Seat C 2SP User manual

Type C 2SP remote
controller
REF 819756/819757
The type C 2-speed remote controller is a safety device for controlling air flow regulation
at low and high speed depending on the position of the sash.
A speed sensor is used to determine the flow rate. Audible and visual alarm is set off in
case of insufficient speed or too high sash height and other malfunctions. The controller
engages the second gear by means of a contactor placed in the path of the sash.
The remote HMI is used to control the fume cupboard ventilation and to carry out the
following adjustments on site.
This controller complies with EN 14175 and RoHS Standards.

2
Table of contents
1. Presentation .................................................................................................................................... 3
1.1. HMI (Human Machine Interface) ................................................................................................ 3
1.2. CPU (Central Processing Unit) ..................................................................................................... 3
1.3. Schematic diagram ...................................................................................................................... 4
1.4. Connector specifications ............................................................................................................. 5
2. Installation and mounting ............................................................................................................... 6
2.1. Dimensions.................................................................................................................................. 6
2.2. Positioning on the fume hood..................................................................................................... 7
2.3. Cutting template ......................................................................................................................... 8
2.4. Installation tips............................................................................................................................ 9
3. Wiring diagram.............................................................................................................................. 10
4. Adjustment procedure .................................................................................................................. 11
5. Factory rest.................................................................................................................................... 13
6. Test mode...................................................................................................................................... 13
7. Change the audible alarm delay.................................................................................................... 14
8. Error messages (digital display option) ......................................................................................... 14
9. FAQ................................................................................................................................................ 14
10. Maintenance.............................................................................................................................. 15
11. Warranty.................................................................................................................................... 15
02/11/2021

3
1. Presentation
The remote type C 2SP remote controller consists of a small HMI, easily installed on a fume
hood, and a central processor.
1.1. HMI (Human Machine Interface)
1.2. CPU (Central Processing Unit)
Display
(Option)
Green LED: air flow OK
Red LED: insufficient air flow
Orange LED: Sash too high
Yellow LED: Ventilation ON/OFF
Push button: ON/OFF ventilation
Yellow LED: Lighting ON/OFF
Push button: ON/OFF lighting
Orange LED: auxiliary faults
Push button: stop buzzer
VENT1 : ON/OFF
ventilation relay
VENT2 : ON/OFF
ventilation relay
Alarm contact
Light relay
Overtaking sash
contact
Second velocity
switch
Output 0/10V
Transformer 230v/12v
connector
Speed probe
connector
Push-button
velocity display
Cut the resistance to activate
the night setback mode
Remote HMI
connector

4
1.3. Schematic diagram
220v power
supply
FAN1 ON/OFF
0/10V
220v
power
supply
Switch sash
position
Velocity probe
Deported HMI CPU box
Second
velocity switch
The remote type C 2-speed controller is used to control the airflow of a fume hood.
Pressing the ventilation ON/OFF button on the remote HMI closes the two relays VENT 1 and 2, which
unlocks the drive. The controller then sends a 0/10v signal that the drive will interpret in order to change
the motor rotation speed and the flow rate. This is a two-speed controller: the CPU sends a fixed voltage
when the sash is low and another fixed voltage when it is high.
A speed sensor permits to measure whether the suction flow is sufficient (≥0.4 m/s) and indicates the
ventilation status by a green and red LED.
The front panel allows you to control the operation of the fume hood and in particular:
-An ON/OFF for lighting
-An ON/OFF for ventilation
-An alarm stop button

5
1.4. Connector specifications
Power supply
Electrical transformer 230v/12v 500mA. (delivered with)
VENT1/FAN1
ON/OFF Ventilation relay driving by
Disconnection voltage: 120v
Disconnection current: 0.5 A
VENT2/FAN2
Same VENT1
0/10v
0/10v output which returns a voltage according to the speed
measured by the sensor. This output must be sent to the
frequency inverter.
a
LIGHT
ON/OFF lighting relay driving by
Disconnection voltage: 220v
Disconnection current: 3 A
ALARM
Relay controlled by alarm activation. Normally open contact
Disconnection voltage: 120v
Disconnection current: 0.5 A
SASH Open
Sash contact which triggers a visual and audible alarm.
IDLE
Sash Contact which toggles from low speed to high speed.

6
2. Installation and mounting
2.1. Dimensions
HMI
CPU
Speed sensor
65 mm
40 mm
28 mm
22 mm

7
2.2. Positioning on the fume hood
The speed sensor must be positioned on
the fume hood ceiling in one of the two
positions shown in the diagram.
These locations must be respected so that
the probe is accurate.
Drill a 22mm diameter hole and put the
speed sensor in it.
An adhesive is provided on the sensor to
fix it correctly to the fume hood and
prevent leaks.
Where to install the speed sensor?
500mm
150 mm
Vertical HMI are usually attached to
the side frame of fume hoods.
Horizontal HMI’s can be set at the
user’s convenience.
◌
To comply with EN 14175
standard, you must install a
sash contact.
The sash contact must be fixed so that
it sets off when the sash exceeds
400mm or 500mm.
◌
The 2nd gear contact is installed
approximately 150mm above the work
surface.
◌
You can install the CPU
in the false ceiling of
the fume cupboard.
The controller is delivered with
a 2,5 meters cable.

8
2.3. Cutting template
If you want to install your fume hood controller without the surface bow mounting, you will
need to make the following cuts:
31mm
110mm

9
2.4. Installation tips
•Do not install the sensor on the extraction tube above the fume hood
•Avoid installing the sensor in a dead zone of the fume cupboard
•The probe must pass entirely through the fume cupboard ceiling. Otherwise, you
must use a 25mm PVC tube to extend the outlet.
•A speed of 0.2 m/s minimum must be measured through the sensor to ensure proper
operation.
•When adjusting the controllers, it is necessary that:
oThe fans are running
oThe laboratory is completely closed (doors, windows, etc.)
oHave an anemometer
•Pay attention to motor connections (star or delta)
230V single phase
power supply
400V three phases
power supply
400V three phases
output
230V three phases
output
DELTA
STAR

10
3. Wiring diagram
220v power
supply
220v power
supply
0/10V
ON/OFF
ventilation
Switch sash
position
Second velocity
switch
Switch sash position
2nd speed switch

11
4. Adjustment procedure
This controller requires a 0/10v setpoint setting for low and high speed and a display setting
in case you have the display option.
Low speed adjustment
Press 3s
Release
Press
simultaneously
Put the sash in down position. Wait 15 seconds for the speed
to stabilize
2
Enter the setting mode: Press and hold for at least 3 seconds on release and then
press and simultaneously on and shortly. The beep will then sound twice, and
the red LED will flash. You are in the setting mode. If you have the display option, the
screen will display the voltage that the controller is communicating.
3
Switch on ventilation with
1
Press on to increase the speed
Press on to decrease the speed
Once the anemometer measures a speed ≥
0.4 m/s, the 0/10v setpoint is adjusted.
Each press increments the setpoint voltage
by 0.5V over a range of 0.5V to 10V.
4
A press on increase the
0/10V reference sent to the
drive.
+ 0.5 volt
A press on decrease
the 0/10V reference sent to
the drive.
- 0.5 volt
To validate the low speed setpoint and exit the adjustment mode, press and hold down .
The low speed is set, now you have to set the high speed.
5
Sash
closed

12
High speed adjustment
Put the sash in the upper position (400 or 500 mm) The
second speed switch is then sets off. Wait 15 seconds for
the speed to stabilize.
6
Guillotine
ouverte
Press 3s
Release
Press
simultaneously
Press on to increase the speed
Press on to decrease the speed
Once the anemometer measures a speed ≥
0.4 m/s, the 0/10v setpoint is adjusted.
Each press increments the setpoint voltage
by 0.5V over a range of 0.5V to 10V.
8
A press on increase the
0/10V reference sent to the
drive.
+ 0.5 volt
A press on decrease
the 0/10V reference sent to
the drive.
- 0.5 volt
Enter the setting mode again: Press and hold for at least 3 seconds on release and press
simultaneously on and shortly. The beep will then sound twice, and the red LED
will flash. You are in the setting mode. The controller recognizes directly that you want to set
the high speed.
7

13
5. Factory rest
6. Test mode
“Test”mode confirms that all functions of the instrument are operational. To enter Test
mode, Follow the procedure:
Press the push button on the electronic
board for 15 seconds (the buzzer then rings
5 times to indicate that the procedure is
working properly).
This procedure resets the factory settings:
Setpoint and display to 0.5m/s, 7V analogue
output and all relays and LEDs to off.
Press the 3 buttons simultaneously
Then the buzzer sounds twice.
1
Press the 3 buttons one after the other to check their correct operation:
•The buzzer sounds 3 times to indicate normal operation.
•The buzzer sounds 10 times if the function is faulty.
•
2
Once the setting has been made, a long press on
allows to both enter and exit the adjustment
mode.
The controller is now ready for use.
10
IF DIGITAL DISPLAY MODEL
Press the push-button on the rear face to
synchronize the speed reading on the anemometer
and the speed displayed on the controller. One push
increases by 0.1 m/s over a range of 0.3 à 0.7 m/s
9

14
7. Change the audible alarm delay
It is possible on the rear face to change the buzzer’s trigger time with
the two switches.
8. Error messages (digital display option)
The controller displays « HI » for a frontal speed greater than 0.8 m/s.
The controller displays « LO » for a frontal speed lower than 0.2 m/s.
The controller displays « PB » in case of speed sensor problem.
9. FAQ
Questions
Solutions
No indicators
Check that the power supply is correctly connected.
The fan does not start up
Check that the controllers ON button is fully engaged and that
the yellow light above is on.
Check wiring.
The display shows “PB”
Check that the speed sensor is correctly connected to the
controller.
Turn off and then restore power to the controller.
The light does not illuminate
The controller does not provide power, it provides a normally
open contact. The light must be connected in the same way as if
it were controlled by a switch.
The frontal speed is too low
Check the direction of rotation of the motor. Check that the
system of installation is correct.
Front speed is too high
Check that the sizing of the installation is correct.
The display shows “8.8.8”
You are in Test mode: see the settings on page 12 to exit this
mode.
The green LED is on and the
red LED is flashing
You are in setting mode: see pages 11-12 to exit this mode.
The alarm sounds after a
short time
Change the alarm delay with the CPU switches: see at the top of
this page.
The speed does not change
Check with a voltmeter if the 0/10v output varies:
-If it changes, check the drive connections.
-If it does not change, check the correct positioning of the
probe on the fume cupboard and carry out the
adjustment procedure.
1 = ON: Alarm still active
1 = OFF: Alarm disabled if ventilation is off
2 = ON: Delay set as 30s
2 = OFF: Delay set as 15s
ON
OFF

15
10. Maintenance
•Do not use abrasive materials.
•Avoid splashing liquid on the plastic box.
•Do not install the sensor on the extraction tube above the fume hood.
•Do not install the sensor in a dead zone of the fume hood.
•The sensor must not be subjected to air flow disturbances.
•The sensor must lead to the laboratory pressure.
•When setting up the controller, it is necessary that:
oThe fan is running
oThe lab must be completely closed (doors, windows, etc.)
oHave an anemometer
11. Warranty
SEAT Ventilation guarantees that its equipment, products and parts are free from
manufacturing defects under normal conditions of use for a period of two years after delivery
to the first user. If a factory return is required within the two-year period from the date of
purchase, contact your distributor. Products must be returned to the point of purchase with
a dated invoice.

16
SEAT VENTILATION SAS
PARC TECHNOLOGIQUE DELTA SUD
09340 VERNIOLLE
France
E-mail: [email protected]
Site Web: www.seat-ventilation.com
This manual suits for next models
2
Table of contents
Other Seat Remote Control manuals
Popular Remote Control manuals by other brands

Hearth and Home Technologies
Hearth and Home Technologies IntelliFire Plus REM300-HNG-AU Installation & operating instructions

noken
noken SMART PLUS PROGRAM manual

Viessmann
Viessmann VITOTROL 200 RF Installation and service instructions

Philips
Philips ProntoPRO SBC RU970 Product information

Opalum
Opalum FLOW series Pairing guide

Sony
Sony RM-NWS1 operating instructions