SDC UR4-8 User manual

I. Features & Benefits
Microprocessor based relay controller that provides 7
different, field selectable application modes for two, three or
four door stations
3 field selectable Interlock (airlock) modes
Field selectable Communicatin (shared) bathroom mode
Field selectable relay modes include:
- Conventional Relay (CR)
- Latchin Relay (LR) – Pulse on, pulse off
- Time Delay Relay (TD) – 1-65 seconds
- Dual Function Relay (CR/LR, TD/LR, TD/CR, CR/CR)
Each output relay is field selectable as a dry contact or a
volta e output
II. Technical Specifications
Input Voltage: 12 or 24VDC +/- 10%
Input Current: 250/130 mA max. @ 12/24 VDC
Relay Inputs: 8-SPST, Dry, Optically Isolated
All Normally Open or Normally Closed (field selectable)
Auxiliary Inputs: 4-SPST, Dry, Normally Open, Optically Isolated
Relay Outputs: 4 fused SPDT relays, 7A @ 30VDC
4 non-fused SPDT relays, 7A @ 30VDC
Individually confi urable as a dry contact or volta e output (field selectable)
Di ensions: 7" W x 5" H x 2" D
(177.8 x 127 x 50.8 mm)
INSTALLATION INSTRUCTIONS
MODEL UR4-8
UNIVERSAL DOOR CONTROLLER
P:\INSTALLATION INST\Power Supplies\INST-UR\INST-UR4-8.vsd REV A1 11-14 Pa e 1
801 Avenida Acaso, Camarillo, Ca. 93012 • (805) 494-0622 •
www.sdcsec rity.com • E-mail: service@sdcsec rity.com
Centralized wirin for all locks, access controls, monitorin
contacts, and peripheral equipment
Onboard input/output status li hts for easy troubleshootin
3 system control inputs: Lock All, Unlock All, System
Lockout
Emer ency release input for fire panel interface
Removable terminal blocks simplify installation
1 or 2 controllers may be installed in SDC 600 series power
supplies

+
(-)
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
SW1
SW2
(
-
)
N
O
N
C
C
(
-
)
N
O
N
C
C
(
-
)
N
O
N
C
C
(-)
N
O
N
C
C
W
D
W
D
FUSE W
D
W
D
FUSE W
D
W
D
FUSE W
D
W
D
FUSE
UR4-8
(
-
)
N
O
N
C
C
(
-
)
N
O
N
C
C
(
-
)
N
O
N
C
C
(
-
)
N
O
N
C
C
Power Input
12/24 VDC
OUTPUT 2 OUTPUT 4 OUTPUT 6 OUTPUT 8
OUTPUT 1 OUTPUT 3
C A1 C A2 C B1 C B2 C C1 C C2 C D1 C D2 C E1 C E2 C E3 C E4
OUTPUT 7OUTPUT 5
III. UR4-8 Board Layout
1
P:\INSTALLATION INST\Power Supplies\INST-UR\INST-UR4-8.vsd REV A1 11-14 Pa e 2
4
2
3
6
5
7
RELAY OUTPUTS – The UR4-8 provides ei ht (8) individual
SPDT relay outputs.
Outputs 1, 3, 5, & 7 are fused. These outputs are typically
used to power the door lockin hardware.
Outputs 2, 4, 6, & 8 are non-fused. These outputs are
typically used as auxiliary (monitorin ) relays. They may
be used to power a remote status annunciator, or send a
si nal to a security panel.
WET/DRY SELECTION JUMPER – Each relay output may be
confi ured as a wet (volta e) or dry output. Use the supplied
jumpers to confi ure each relay individually.
Jumper over top 2 pins = WET
Jumper over bottom 2 pins = DRY
The relay output volta e will be the same as the UR4-8 input
volta e (12 or 24 VDC).
MAIN INPUTS – The UR4-8 provides ei ht (8) individual
optically isolated inputs. The inputs must be connected to a dry
switch.
These inputs may be collectively confi ured as Normally Open
or Normally Closed inputs.
NOTE: If Normally Closed inputs are selected, all unused
inputs will need to be shorted.
1
W
D
W
D
FUSE
OUTPUT 2
OUTPUT 1
(
-
)
N
O
N
C
C
(
-
)
N
O
N
C
C
FAIL-
SECURE
LOCK
FAIL-
SAFE
LOCK
-
+
-
+
Monitoring
Relay
Output
2
W
D
W
D
3
C A1 C A2 C B1 C B2
}
}
Input
A1
Input
A2
}
}
Input
B1
Input
B2
AUXILIARY INPUTS – The UR4-8 provides four (4) individual
dry, optically isolated auxiliary inputs.
NOTE: These input connections are optional and must be wired
as Normally Open connections. The input will only be active when
closed (shorted).
Input E1 – LOCK ALL – When activated, this input will lock
all the doors, until the input is deactivated. Door Monitorin
Inputs will be i nored.
Input E2 – UNLOCK ALL – When activated, this input will
unlock all the doors, until the input is deactivated. Door
Monitorin Inputs will be i nored.
Input E3– LOCKOUT – When activated, this input will cause
all the lock outputs to remain in their current state, and
i nore chan es to the Door Monitorin Inputs. Lock/Unlock
All inputs will also i nored.
Input E4 – EMERGENCY RELEASE (FIRE ALARM) –
When activated, this input will simultaneously release all fail-
safe locks. Door Monitorin Inputs, Lock/Unlock All inputs,
and the Lockout input will be i nored.
INPUT POWER CONNECTION – The UR4-8 must be powered by
a filtered and re ulated 12 or 24VDC Power Supply. SDC 600
Series Power Supplies are desi ned to accommodate and
interface with up to two (2) UR4-8 controllers.
MODE CONFIGURATION DIP SWITCHES – The UR4-8 utilizes
two (2) 8-position dip switch modules for confi urin the system
operational modes. They are SW1 and SW2.
STATUS LIGHTS – The UR4-8 provides dia nostic li hts to show
the status of each individual input and output on the board.
If an input is closed, its correspondin li ht
will be ON.
If an output is active, its correspondin li ht
will be ON.
4
C E1 C E2 C E3 C E4
}
}
Input
E1
Input
E2
}
}
Input
E3
Input
E4
5
6
E
3
E
4
O
1
O
2
O
3
O
4
O
5
O
6
O
7
O
8
A
1
A
2
B
1
B
2
C
1
C
2
D
1
D
2
E
1
E
2
7
Station A Station B Station C Station D Auxiliary Inputs
Station A Station B
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
SW1
SW2
ON
ON

IV. Applications
For detailed wirin instructions and setup, select your specific application from the followin available modes, and
continue to the pa e number indicated next to the section title.
Section V – 2, 3, or 4-Door Interlock “A” Setup - Go To Pages 5 & 6
All doors are normally closed and unlocked. Openin any door causes the other doors to lock until the opened door returns to its
normal state.
Section VI – 2, 3, or 4-Door Mantrap “B” Setup – Go To Pages 7 & 8
All doors are normally closed and locked. Each door may be individually unlocked usin the Access Control System or a remote
release. Unlockin any door causes the other doors to be incapable of bein unlocked until the unlocked door returns to its normal
state.
Section VII – 2, 3, or 4-Door Interlock “C” Setup – Go To Pages 9 & 10
All doors are normally closed. Up to three (3) doors may be normally locked, and the remainin door(s) will be normally unlocked.
The possible confi urations are:
2 Doors: Door 1 – Locked, Door 2 – Unlocked
3 Doors: Door 1 – Locked, Doors 2 & 3 – Unlocked
Doors 1 & 2 – Locked, Door 3 – Unlocked
4 Doors: Door 1 – Locked, Doors 2, 3, & 4 – Unlocked
Doors 1 & 2 – Locked, Doors 3 & 4 – Unlocked
Doors 1, 2, & 3 – Locked, Door 4 – Unlocked
Normally Locked doors may be unlocked usin the Access Control System. Unlockin or openin any door will lock the unlocked
doors, and make the locked doors incapable of bein unlocked, until the unlocked/opened door returns to its normal state.
Section VIII – Dual Relay Control Mode – Go To Pages 11 & 12
In Dual Relay Control Mode, the UR4-8 operates as four (4) individually controlled relay stations. Each station provides:
(1) Fused, SPDT lock output, wet or dry,
(1) Non-fused, SPDT auxiliary (monitorin ) output, wet or dry, and
(2) Dry tri er inputs
Activatin each station’s Input 1 OR Input 2 will tri er the correspondin lock output AND the monitorin output simultaneously.
Each Output Station may be confi ured as one of the followin (Input 1 = CR/Input 2 = CR, Input 1 = TD/ Input 2 = CR (TD reset),
Input 1 = CR (LR reset)/Input 2 = LR, or Input 1 = TD/Input 2 = LR)
As a conventional relay (CR), the lock output relay is only activated while the tri er input is activated. Once the tri er input is
released, the output relay returns to its restin state. The monitorin relay output follows the lock output relay.
As a time delayed relay (TD), the lock output relay is activated by the tri er input. Once the tri er input is released, the output
remains activated for a specified period of time, as confi ured by the dip switches. The monitorin relay output follows the lock output
relay.
As a latchin relay (LR), the lock output relay is activated by tri er Input 2. A sin le activation and release of tri er Input 2 latches
the lock output relay. The lock output relay remains latched until tri er Input 2 is reactivated or until the Input 1 is momentarily
activated. The monitorin relay output relay follows the lock output relay.
W
D
W
D
FUSE
OUTPUT 2
OUTPUT 1
(
-
)
N
O
N
C
C
(
-
)
N
O
N
C
C
FAIL-
SECURE
LOCK
FAIL-
SAFE
LOCK
-
+
-
+
Monitoring
Relay
Output
C A1 C A2 C B1 C B2
}
}
Input
1
Input
2
Station A
Station A Inputs activate Outputs 1 & 2
Station B Inputs activate Outputs 3 & 4
Station C Inputs activate Outputs 5 & 6
Station D Inputs activate Outputs 7 & 8
P:\INSTALLATION INST\Power Supplies\INST-UR\INST-UR4-8.vsd REV A1 11-14 Pa e 3

IV. Applications (Continued)
Section IX – Single Relay Control Mode – Go To Pages 13 & 14
In Sin le Relay Control Mode, the UR4-8 operates as ei ht (8) individually controlled relay stations.
Stations A1, B1, C1, & D1 each provide:
(1) Fused, SPDT lock output, wet or dry and
(1) Dry tri er input
Stations A2, B2, C2, & D2 each provide:
(1) Non-fused, SPDT lock output, wet or dry and
(1) Dry tri er input
Each input may be individually confi ured to operate as a conventional relay or a time delayed relay.
Alternatively, each input may be individually confi ured to operate as a latchin relay or a time delayed relay.
As a conventional relay (CR), the lock output relay is only activated while the tri er input is activated. Once the tri er input is
released, the output relay returns to its restin state.
As a time delayed relay (TD), the lock output relay is activated by the tri er input. Once the tri er input is released, the output
remains activated for a specified period of time, as confi ured by the dip switches.
As a latchin relay (LR), the lock output relay is activated by the tri er Input. A sin le activation and release of the latchin tri er
input latches the lock output relay. The lock output relay remains latched until the latchin tri er input is reactivated.
Section X – 2-Door Co unicating (Shared) Bath Syste (Single or Dual) – Go to Page 15 & 16
Both doors are normally closed and unlocked.
System Activation:
Upon enterin the bathroom and closin both doors, pressin an Activation button will lock both doors and turn on the indicator lamps
on the Activation button and Emer ency Unlock buttons, indicatin the bathroom is occupied.
System Deactivation:
When sing EMLocks®, pressin the Activation button a second time will unlock both doors and turn off all indicator lamps.
When sing fail-safe electric strikes or electrified locksets, operatin the inside lever to retract the latch on either door will unlock both
doors and turn off all indicator lamps. Usin a key override from the outside to enter either door will also reset the system and unlock
both doors.
Emergency Override:
Emer ency Unlock buttons located outside each bathroom door will immediately unlock its specified door and indicate its activation
by causin the button’s indicator lamp to flash. Pressin the Emer ency Unlock button a second time will return the door to the
locked state and the indicator lamp will return to a steady li hted state. Pressin the Activation button durin an emer ency override,
will reset the system and unlock both doors
Station A, Input 1 activates Output 1
Station A, Input 2 activates Output 2
Station B, Input 1 activates Output 3
Station B, Input 2 activates Output 4
Station C, Input 1 activates Output 5
Station C, Input 2 activates Output 6
Station D, Input 1 activates Output 7
Station D, Input 2 activates Output 8
P:\INSTALLATION INST\Power Supplies\INST-UR\INST-UR4-8.vsd REV A1 11-14 Pa e 4
C A1 C A2 C B1 C B2
}
}
Input
1
Input
2
Station A
W
D
W
D
FUSE
OUTPUT 2
OUTPUT 1
(
-
)
N
O
N
C
C
(
-
)
N
O
N
C
C
FAIL-
SECURE
LOCK
FAIL-
SAFE
LOCK
-
+
-
+FAIL-
SECURE
LOCK
FAIL-
SAFE
LOCK
-
+
-
+
}
}
Input
1
Input
2
Station B

V. 2, 3, or 4-Door Interlock “A” Setup
Follow the installation steps below before applyin power to the UR4-8.
Refer to the INTERLOCK “A” MODE wirin dia ram on Page 6.
NOTE: It is assumed that the UR4-8 and lockin hardware share the
same power supply.
Interlock “A” Standard Operation:
All doors are normally closed and unlocked. Openin any door causes
the other doors to lock until the opened door returns to its normal state.
Step 1 – Set Dip Switches
The dip switch settin s below are an example of the typical Interlock A
setup shown on Pa e 6. Adjust dip switches SW2-5 & SW2-7 as needed.
All other dip switches should remain as shown below.
Step 2 – Configure the Relay Outputs to be Wet
(Voltage) or Dry.
Use the red WET/DRY Selection Jumpers to confi ure each output.
Refer to Pa e 2 of this instruction for selection procedure.
On the typical Interlock A wirin dia ram, the Lock Relays (Outputs 1, 3,
5, & 7) are confi ured to be wet outputs.
The Monitorin Relays (Outputs 2, 4, 6, & 8) are dry.
NOTE: It is recommended that any unused relays be confi ured as dry
outputs.
Step 3 – Ter inate the Lock Power Wiring
Follow the typical Interlock A wirin dia ram for fail-safe or fail-secure
locks. Be careful to observe lock volta e polarity.
*
WARNING!:
The UR board Relay Outputs must be protected a ainst
inductive kickback enerated when power is removed from an inductive
load (e. ., electric strikes). Refer to the lock manufacturer's installation
manual or contact the manufacturer for kickback protection
recommendations.
NOTE: All low volta e wirin shall be 18- au e minimum. The minimum
lock power wire au e shall be determined by the SDC wire au e chart.
Si nal wire shall be 22- ua e minimum.
Step 4. Ter inate the Door Monitoring Inputs
Connect the Door Monitorin Switches to Input terminals A1, B1, C1, &
D1. This is a required connection for all door stations bein used.
Door Monitorin inputs (typically Door Position Switches), should be dry,
Normally Open or Normally Closed switches, dependin on the
confi uration of Dip Switch 2-5 (Step 1).
NOTE: Dip Switch 2-5 confi ures the normal state of the Door Monitorin
input when the door is in a CLOSED position. If Normally Closed inputs
are selected, all unused inputs will need to be shorted.
Step 5. Ter inate Auxiliary Inputs and Outputs
(Optional)
Auxiliary Inputs – These inputs must be wired as dry, Normally Open
switches. The input will only be active when closed (shorted). Refer to
Pa e 2 for input descriptions.
Monitorin Relay Outputs – Each door station provides a non-fused,
SPDT monitorin relay. This output may be used to si nal a Security
Panel or to activate a Remote Annunciator. The relay is confi urable as a
Wet or Dry output (Step 2). The relay activation will follow the Lock Relay
or follow the Door Monitorin Input, dependin on the confi uration of Dip
Switch 2-7 (Step 1).
Step 6. Connect a 12 or 24VDC Power Source to the
UR4-8 Controller.
Before applyin power, verify that all the connections are securely
terminated by gently pulling on each wire.
Terminate the volta e wirin to the Controller Power Input, as shown on
Pa e 6. Be careful to observe polarity.
Verify that all the doors are closed & apply power to the controller.
Step 7. UR4-8 Controller Startup and Operation
Verification.
Verify the polarity of the Door Monitorin Inputs by observin the Status
Li hts located on the lower ri ht of the UR4-8 controller.
Status Li hts A1, B1, C1, & D1 will be OFF if Dip Switch 2-5 = OFF, or
will be ON if Dip Switch 2-5 = ON.
Test the standard operation of the interlock by openin any door. All
other doors will lock until the unlocked door returns to its normal state
(closed).
P:\INSTALLATION INST\Power Supplies\INST-UR\INST-UR4-8.vsd REV A1 11-14 Pa e 5
SW2-1 = OFF
SW2-2 = OFF
SW2-3 = OFF
SW2-4 = OFF
SW2-5 = OFF Sets the polarity of the Door Monitoring Inputs w hen the
door is in the CLOSED position. {OFF = N/O; ON = N/C}
SW2-6 = OFF
SW2-7 = OFF
Sets the operation of all the Monitoring Relay Outputs.
{OFF = Relay w ill follow the Door Monitoring Input;
ON = Relay w ill follow the Lock Output Relay}
SW2-8 = ON
SW1 -1 = OFF
SW1 -2 = OFF
SW1 -3 = OFF
SW1 -4 = OFF
SW1 -5 = OFF
SW1 -6 = OFF
SW1 -7 = OFF
SW1 -8 = OFF
W
D
W
D
= WET = DRY

DOOR
MONITORING
(DPS)
DOOR #1 DOOR #2
DOOR
MONITORING
(DPS)
DOOR
MONITORING
(DPS)
DOOR #3 DOOR #4
DOOR
MONITORING
(DPS )
LOCK
ALL
(Optional)
UNLOCK
ALL
(Optional)
EMERGENCY
RELEASE
(Optional)
Monitoring
Relay
Output
(Optional)
12/24 VDC
POWER
SUPPLY
SDC 600
Series
+
-
+
(-)
(
-
)
N
O
N
C
C
(
-
)
N
O
N
C
C
(
-
)
N
O
N
C
C
(-)
N
O
N
C
C
W
D
W
D
FUSE W
D
W
D
FUSE W
D
W
D
FUSE W
D
W
D
FUSE
INTERLOCK “A” MODE
(
-
)
N
O
N
C
C
(
-
)
N
O
N
C
C
(
-
)
N
O
N
C
C
(
-
)
N
O
N
C
C
Power Input
12/24 VDC
FAIL-SECURE
LOCK
(12 OR 24 VDC)
FAIL-SAFE LOCK
(12 OR 24 VDC)
+
+
-
-
DOOR
#1
LOCK
FAIL-SECURE
LOCK
(12 OR 24 VDC)
FAIL-SAFE LOCK
(12 OR 24 VDC)
+
+
-
-
DOOR
#2
LOCK
OUTPUT 2 OUTPUT 4 OUTPUT 6 OUTPUT 8
OUTPUT 1 OUTPUT 3
C A1 C A2 C B1 C B2 C C1 C C2 C D1 C D2 C E1 C E2 C E3 C E4
LOCKOUT
(Optional)
FAIL-SECURE
LOCK
(12 OR 24 VDC)
FAIL-SAFE LOCK
(12 OR 24 VDC)
+
-
DOOR
#4
LOCK
FAIL-SECURE
LOCK
(12 OR 24 VDC)
FAIL-SAFE LOCK
(12 OR 24 VDC)
+
+
-
-
DOOR
#3
LOCK
+
-
OUTPUT 7OUTPUT 5
INSTALLATION NOTES:
1. Door Monitoring circuits are shown open when the
door is in the closed position. Use dip switch SW2-5 to
configure the door switch polarity.
2. All Lock Relay Outputs (1, 3, 5, & 7) have been
configured to have wet (voltage) outputs. Lock output
voltage will be the sa e as the UR4-8 input voltage.
3. Monitoring Relay Outputs have been configured to
follow the Door Monitoring Input.
P:\INSTALLATION INST\Power Supplies\INST-UR\INST-UR4-8.vsd REV A1 11-14 Pa e 6
Monitoring
Relay
Output
(Optional)
Monitoring
Relay
Output
(Optional)
Monitoring
Relay
Output
(Optional)
MOV
*
MOV
*
MOV
*
MOV
*
*MOV for Inductive Kickback protection.
See Step 3 on P . 5
DIP SWITCHES
Set as shown on
Pa e 5, Step 1

P:\INSTALLATION INST\Power Supplies\INST-UR\INST-UR4-8.vsd REV A1 11-14 Pa e 7
VI. 2, 3, or 4-Door Mantrap “B” Setup
Follow the installation steps below before applyin power to the UR4-8.
Refer to the MANTRA “B” MODE wirin dia ram on Page 8.
NOTE: It is assumed that the UR4-8 and lockin hardware share the
same power supply.
Mantrap “B” Standard Operation:
All doors are normally closed and locked. Each door may be individually
unlocked usin the Access Control System or a remote release.
Unlockin any door causes the other doors to be incapable of bein
unlocked until the unlocked door returns to its normal state.
The door unlock time will be determined by the Access Control System
and by Dip Switches 2-1 throu h 2-4 (See Step 1).
Step 1 – Set Dip Switches
The dip switch settin s below are an example of the typical Mantrap B
setup shown on Pa e 8. Adjust dip switches SW2-1 thru SW2-7 as
needed. All other dip switches should remain as shown below.
Step 2 – Configure the Relay Outputs to be Wet
(Voltage) or Dry.
Use the red WET/DRY Selection Jumpers to confi ure each output.
Refer to Pa e 2 of this instruction for selection procedure.
On the typical Mantrap B wirin dia ram, the Lock Relays (Outputs 1, 3,
5, & 7) are confi ured to be wet outputs.
The Monitorin Relays (Outputs 2, 4, 6, & 8) are dry.
NOTE: It is recommended that any unused relays be confi ured as dry
outputs.
Step 3. Ter inate the Lock Power Wiring
Follow the typical Mantrap B wirin dia ram for fail-safe or fail-secure
locks. Be careful to observe lock volta e polarity.
*
WARNING!:
The UR board Relay Outputs must be protected a ainst
inductive kickback enerated when power is removed from an inductive
load (e. ., electric strikes). Refer to the lock manufacturer's installation
manual or contact the manufacturer for kickback protection
recommendations.
NOTE: All low volta e wirin shall be 18- au e minimum. The minimum
lock power wire au e shall be determined by the SDC wire au e chart.
Si nal wire shall be 22- ua e minimum.
Step 4. Ter inate the Access Control and Door
Monitoring Inputs
Connect the Door Monitorin Switches to input terminals A1, B1, C1, &
D1. This is a required connection for all door stations bein used.
Connect Access Control or remote releases to input terminals A2, B2, C2,
& D2. This is a required connection for all door stations bein used.
Door Monitorin and Access Control inputs should be dry, Normally Open
or Normally Closed switches, dependin on the confi uration of Dip
Switches 2-5 and 2-6, respectively.
NOTE: Dip Switch 2-5 confi ures the normal state of the Door Monitorin
input when the door is in a CLOSED and/or LOCKED position. If
Normally Closed inputs are used, all unused inputs will need to be
shorted.
Step 5. Ter inate Optional Inputs and Outputs
Auxiliary Inputs – These inputs must be wired as dry, Normally Open
switches. The input will only be active when closed (shorted). Refer to
Pa e 2 for input descriptions.
Monitorin Relay Outputs – Each door station provides a non-fused,
SPDT monitorin relay. This output may be used to si nal a Security
Panel or to activate a Remote Annunciator. The relay is confi urable as a
Wet or Dry output (Step 2). The relay activation will follow the Lock Relay
or follow the Door Monitorin Input, dependin on the confi uration of Dip
Switch 2-7 (Step 1).
Step 6. Connect a 12 or 24VDC Power Source to the
UR4-8 Controller.
Before applyin power, verify that all the connections are securely
terminated by gently pulling on each wire.
Terminate the volta e wirin to the Controller Power Input. Be careful to
observe polarity.
Verify that all the doors are closed & apply power to the controller.
Step 7. UR4-8 Controller Startup and Operation
Verification.
Verify the polarity of the Access Control & Door Monitorin Inputs by
observin the Status Li hts located on the lower ri ht of the UR4-8
controller.
Status Li hts A1, B1, C1, & D1 will be OFF if Dip Switch 2-5 = OFF, or
will be ON if Dip Switch 2-5 = ON.
Status Li hts A2, B2, C2, & D2 will be OFF if Dip Switch 2-6 = OFF, or
will be ON if Dip Switch 2-6 = ON.
Test the standard operation of the mantrap by unlockin any door usin
the Access Control System or remote release. All other doors will be
incapable of bein unlocked until the unlocked door returns to its normal
state (closed & locked).
SW2-1= ON
SW2-2 = OFF
SW2-3 = OFF
SW2-4 = OFF
SW2-5 = OFF
Sets the po larity of the Do o r M onito ring Inputs when the
doo r is in the CLOSED and/o r LOCKED po sitio n.
{OFF = N/O; ON = N/C}
SW2-6 = OFF Sets the po larity of A ccess Co ntro l Inputs when the switch
is in a no rmal (resting) state. {OFF = N/O; ON = N/C}
SW2-7 = OFF
Sets the o peratio n of all the M onitoring Relay Outputs.
{OFF = Relay will follo w the Doo r M o nitoring Input;
ON = Relay will follo w the Lo ck Output Relay}
SW2-8 = ON
SW1-1= ON
SW1-2 = ON
SW1-3 = ON
SW1-4 = ON
SW1-5 = OFF
SW1-6 = OFF
SW1-7 = OFF
SW1-8 = OFF
SW2-1 thro ugh 2-4 set the unlock time o f the Lock Relay.
N O T E : This is in additio n to yo ur A ccess Control System
unlo ck time.
SW2-1 ON = 5 sec., OFF = 0 sec.;
SW2-2 ON = 10 sec., OFF = 0 sec.;
SW2-3 ON = 20 sec., OFF = 0 sec.;
SW2-4 ON = 30 sec., OFF = 0 sec.;
Switch times are additive. {A ll OFF = 1 sec.; All ON = 65
sec.}
W
D
W
D
= WET = DRY

ACCESS
CONTROL
OR
REMOTE
RELEASE
DOOR
MONITORING
(DPS or BAS)
DOOR #1DOOR #2
ACCESS
CONTROL
OR
REMOTE
RELEASE
DOOR
MONITORING
(DPS or BAS)
FAIL-SECURE
LOCK
(12 OR 24 VDC)
FAIL-SAFE LOCK
(12 OR 24 VDC)
+
+
-
-
DOOR
#1
LOCK
FAIL-SECURE
LOCK
(12 OR 24 VDC)
FAIL-SAFE LOCK
(12 OR 24 VDC)
+
+
-
-
DOOR
#2
LOCK
FAIL-SECURE
LOCK
(12 OR 24 VDC)
FAIL-SAFE LOCK
(12 OR 24 VDC)
+
-
DOOR
#4
LOCK
FAIL-SECURE
LOCK
(12 OR 24 VDC)
FAIL-SAFE LOCK
(12 OR 24 VDC)
+
+
-
-
DOOR
#3
LOCK
ACCESS
CONTROL
OR
REMOTE
RELEASE
DOOR
MONITORING
(DPS or BAS)
DOOR #3DOOR #4
ACCESS
CONTROL
OR
REMOTE
RELEASE
DOOR
MONITORING
(DPS or BAS)
+
-
12/24 VDC
POWER
SUPPLY
SDC 600
Series
+
-
INSTALLATION NOTES:
1. Access Control inputs are shown Norally Open.
Door Monitoring circuits are shown open when the door
is in the closed position. Use dip switches SW2-6 &
SW2-5, respectively, to configure the polarity.
2. All Lock Relay Outputs (1, 3, 5, & 7) have been
configured to have wet (voltage) outputs. Lock output
voltage will be the sae as the UR4-8 input voltage.
3. Monitoring Relay Outputs have been configured to
follow the Door Monitoring Input.
+
(-)
CA1CA2CB1CB2CC1CC2CD1CD2CE1CE2CE3CE4
(
-
)
N
O
N
C
C
(
-
)
N
O
N
C
C
(
-
)
N
O
N
C
C
(-)
N
O
N
C
C
W
D
W
D
FUSEW
D
W
D
FUSEW
D
W
D
FUSEW
D
W
D
FUSE
MANTRAP “B” MODE
OUTPUT 2OUTPUT 4OUTPUT 6OUTPUT 8
OUTPUT 1OUTPUT 7
OUTPUT 5
OUTPUT 3
(
-
)
N
O
N
C
C
(
-
)
N
O
N
C
C
(
-
)
N
O
N
C
C
(
-
)
N
O
N
C
C
Power Input
12/24 VDC
LOCK
ALL
(Optional)
UNLOCK
ALL
(Optional)
EMERGENCY
RELEASE
(Optional)
LOCKOUT
(Optional)
P:\INSTALLATION INST\Power Supplies\INST-UR\INST-UR4-8.vsd REV A1 11-14 Pae 8
Monitoring
Relay
Output
(Optional)
Monitoring
Relay
Output
(Optional)
Monitoring
Relay
Output
(Optional)
Monitoring
Relay
Output
(Optional)
MOV
*
MOV
*
MOV
*
MOV
*
*MOV for Inductive Kickback protection.
See Step 3 on P . 7
DIP SWITCHES
Set as shown on
Pa e 7, Step 1

VII. 2, 3, or 4-Door Interlock “C” Setup
Follow the installation steps below before applyin power to the UR4-8.
Refer to the INTERLOCK “C” MODE wirin dia ram on Page 10.
NOTE: It is assumed that the UR4-8 and lockin hardware share the
same power supply.
Interlock “C” Standard Operation:
Refer to Page 3 – Section VII for method of operation.
Step 1 – Set Dip Switches
The dip switch settin s below are an example of a typical Interlock “C”
setup as shown on Pa e 10.
A) Use dip switches SW1-1 thru SW1-4 to select the Interlock “C” mode
B) Adjust dip switches SW2-1 thru SW2-7 as needed. All other dip
switches should remain as shown below.
Step 2 – Configure the Relay Outputs to be Wet
(Voltage) or Dry.
Use the red WET/DRY Selection Jumpers to confi ure each output.
Refer to Pa e 2 of this instruction for selection procedure.
On the typical Interlock C wirin dia ram, the Lock Relays (Outputs 1, 3,
5, & 7) are confi ured to be wet outputs. The Monitorin Relays (Outputs
2, 4, 6, & 8) are dry.
NOTE: It is recommended that any unused relays be confi ured as dry
outputs.
Step 3. Ter inate the Lock Power Wiring
Follow the typical Interlock “C” wirin dia ram for fail-safe or fail-secure
locks. Be careful to observe lock volta e polarity.
*
WARNING!:
The UR board Relay Outputs must be protected a ainst
inductive kickback enerated when power is removed from an inductive
load (e. ., electric strikes). Refer to the lock manufacturer's installation
manual or contact the manufacturer for kickback protection
recommendations.
NOTE: All low volta e wirin shall be 18- au e minimum. The minimum
lock power wire au e shall be determined by the SDC wire au e chart.
Si nal wire shall be 22- ua e minimum.
Step 4. Ter inate the Access Control and Door
Monitoring Inputs
NOTE: The Interlock “C” wirin dia ram is shown confi ured for a 4-door
system (3 normally locked doors, and 1 normally unlocked door).
Connect the Door Monitorin Switches to input terminals A1, B1, C1, &
D1. This is a required connection for all door stations bein used.
Connect Access Control or remote releases to input terminals A2, B2, C2,
& D2. This connection is ONLY required for normally locked doors.
Door Monitorin and Access Control inputs should be dry, Normally Open
or Normally Closed switches, dependin on the confi uration of Dip
Switches 2-5 and 2-6, respectively.
NOTE: Dip Switch 2-5 confi ures the normal state of the Door Monitorin
input when the door is in a CLOSED and/or LOCKED position. If
Normally Closed inputs are used, all unused inputs will need to be
shorted.
Step 5. Ter inate Optional Inputs and Outputs
Auxiliary Inputs – These inputs must be wired as dry, Normally Open
switches. The input will only be active when closed (shorted). Refer to
Pa e 2 for input descriptions.
Monitorin Relay Outputs – Each door station provides a non-fused,
SPDT monitorin relay. This output may be used to si nal a Security
Panel or to activate a Remote Annunciator. The relay is confi urable as a
Wet or Dry output (Step 2). The relay activation will follow the Lock Relay
or follow the Door Monitorin Input, dependin on the confi uration of Dip
Switch 2-7 (Step 1).
Step 6. Connect a 12 or 24VDC Power Source to the
UR4-8 Controller.
Before applyin power, verify that all the connections are securely
terminated by gently pulling on each wire.
Terminate the volta e wirin to the Controller Power Input. Be careful to
observe polarity.
Verify that all the doors are closed & apply power to the controller.
Step 7. UR4-8 Controller Startup and Operation
Verification.
Verify the polarity of the Access Control & Door Monitorin Inputs by
observin the Status Li hts located on the lower ri ht of the UR4-8
controller.
Status Li hts A1, B1, C1, & D1 will be OFF if Dip Switch 2-5 = OFF, or
will be ON if Dip Switch 2-5 = ON.
Status Li hts A2, B2, & C2 will be OFF if Dip Switch 2-6 = OFF, or will be
ON if Dip Switch 2-6 = ON.
Test the standard operation of the interlock by unlockin any door or by
openin the unlocked door(s). All other doors will be incapable of bein
opened/unlocked until the opened door returns to its normal state.
SW
1 - 1
SW
1 - 2
SW
1 - 3
SW
1 -4
2-Door Door 1 - Locked; Door 2 Unlocked ON OFF OFF OFF
Door 1 - Locked; Door 2 & 3 - Unlocked ON OFF OFF OFF
Door 1 & 2 - Locked; Door 3 - Unlocked ON ON OFF OFF
Door 1 - Locked; Doors 2, 3 & 4 - Unlocked ON OFF OFF OFF
Doors 1 & 2 - Locked; Doors 3 & 4 - Unlocked ON ON OFF OFF
Doors 1, 2, & 3 - Locked; Door 4 - Unlocked ON ON ON OFF
3-Door
4-Door
Interlock "C" Configurations
P:\INSTALLATION INST\Power Supplies\INST-UR\INST-UR4-8.vsd REV A1 11-14 Pa e 9
SW2-1= ON
SW2-2 = OFF
SW2-3 = OFF
SW2-4 = OFF
SW2-5 = OFF Sets the polarity of the Doo r M onito ring Inputs when the doo r
is in the CLOSED position. {OFF = N/O; ON = N/C}
SW2-6 = OFF Sets the polarity of A ccess Contro l Inputs when the switch is in
a no rmal (resting) state. {OFF = N/O; ON = N/C}
SW2-7 = OFF
Sets the o peratio n o f all the M onito ring Relay Outputs.
{OFF = Relay will follo w the Do or M o nito ring Input;
ON = Relay will fo llow the Lock Output Relay}
SW2-8 = ON
SW1-1=
SW1-2 =
SW1-3 =
SW1-4 =
SW1-5 = OFF
SW1-6 = OFF
SW1-7 = OFF
SW1-8 = OFF
Refer to the table belo w to set Dip Switches 1-1 thro ugh 1-4
SW2-1 through 2-4 set the unlock time of the Lo ck Relay for
normally locked do o rs.
N O T E : This is in addition to yo ur Access Co ntro l System
unlock time.
SW2-1 ON = 5 sec., OFF = 0 sec.;
SW2-2 ON = 10 sec., OFF = 0 sec.;
SW2-3 ON = 20 sec., OFF = 0 sec.;
SW2-4 ON = 30 sec., OFF = 0 sec.;
Switch times are additive. {A ll OFF = 1 sec.; A ll ON = 65 sec.}
W
D
W
D
= WET = DRY

ACCESS
CONTROL
OR
REMOTE
RELEASE
DOOR
MONITORING
(DPS or BAS)
DOOR #1DOOR #2
ACCESS
CONTROL
OR
REMOTE
RELEASE
DOOR
MONITORING
(DPS or BAS)
DOOR
MONITORING
(DPS or BAS)
DOOR #3DOOR #4
DOOR
MONITORING
(DPS)
LOCK
ALL
(Optional)
UNLOCK
ALL
(Optional)
EMERGENCY
RELEASE
(Optional)
12/24 VDC
POWER
SUPPLY
SDC 600
Series
+
-
INSTALLATION NOTES:
1. Access Control input is shown Norally Open. Door
Monitoring circuits are shown open when the door is in
the closed position. Use dip switches SW2-6 & SW2-5,
respectively, to configure the polarity.
2. All Lock Relay Outputs (1, 3, 5, & 7) have been
configured to have wet (voltage) outputs. Lock output
voltage will be the sae as the UR4-8 input voltage.
3. All doors require Door Monitoring Inputs. Only
Norally Locked doors require Access Control Inputs.
4. Monitoring Relay Outputs have been configured to
follow the Door Monitoring Input.
+
(-)
(
-
)
N
O
N
C
C
(
-
)
N
O
N
C
C
(
-
)
N
O
N
C
C
(-)
N
O
N
C
C
W
D
W
D
FUSEW
D
W
D
FUSEW
D
W
D
FUSEW
D
W
D
FUSE
INTERLOCK “C” MODE
(
-
)
N
O
N
C
C
(
-
)
N
O
N
C
C
(
-
)
N
O
N
C
C
(
-
)
N
O
N
C
C
Power Input
12/24 VDC
ACCESS
CONTROL
OR
REMOTE
RELEASE
LOCKOUT
(Optional)
FAIL-SECURE
LOCK
(12 OR 24 VDC)
FAIL-SAFE LOCK
(12 OR 24 VDC)
+
+
-
-
DOOR
#1
LOCK
FAIL-SECURE
LOCK
(12 OR 24 VDC)
FAIL-SAFE LOCK
(12 OR 24 VDC)
+
+
-
-
DOOR
#2
LOCK
FAIL-SECURE
LOCK
(12 OR 24 VDC)
FAIL-SAFE LOCK
(12 OR 24 VDC)
+
-
DOOR
#4
LOCK
FAIL-SECURE
LOCK
(12 OR 24 VDC)
FAIL-SAFE LOCK
(12 OR 24 VDC)
+
+
-
-
DOOR
#3
LOCK
+
-
OUTPUT 2OUTPUT 4OUTPUT 6OUTPUT 8
OUTPUT 1OUTPUT 7
OUTPUT 5
OUTPUT 3
CA1CA2CB1CB2CC1CC2CD1CD2CE1CE2CE3CE4
P:\INSTALLATION INST\Power Supplies\INST-UR\INST-UR4-8.vsd REV A1 11-14 Pae 10
Monitoring
Relay
Output
(Optional)
Monitoring
Relay
Output
(Optional)
Monitoring
Relay
Output
(Optional)
Monitoring
Relay
Output
(Optional)
MOV
*
MOV
*
MOV
*
MOV
*
*MOV for Inductive Kickback protection. See Step 3 on P . 9
DIP SWITCHES
Set as shown on
Pa e 9, Step 1

P:\INSTALLATION INST\Power Supplies\INST-UR\INST-UR4-8.vsd REV A1 11-14 Pa e 11
VIII. Dual Relay Control Mode Setup
Follow the installation steps below before applyin power to the UR4-8.
Refer to the DUAL RELAY CONTROL MODE wirin dia ram on Page
12.
NOTE: It is assumed that the UR4-8 and locks will share the same power
supply.
Standard Operation:
Refer to Page 3 – Section VIII for method of operation.
Step 1 – Set Dip Switches
The dip switch settin s below are an example of the typical Dual Relay
Control Mode Setup as shown on Pa e 12.
A) Use dip switches SW1-1 throu h SW1-8 to select the operation of
each tri er input: CR, TD, or LR.
B) Adjust dip switches SW2-1 thru SW2-5 as needed. All other dip
switches shall remain as shown below.
Step 2 – Configure the Relay Outputs to be Wet
(Voltage) or Dry.
Use the red WET/DRY Selection Jumpers to confi ure each output.
Refer to Pa e 2 of this instruction for selection procedure.
On the typical Dual Relay Control Mode wirin dia ram, the Lock Relays
(Outputs 1, 3, 5, & 7) are confi ured to be wet outputs. The Monitorin
Relays (Outputs 2, 4, 6, & 8) are dry.
The relay output volta e will be the same as the UR4-8 input volta e (12
or 24 VDC).
NOTE: It is recommended that any unused relays be confi ured as dry
outputs.
Step 3. Ter inate the Lock Power Wiring
Follow the typical Dual Relay Control Mode wirin dia ram for fail-safe or
fail-secure locks. Be careful to observe lock volta e polarity.
*
WARNING!:
The UR board Relay Outputs must be protected a ainst
inductive kickback enerated when power is removed from an inductive
load (e. ., electric strikes). Refer to the lock manufacturer's installation
manual or contact the manufacturer for kickback protection
recommendations.
NOTE: All low volta e wirin shall be 18- au e minimum. The minimum
lock power wire au e shall be determined by the SDC wire au e chart.
Si nal wire shall be 22- ua e minimum.
Step 4. Ter inate the Station Trigger Inputs
Connect each station’s tri er input 1 and input 2, as required.
All the tri er inputs should be dry, momentary, Normally Open or
Normally Closed switches, dependin on the confi uration of Dip Switch
2-5 (Step 1).
NOTE: Dip Switch 2-5 confi ures the normal (restin ) state of the tri er
input. If Normally Closed inputs are used, all unused tri er inputs will
need to be shorted.
Step 5. Ter inate Optional Inputs and Outputs
Auxiliary Inputs – These inputs must be wired as dry, Normally Open
switches. The input will only be active when closed (shorted). Refer to
Pa e 2 for input descriptions.
Monitorin Relay Outputs – Each door station provides a non-fused,
SPDT monitorin relay. This output may be used to si nal a Security
Panel or to activate a Remote Annunciator. The relay is confi urable as a
Wet or Dry output (Step 2). The relay activation will follow the Lock
Relay.
Step 6. Connect a 12 or 24VDC Power Source to the
UR4-8 Controller.
Before applyin power, verify that all the connections are securely
terminated by gently pulling on each wire.
Terminate the volta e wirin to the Controller Power Input. Be careful to
observe polarity.
Verify that all the tri er inputs are in their normal (restin ) state & apply
power to the controller.
Step 7. UR4-8 Controller Startup and Operation
Verification.
Verify the polarity of each Station tri er input by observin the Status
Li hts located on the lower ri ht of the controller.
Status Li hts A1, A2, B1, B2, C1, C2, D1 & D2 will be OFF if Dip Switch
2-5 = OFF, or will be ON if Dip Switch 2-5 = ON.
Test the standard operation of each station control relay by momentarily
pressin the tri er input.
In CR mode, the respective door will unlock while the tri er input is
activated, and relock when the tri er is released.
In TD mode, the respective door will unlock when the tri er input is
activated. Releasin the tri er input will start the unlock timer and the
door will remain unlocked. The door will relock after the set unlock time
has expired.
In LR mode, the respective door will unlock when the tri er input is
momentarily activated and released. The door will remained unlocked
indefinitely until the tri er input is reactivated.
W
D
W
D
= WET = DRY
SW2-1= OFF
SW2-2 = OFF
SW2-3 = OFF
SW2-4 = OFF
SW2-5 = OFF Sets the polarity of A LL the trigger inputs when the trigger is
in a non-activated state. {OFF = N/O; ON = N/C}
SW2-6 = OFF
SW2-7 = ON
SW2-8 = OFF
SW1-1= OFF Statio n A, Input 1 M ode Selectio n {OFF = CR; ON = TD}
SW1-2 = OFF Statio n A, Input 2 M ode Selectio n {OFF = CR; ON = LR}
SW1-3 = OFF Statio n B, Input 1 M ode Selectio n {OFF = CR; ON = TD}
SW1-4 = OFF Statio n B, Input 2 M ode Selectio n {OFF = CR; ON = LR}
SW1-5 = OFF Statio n C, Input 1 M o de Selection {OFF = CR; ON = TD}
SW1-6 = OFF Statio n C, Input 2 M o de Selection {OFF = CR; ON = LR}
SW1-7 = OFF Statio n D, Input 1M o de Selectio n {OFF = C R; ON = TD}
SW1-8 = OFF Statio n D, Input 2 M o de Selection {OFF = CR; ON = LR}
When using TD mode, SW 2-1 thro ugh 2-4 sets the unlo ck
delay time o f the relays.
SW2-1ON = 5 sec., OFF = 0 sec.;
SW2-2 ON = 10 sec., OFF = 0 sec.;
SW2-3 ON = 20 sec., OFF = 0 sec.;
SW2-4 ON = 30 sec., OFF = 0 sec.;
Switch times are additive. {All OFF = 1 sec.; All ON = 65 sec.}

LOCK
ALL
(Optional)
UNLOCK
ALL
(Optional)
EMERGENCY
RELEASE
(Optional)
12/24 VDC
POWER
SUPPLY
SDC 600
Series
+
-
INSTALLATION NOTES:
1. All inputs are shown configured as Nor ally Open
switches.
2. All Lock Relay Outputs (1, 3, 5, & 7) have been
configured to have wet (voltage) outputs. Lock output
voltage will be the sa e as the UR4-8 input voltage.
3. The Monitoring Relay Output will always follow the
lock relay.
+
(-)
(
-
)
N
O
N
C
C
(
-
)
N
O
N
C
C
(
-
)
N
O
N
C
C
(-)
N
O
N
C
C
W
D
W
D
FUSE W
D
W
D
FUSE W
D
W
D
FUSE W
D
W
D
FUSE
DUAL RELAY CONTROL
MODE
(
-
)
N
O
N
C
C
(
-
)
N
O
N
C
C
(
-
)
N
O
N
C
C
(
-
)
N
O
N
C
C
Power Input
12/24 VDC
LOCKOUT
(Optional)
INPUT 1 INPUT 2
Station A Triggers Station B Triggers Station C Triggers Station D Triggers
C A1 C A2 C B1 C B2 C C1 C C2 C D1 C D2 C E1 C E2 C E3 C E4
FAIL-SECURE
LOCK
(12 OR 24 VDC)
FAIL-SAFE LOCK
(12 OR 24 VDC)
+
+
-
-
Station
A
LOCK
FAIL-SECURE
LOCK
(12 OR 24 VDC)
FAIL-SAFE LOCK
(12 OR 24 VDC)
+
+
-
-
Station
B
LOCK
FAIL-SECURE
LOCK
(12 OR 24 VDC)
FAIL-SAFE LOCK
(12 OR 24 VDC)
+
-
Station
D
LOCK
FAIL-SECURE
LOCK
(12 OR 24 VDC)
FAIL-SAFE LOCK
(12 OR 24 VDC)
+
+
-
-
Station
C
LOCK
+
-
OUTPUT 4
OUTPUT 2
OUTPUT 1 OUTPUT 3 OUTPUT 6 OUTPUT 8
OUTPUT 7OUTPUT 5
P:\INSTALLATION INST\Power Supplies\INST-UR\INST-UR4-8.vsd REV A1 11-14 Pa e 12
INPUT 1 INPUT 2 INPUT 1 INPUT 2 INPUT 1 INPUT 2
Monitoring
Relay
Output
(Optional)
Monitoring
Relay
Output
(Optional)
Monitoring
Relay
Output
(Optional)
Monitoring
Relay
Output
(Optional)
MOV
*
MOV
*
MOV
*
MOV
*
*MOV for Inductive Kickback protection.
See Step 3 on P . 11
DIP SWITCHES
Set as shown on
Pa e 11, Step 1

IX. Single Relay Control Mode Setup
Follow the installation steps below before applyin power to the UR4-8.
Refer to the SINGLE RELAY CONTROL MODE wirin dia ram on Page
14.
NOTE: It is assumed that the UR4-8 and locks will share the same power
supply.
Standard Operation:
Refer to Page 4 – Section IX for method of operation.
Step 1 – Set Dip Switches
The dip switch settin s below are an example of the typical Single Relay
Control Mode Setup as shown on Pa e 14.
A) Use dip switches SW1-1 throu h SW1-8 to select the operation of
each tri er input: CR, TD, or LR.
If dip switch SW2-6 = OFF, each input is selectable as a CR or TD only.
If dip switch SW2-6 = ON, each input is selectable as a LR or TD only.
B) Adjust dip switches SW2-1 thru SW2-5 as required. All other dip
switches should remain as shown below.
Step 2 – Configure the Relay Outputs to be Wet
(Voltage) or Dry.
Use the red WET/DRY Selection Jumpers to confi ure each output.
Refer to Pa e 2 of this instruction for selection procedure.
On the typical Sin le Relay Control Mode wirin dia ram, all relay outputs
are confi ured as wet outputs.
The relay output volta e will be the same as the UR4-8 input volta e (12
or 24 VDC).
NOTE: It is recommended that any unused relays be confi ured as dry
outputs.
Step 3. Ter inate the Lock Power Wiring
Follow the Sin le Relay Control Mode wirin dia ram for fail-safe or fail-
secure locks. Be careful to observe lock volta e polarity.
*
WARNING!:
The UR board Relay Outputs must be protected a ainst
inductive kickback enerated when power is removed from an inductive
load (e. ., electric strikes). Refer to the lock manufacturer's installation
manual or contact the manufacturer for kickback protection
recommendations.
NOTE: All low volta e wirin shall be 18- au e minimum. The minimum
lock power wire au e shall be determined by the SDC wire au e chart.
Si nal wire shall be 22- ua e minimum.
Step 4. Ter inate the Station Trigger Inputs
Connect each station’s tri er input as required.
All the tri er inputs should be dry, momentary, Normally Open or
Normally Closed switches, dependin on the confi uration of Dip Switch
2-5 (Step 1).
NOTE: Dip Switch 2-5 confi ures the normal (restin ) state of the tri er
input. If Normally Closed inputs are used, all unused tri er inputs will
need to be shorted.
Step 5. Ter inate Optional Inputs and Outputs
Auxiliary Inputs – These inputs must be wired as dry, Normally Open
switches. The input will only be active when closed (shorted). Refer to
Pa e 2 for input descriptions.
Step 6. Connect a 12 or 24VDC Power Source to the
UR4-8 Controller.
Before applyin power, verify that all the connections are securely
terminated by gently pulling on each wire.
Terminate the volta e wirin to the Controller Power Input. Be careful to
observe polarity.
Verify that all the tri er inputs are in their normal (restin ) state & apply
power to the controller.
Step 7. UR4-8 Controller Startup and Operation
Verification.
Verify the polarity of each Station tri er input by observin the Status
Li hts located on the lower ri ht of the controller.
Status Li hts A1, A2, B1, B2, C1, C2, D1 & D2 will be OFF if Dip Switch
2-5 = OFF, or will be ON if Dip Switch 2-5 = ON.
Test the standard operation of each station control relay by momentarily
pressin the tri er input.
In CR mode, the respective door will unlock while the tri er input is
activated, and relock when the tri er is released.
In TD mode, the respective door will unlock when the tri er input is
activated. Releasin the tri er input will start the unlock timer and the
door will remain unlocked. The door will relock after the set unlock time
has expired.
In LR mode, the respective door will unlock when the tri er input is
momentarily activated and released. The door will remained unlocked
indefinitely until the tri er input is reactivated.
P:\INSTALLATION INST\Power Supplies\INST-UR\INST-UR4-8.vsd REV A1 11-14 Pa e 13
W
D
W
D
= WET = DRY
SW2-1= OFF
SW2-2 = OFF
SW2-3 = OFF
SW2-4 = OFF
SW2-5 = OFF Sets the polarity of A LL the trigger inputs when the trigger is in
a no n-activated state. {OFF = N/O; ON = N/C}
SW2-6 = OFF {OFF = Each trigger input is selectable as CR or TD o nly;
ON = Each trigger input is selectable as LR or TD only}
SW2-7 = OFF
SW2-8 = OFF
SW1-1= OFF Station 1 M ode Selectio n {OFF = CR or LR; ON = TD}
SW1-2 = OFF Station 2 M ode Selection {OFF = CR o r LR; ON = TD}
SW1-3 = OFF Station 3 M ode Selectio n {OFF = CR or LR; ON = TD}
SW1-4 = OFF Station 4 M ode Selectio n {OFF = CR or LR; ON = TD}
SW1-5 = OFF Station 5 M ode Selection {OFF = CR o r LR; ON = TD}
SW1-6 = OFF Station 6 M ode Selection {OFF = CR o r LR; ON = TD}
SW1-7 = OFF Station 7 M ode Selection {OFF = CR o r LR; ON = TD}
SW1-8 = OFF Station 8 M ode Selection {OFF = CR o r LR; ON = TD}
When using TD mode, SW 2-1 through 2-4 set the unlo ck
delay time o f the Lock Relay.
SW2-1ON = 5 sec., OFF = 0 sec.;
SW2-2 ON = 10 sec., OFF = 0 sec.;
SW2-3 ON = 20 sec., OFF = 0 sec.;
SW2-4 ON = 30 sec., OFF = 0 sec.;
Switch times are additive. {A ll OFF = 1 sec.; A ll ON = 65 sec.}

Station A1
Trigger
LOCK
ALL
(Optional)
UNLOCK
ALL
(Optional)
EMERGENCY
RELEASE
(Optional)
+
(-)
(
-
)
N
O
N
C
C
(
-
)
N
O
N
C
C
(
-
)
N
O
N
C
C
(-)
N
O
N
C
C
W
D
W
D
FUSEW
D
W
D
FUSEW
D
W
D
FUSEW
D
W
D
FUSE
SINGLE RELAY CONTROL
MODE
(
-
)
N
O
N
C
C
(
-
)
N
O
N
C
C
(
-
)
N
O
N
C
C
(
-
)
N
O
N
C
C
Power Input
12/24 VDC
LOCKOUT
(Optional)
Station A2
Trigger
Station B1
Trigger
Station B2
Trigger
Station C1
Trigger
Station C2
Trigger
Station D1
Trigger
Station D2
Trigger
FAIL-SECURE
LOCK
(12 OR 24 VDC)
FAIL-SAFE LOCK
(12 OR 24 VDC)
+
+
-
-
Station
A1
LOCK
FAIL-SECURE
LOCK
(12 OR 24 VDC)
FAIL-SAFE LOCK
(12 OR 24 VDC)
+
+
-
-
Station
C1
LOCK
INSTALLATION NOTES:
1. All inputs are shown
configured as Norally
Open switches.
2. All relay outputs have
been configured to have
wet (voltage) outputs.
Relay output voltage will be
the sae as the UR4-8
input voltage.
3. Outputs 2, 4, 6, & 8 are
non-fused.
CA1CA2CB1CB2CC1CC2CD1CD2CE1CE2CE3CE4
OUTPUT 4
OUTPUT 2
OUTPUT 1OUTPUT 3OUTPUT 6OUTPUT 8
OUTPUT 7
OUTPUT 5
FAIL-SECURE
LOCK
(12 OR 24 VDC)
FAIL-SAFE LOCK
(12 OR 24 VDC)
+
+
-
-
Station
A2
LOCK
FAIL-SECURE
LOCK
(12 OR 24 VDC)
FAIL-SAFE LOCK
(12 OR 24 VDC)
+
+
-
-
Station
B1
LOCK
FAIL-SECURE
LOCK
(12 OR 24 VDC)
FAIL-SAFE LOCK
(12 OR 24 VDC)
+
+
-
-
Station
B2
LOCK
FAIL-SECURE
LOCK
(12 OR 24 VDC)
FAIL-SAFE LOCK
(12 OR 24 VDC)
+
+
-
-
Station
C2
LOCK
FAIL-SECURE
LOCK
(12 OR 24 VDC)
FAIL-SAFE LOCK
(12 OR 24 VDC)
+
+
-
-
Station
D1
LOCK
FAIL-SECURE
LOCK
(12 OR 24 VDC)
FAIL-SAFE LOCK
(12 OR 24 VDC)
+
+
-
-
Station
D2
LOCK
P:\INSTALLATION INST\Power Supplies\INST-UR\INST-UR4-8.vsd REV A1 11-14 Pae 14
MOV
*
MOV
*
MOV
*
MOV
*
MOV
*
MOV
*
MOV
*
MOV
*
12/24 VDC
POWER
SUPPLY
SDC 600
Series
+
-
*MOV for Inductive Kickback protection. See Step 3 on P . 13
DIP SWITCHES
Set as shown on
Pa e 13, Step 1

X. 2-Door Co unicating Bath Syste
Setup (Single or Dual)
Follow the installation steps below before applyin power to the UR4-8.
Standard Operation:
Refer to Page 4 – Section IX for method of operation.
Refer to the 2-Door Communicating Bath System wirin dia ram on
Page 16.
It is assumed that the UR4-8 and locks will share the same power supply.
Step 1 – Set Dip Switches
The dip switch settin s for a 2-Door Communicatin Bath System must be
set as shown below. Adjust SW1-7 as required.
Step 2 – Configure the Relay Outputs to be Wet
(Voltage) or Dry.
Use the red WET/DRY Selection Jumpers to confi ure each output.
Refer to Pa e 2 of this instruction for selection procedure.
For a Single Comm nicating Bath System:
Outputs 1, 2, 3, & 4 are confi ured to be wet outputs.
Outputs 5, 6, 7, & 8 are confi ured as dry outputs.
For D al Comm nicating Bath Systems:
All outputs are confi ured to be wet outputs.
The relay output volta e will be the same as the UR4-8 input volta e (12
or 24 VDC).
Step 3. Ter inate the Activation and E ergency
Unlock Buttons
For each system, connect the (2) Emer ency Unlock buttons and (1)
Activation button as shown on the Communicatin Bath system wirin
dia ram.
All button switches are wired Normally Open.
Lamp volta e is not polarity sensitive.
NOTE: All low volta e wirin shall be 18- au e minimum. The minimum
lock power wire au e shall be determined by the SDC wire au e chart.
Si nal wire shall be 22- ua e minimum.
Step 4. Ter inate the Lock Power and Lock
Monitoring Options
Select your specific lock type below. Follow the typical Communicatin
Bath system wirin dia ram. Be careful to observe lock volta e polarity.
*
WARNING!:
The UR board Relay Outputs must be protected a ainst
inductive kickback enerated when power is removed from an inductive
load (e. ., electric strikes). Refer to the lock manufacturer's installation
manual or contact the manufacturer for kickback protection
recommendations.
NOTE: All lock monitorin options below (LBM, DPS, and/or REX) shown
wired so that the circuit is OPEN when the doors are CLOSED and
LATCHED.
Using EMLocks®:
Using Fail-safe Uni-FLEX™ Electric Strikes:
Using Fail-safe Selectric® Pro Locks:
Step 6. Connect a 12 or 24VDC Power Source to the
UR4-8 Controller.
Before applyin power, verify that all the connections are securely
terminated by gently pulling on each wire.
Terminate the volta e wirin to the Controller Power Input. Be careful to
observe polarity.
Verify that both doors are closed & apply power to the controller.
Step 7. UR4-8 Controller Startup and Operation
Verification.
Verify the polarity of the inputs by observin the Status Li hts located on
the lower ri ht of the controller.
With the system at rest, Status Li hts A1, A2, B1, B2, & C1 should all be
turned off.
Test the standard operation of the Communicatin Bath System as
described on Pa e 4.
P:\INSTALLATION INST\Power Supplies\INST-UR\INST-UR4-8.vsd REV A1 11-14 Pa e 15
EMLock® with DPS
(12 OR 24 VDC)
3 4 5 6 7 8
NC
C
NO
DPS
LOCK
PWR
To Lock
Monitoring
Input
LBM
Fail-safe Electric Strike
w/ Latch Bolt Monitoring (LBM)
NOTE: Mechanical locksets are
configured for “Storeroo ”
function.
NO
+
-
LOCK
PWR
To Lock
Monitoring
Input
NC
C
MOV
*
Fail-safe Electrified Mortise Lock
w/ Door Position Switch (DPS) &
Request-to-Exit Switch (REX)
C
NO
+
-
NC
C
NO
NC
DPS
REX To Lock
Monitoring
Input
LOCK
PWR
MOV
*
SW1-1= OFF
SW1-2 = OFF
SW1-3 = OFF
SW1-4 = OFF
SW1-5 = OFF
SW1-6 = OFF
SW1-7 = OFF {OFF = Single Comm Bath System;
ON = Dual Comm Bath System}
SW1-8 = ON
SW2-1= OFF
SW2-2 = OFF
SW2-3 = OFF
SW2-4 = OFF
SW2-5 = OFF
SW2-6 = OFF
SW2-7 = OFF
SW2-8 = ON

12/24 VDC
POWER
SUPPLY
SDC 600
Series
+
-
INSTALLATION NOTES:
1. For a Single Co . Bath Syste , ter inate Syste “A” wiring
only. For Dual Co . Bath Syste s, ter inate Syste “A” & “B”
wiring.
2. Refer to the lock’s installation instructions for the lock wiring
details.
3. For a single syste , outputs 1- 4 are configured as wet (voltage)
outputs. For dual syste s, all outputs are configured as wet (voltage)
outputs. Output voltage will be the sa e as the UR4-8 input voltage.
+
(-)
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
SW1
SW2
(-)
N
O
N
C
C
(-)
N
O
N
C
C
(-)
N
O
N
C
C
(-)
N
O
N
C
C
W
D
W
D
FUSE W
D
W
D
FUSE W
D
W
D
FUSE W
D
W
D
FUSE
2-Door Communi ating Bath
(Single or Dual System)
(-)
N
O
N
C
C
(-)
N
O
N
C
C
(-)
N
O
N
C
C
(-)
N
O
N
C
C
Power Input
12/24 VDC
C A1 C A2 C B1 C B2 C C1 C C2 C D1 C D2 C E1 C E2 C E3 C E4
OUTPUT 1
P:\INSTALLATION INST\Power Supplies\INST-UR\INST-UR4-8.vsd REV A1 11-14 Pa e 16
OUTPUT 3
L
CB402B
E ergency
Button
(Syste A – Door #1)
OUTPUT 2
Fail-safe Lock
(Syste A – Door #1)
LOCK
POWER
+
(-)
FROM LOCK
MONITORING
OUTPUT
NO
NC
C
L
CB402B
E ergency
Button
(Syste A – Door #2)
Fail-safe Lock
(Syste A – Door #2)
LOCK
POWER
+
(-)
FROM LOCK
MONITORING
OUTPUT
NO
NC
C
OUTPUT 4
NO
NC
C
L
CB402B
E ergency
Button
(Syste B – Door #2)
Fail-safe Lock
(Syste B – Door #2)
LOCK
POWER
+
(-)
FROM LOCK
MONITORING
OUTPUT
OUTPUT 5 OUTPUT 6 OUTPUT 7 OUTPUT 8
NO
NC
C
L
CB402B
E ergency
Button
(Syste B – Door #1)
Fail-safe Lock
(Syste B – Door #1)
LOCK
POWER
+
(-)
FROM LOCK
MONITORING
OUTPUT
NO
NC
C
L
CB402A
Activation
Button
(Syste A)
NO
NC
C
L
CB402A
Activation
Button
(Syste B)
DIP SWITCHES
Set as shown on
Pa e 15, Step 1
Table of contents
Other SDC Controllers manuals
Popular Controllers manuals by other brands

LOVATO ELECTRIC
LOVATO ELECTRIC RGK800SA instruction manual

Greenheck
Greenheck 474706 reference guide

gefran
gefran GEFLEX-ETHERNET Installation and operation manual

TECH
TECH ST-21D5 user manual

Kutai electronics
Kutai electronics ADVR-083-400HZ Operation manual

Emerson
Emerson Fisher EZR series installation guide