ENFORCER Access Power Distribution Boards
SECO-LARM U.S.A., Inc. 5
Installation (Continued):
Connect the power supply's positive terminal to the power distribution board output
terminal or this device marked "C."
iv. For ail-sa e operation, connect the positive input o the powered device to the
terminal marked "NC."
v. For ail-secure operation, connect the positive input o the powered device to the
terminal marked "NO."
c. Unswitched auxiliary power outputs (to provide power to card readers, keypads, etc.)
i. Connect the positive input o the powered device to the terminal marked "C."
ii. Connect the negative input o the powered device to the terminal marked "COM."
NOTE: Keep power limited wiring separated rom non-power limited wiring (AC input, battery
wiring) by a minimum distance o
1
/
4
" (7mm) and use separate knockouts in the
enclosure.
5. Connect each controlling device (card reader, keypad, RTE plate, etc.) to the corresponding
input terminal or the particular device to be controlled. Inputs are activated by normally open
or open collector sink inputs.
a. Normally open (N.O.) input triggers:
i. Connect the devices to the terminals marked "IN" and "GND" that correspond to the
power output terminals o the device to be controlled.
b. Open collector sink inputs:
i. Connect the access control panel open collector output to the power distribution
board's input terminal marked "IN."
ii. Connect the access control panel open collector's common (negative) to the power
distribution board's input terminal marked "GND."
6. Connect an Auxiliary Inter ace Control Panel (AICP) to the power distribution board's Aux.
Inter ace. A normally open, normally closed, or polarity reversal input rom an AICP signaling
circuit will trigger selected outputs. To enable AICP disconnect or any output, set the
corresponding DIP switch or that output to "ON." To disable AICP disconnect or any output,
set its corresponding DIP switch to "OFF" (de ault, "OFF").
a. Normally open (N.O.) input:
i. For a non-latching hookup, re er to the instructions or Fig. 1 on pg. 7.
ii. For a latching hookup, re er to the instructions or Fig. 4 on pg. 7.
b. Normally closed (N.C.) input:
i. For a non-latching hookup, re er to the instructions or Fig. 2 on pg. 7.
ii. For a latching hookup, re er to the instructions or Fig. 5 on pg. 7.
c. AICP signaling circuit input trigger
i. For a polarity reversal input rom the AICP Auxiliary Output, re er to the instructions
or Fig. 3 on pg. 7.
7. The AICP Auxiliary Output may also be connected as a dry orm C output as ollows:
a.
Connect the device to be triggered by the unit's dry contact output to the power distribution
board's Aux. Inter ace terminals as ollows:
i. For normally open output, connect to the terminals marked "NO" and "C."
ii. For normally closed output, connect to the terminals marked "NC" and "C."
The unit should be tested at least once a year or proper operation. Voltage on eac
should be tested or both triggered and untriggered states and the operation o the AICP