZ%*-TXJUDI
1MVH$PNNT1$#JOUPUIFTPDLFUBOE
SFDPOOFDUEJTQMBZCPBSESJCCPODBCMFUP
TPDLFUPOUPQPG$PNNT1$#
PSU
@ + -
28V 0V
+-
FIRE
C NC NO
FAULT
C NC NO
FR
-OP
FLT
-OP
CC
-IP
PUL
-IP
SND
+
R1
-
SNDR2
+-
ZONE1
+-
ZONE2
+-
ZON
+
E3
-
ZONE4
+-
PSU
@ + -
28V 0V
+-
FIRE
C NC NO
FAULT
C NC NO
FR
-OP
FLT
-OP
CC
-IP
PUL
-IP
SND
+
R1
-
SNDR2
+-
ZONE1
+-
ZONE2
+-
ZON
+
E3
-
ZONE4
+-
+-
BATTERY
1
$#%#&#'#8#9#)#####
+-
BATTERY
0//FUXPSL
3FQFBUFSNPEF
!"#
$# %# &# '# 8# 9# )#
This manual suits for next models
3
Table of contents
Other Ceasefire Control Panel manuals
Popular Control Panel manuals by other brands

STG-BEIKIRCH
STG-BEIKIRCH SHE TRZ Basic 2A/BMA Technical information and operating instruction

Muirhead
Muirhead 16936 product manual

DMP Electronics
DMP Electronics XR150CAN Series installation guide

Bticino
Bticino 352500 manual

Texecom
Texecom Premier Elite 48-W quick start guide

Bosch
Bosch FPA-5000 System information guide