Seg MRD1-G User manual

MRD1-G -Generator Differential Protection System

2TB MRD1-G 11.01 E
Contents
1 Introduction and Application
2 Features and Characteristics
3Design
3.1.1 Relay front
3.1.2 Display
3.1.3 LEDs
3.1.4 Push-buttons
3.1.5 Parameter interface RS232
3.1.6 Disturbance recorder (optionally)
3.2 Master module
3.2.1 Interface RS485
3.2.2 CAN-Bus (optionally)
3.2.3 Function inputs and signal inputs
(optionally)
3.3 Basic module
3.3.1 Basic module NT 6I
4 Working principle
4.1 Protective functions
4.1.1 Generator differential protection
4.2 Analogue measured value detection
4.2.1 Current measuring
4.3 Digital signal processor
4.4 Digital main processor
4.5 Block diagram
4.6 General functions
4.6.1 Event-Recorder
4.6.2 Fault-Recorder
4.6.3 Self-test relay
4.6.4 Self-test
4.6.5 Output relay settings
4.6.6 Parametrizing blocking
5Operation
5.1 General
5.1.1 Data organization
5.1.2 Parameter sets
5.1.3 Key function
5.1.4 LEDs
5.1.5 VIEW mode / EDIT mode
5.1.6 OFFLINE-TEST mode
5.1.7 Reset (DEVICE RESET)
5.1.8 Enter password
5.1.9 Password forgotten
5.2 SYSTEM settings
5.2.1 Selection
5.2.2 Overview
5.2.3 Time / Date
5.2.4 Password change
5.3 PARAMETER-pages
5.3.1 Selection
5.3.2 Overview
5.3.3 Generator ratings
5.3.4 Protection parameters
5.3.5 Relay-settings
5.3.6 Setting of logic functions
5.3.7 Blocking Setting
5.3.8 Validity check
5.4 DATA pages
5.4.1 Selection
5.4.2 Overview
5.4.3 Measured and calculated data
5.4.4 FAULT Recorder
5.4.5 EVENT-Recorder
5.4.6 Statistic data
5.5 TEST-routines page (Self-test)
5.5.1 Page selection
5.5.2 Overview
5.6 Parameter programming help
6RelayTests
7 Commissioning
7.1 Check list
7.2 C.T. connection
8 Technical Data
8.1 MRD - G Generator Differential
Protection Relay
9 Tables / Connection diagrams
9.1 Possible event messages
9.2 View
10 Type code
This technical manual is valid for software version
V01-1.03.

TB MRD1-G 11.01 E 3
1Introduction and Application
MRD1
is a modular system to protect electrical appa-
ratus and it is used for complex applications in the
energy distribution, primarily designed for transformer,
generator, motor or line protection; additionally it can
be integrated into automation systems. Due to its
modular design, the MRD1
can
be
adapted to indi-
vidual applications without problem, with all imple-
mented functions remaining combined in one single
device. All vacant rack places in the basic unit can op-
tionally be used for modules according to require-
ments. The modules provide the necessary measuring
inputs e.g. for two-winding or three-winding transform-
ers as well as increase the number of output relays or
digital inputs according to requirements.
The high-performance digital technique of data calcu-
lation makes complex mathematical algorithm for
measured value processing possible for
the MRD1
as
well as utilization of the trip decision resulting from the
individual protection functions. The MRD1
software is
also of modular structure. Each protection function is al-
located to a special program segment and so it is
possible to subsequently add further functions.
All essential parameters, measuring data or values
calculated from these can be called off and are shown
locally on the display. The MRD1
is equipped with an
Event Recorder which stores all system signals, protec-
tion activations or trip events. When trips occur a Fault
Recorder records all fault data mesaured at the instant
of the trip. Data of both recorders is provided with a
time stamp and can be called off either at the display
or interface.
For exact fault analysis a Disturbance Recorder can
optionally be integrated which stores all measured
fault data and time characteristic of the sampled signal
after a trip event, filed on an easy exchangeable
memory card.
At present the following versions of MRD1
are avail-
able :
•MRD1-T2 Transformer differential protection for
two-winding transformers
•MRD1-T3 Transformer differential protection for
three-winding transformers
•MRD1-G Differential protection for generators and
motors

4TB MRD1-G 11.01 E
2Features and Characteristics
Basic Unit
Standard equipment
•Modular design
with automatic short circuiting C.T.-inputs
•Signal and data processing in a separate digital
signal processor (32 samples per cycle)
•Digital filtering of measured quantities
•Three possibilities of parameter setting and data
calling:
1) keyboard and display
2) RS232 interface at the front (lap top)
3) RS485 interface for integration into control
systems at the rear
•Safety interlocking preventing parameter setting via
different ways at the same time
•extensive internal plausibility check of modified pa-
rameters
•Event Recorder for recording system messages
•Fault Recorder for recording measured fault data
•Four programmable independent parameter sets
•Non-volatile memory for parameter sets, events and
fault data
•Indication of measured operational values and re-
sulting quantities
•Wide-ranging automatic self-tests
•Small relay size
•Three possibilities for relay resetting
•Indication of relay function optically or via separate
selfsupervision relay
•All data interfaces galvanical isolated
•Rated frequency selectable: 50 Hz/60 Hz
•Parameter setting protected by password
Functions which can be programmed by the user :
•Protection
and system parameters
•Latched position or minimal signal duration for
each of the output relays
Optional equipment
•CAN Bus
•FO connection (fibre optic) for RS485 interface
•Disturbance recorder on PCM card
•Addition of further protection functions after installa-
tion of additional software modules
Generator differential protection
•Stabilization against CT measuring errors
•No complete blocking of differential element but
only reduced sensivity
•Independent High Set differential element for heavy
faults

TB MRD1-G 11.01 E 5
3Design
This chapter informs briefly about operation elements
and indication elements of the MRD1. Name and po-
sition of the individual modules are also described. In
chapter 5 operating of the relay and type specific
functions are explained in more detail.
!Note
NoteNote
Note
Front view and rear view illustrations of the MRD1 as
well as connection diagrams can be found at the end
of the manual.
3.1.1 Relay front
Display in Home Position
3.1.2 Display
The MRD1
is provided with a 16-digit, double-line
liquid crystal display (LCD), which is of alphanumerical
design for an easy dialog. The figure above shows the
basic status of the display. Dependent on the mode se-
lected, the following data can be shown on the dis-
play:
•Date / Time / Relay type (Home Position)
•Measured operational data
•Measured fault data
•System parameters and protection parameters
•System signals and fault signals
3.1.3 LEDs
Additionally to the display there are max. 30 LEDs at
the front, indicating each of the operational status in
the MRD1. All LEDs are two-coloured (red/green) and
arranged in two groups:
a) System and relay status indications
The 15 system indications are arranged underneath
the alphanumerical display. They are allocated to a
certain function and show:
•Operational voltage available
•Trip
•OFFLINE TEST mode active
•Edit mode active
•Displayed parameter is modified but has not been
stored yet
•Switch status of the 5 (optionally 10) output relays
•Display of the relay function (self-test)
b) Status display of the 15 digital inputs (if provided)
These 15 indications are shown at the left of the dis-
play informing about the status of the digital inputs.
3.1.4 Push-buttons
All necessary MRD1
adjustments and inquiries can be
carried out from the front of the relay by pressing the
respective push-button (9 in total). Individual function of
these push-buttons is explained in chapter Operating.
3.1.5 Parameter interface RS232
At the left of the relay front there is a 9-pole, D-SUB
plug-and-socket connector for temporary lap-top con-
nection. At this connection a serial interface RS-232 is
provided. A standard IBMTM compatible PC or port-
able notebook can be connected to this PC interface.
To connected MRD1 and PC a 1:1 modem-cable with
9-pole plug-and-socket is used. By using SEG software
HTLSOFT 3, which is WindowsTM compatible, MRD1
parameters can comfortably be set. Additionally all
measured operational and fault data can be read out
of the relay integrated non-volatile memories and the
optional fault recorder.
3.1.6 Disturbance recorder (optionally)
The right rack place at the relay front is reserved for
the disturbance recorder and consists of a duct for the
storage medium which is a PC memory card accord-
ing to the PC card standard (PCMCIA) in this case.

6TB MRD1-G 11.01 E
3.2 Master module
The master module is fitted right in the middle and con-
tains componentries for data processing, the main
processor and the following connections:
3.2.1 Interface RS485
Interface RS485 at the rear of the relay is a permanent
connection between the MRD1 and the host computer.
This interface operates at a constant transmission ratio
of 9600 Baud if |SEG protocol "RS485pro" is used.
Via RS485 interface all measured operational and
fault data as well as operational status indications can
be read out - identical to RS232 interface. Remote set-
ting of parameters is also possible from the control sta-
tion. The 8-pole plug-and-socket connector contains all
necessary connections for this interface.
3.2.2 CAN-Bus (optionally)
This data interface is used for integrating the MRD1
into special automation systems and for specific func-
tion additions (e.g. temperature measuring module,
graphic-display module). For the CAN Bus interfaces
two 9-pole D-SUB plug-and-socket connectors are
used.
3.2.3 Function inputs and signal inputs
(optionally)
These 15 digital inputs (contacts 1-15) are combined
on the 16-pole plug-and-socket connector. The six-
teenth contact is the common return wire. Any incom-
ing information
a) can direct be assigned to selectable output relays.
This application method enables recording of the con-
tact status (open or closed) of external protection de-
vices.
b) can logically be interlinked with MRD1 internal pro-
tection functions. The logical interlinking result can than
be assigned to output relays.
An input can be considered active when a voltage
quantity within the permissible high range (see Tecni-
cal Data) is connected to the input contact and the
common return wire. If the voltage is lower, the input is
classed as being inactive. Specific function of the indi-
vidual inputs can be defined during programming (see
chapter 6). Digital inputs are galvanical isolated from
the relay electronics.

TB MRD1-G 11.01 E 7
3.3 Basic module
Plug-in units 1 and 3 are intended for individual appli-
cations and at our works they are equipped with mod-
ules for measuring value detection in compliance with
the relay function. (see folding page)
!Important Note
The MRD1 must only be dismantled or opened by authorized staff .
Removal of live modules entail severe danger for the person(s) involved because there can no sufficient protection
against accidental contact be guaranteed as soon as the relay has been opened. Furthermore there is the risk of
the modules being damaged by electrostatic discharge (ESD/EGB) when handled improperly.
Identical modules must not be exchanged between different MRD1 basic versions.
..
.
Calibration of every MRD1 is done at work with regard to the specific features of that relay.
A random change
of modules would lead to unreliable operation of the relay because the compatibility of the relay components
among each other would be in disorder and could not be guaranteed any longer.
Any modification jobs on the MRD1, for instance, exchange of modules or software additions, are only allowed
to be done at our works or by authorized agents.
3.3.1 Basic module NT 6I
For generator, motor and transformer differential pro-
tection, module NT-61 is plugged into the first space.
Measuring inputs
The module consists of six current measuring channels
which are used for measuring the three conductor cur-
rents of each winding. The CT start point must be
formed outside the relay since all 12 CT connections
are wired separately on terminals. In addition to other
measuring or protection devices the MRD1 can be
looped in to existing CT lines, assumed the CT being
able to carry the total burden.
Apart from further connections for voltage supply of the
relay, the module is also provided with a digital input
for remote resetting as well as connection facilities for
the five output relays. Four of these are free to be used
acc. to requirement, the fifth is assigned for Selftest Re-
lay.
RESET Input
If a voltage is applied to terminals of the RESET input
(C8-D8), the MRD1 is reset to its basic status. By this
procedure possible alarms and trip signals are can-
celled.
The voltage applied for resetting must be within the
permissible high-range (see technical data), although it
must not necessarily be identical with the latter. The
input is galvanical isolated from the relay electronics.
Contact D8 is also the neutral or minus for the block-
ing input.
Blocking Input
If a voltage is applied to the terminals of the blocking
input (D8-E8), all protection functions assigned to the
output relays are blocked. Terminal D8 is also the neu-
tral or minus for the input.
Alarm relays
Potential free outputs of the five alarm relays provided
are at terminals C, D and E, series 1 to 7. Exact allo-
cation can be taken from the connection diagram. Re-
lay 5 is permanently assigned to Selftest Relay. Func-
tion allocation of the remaining relays is free and can
be defined when programming (see chapter 5). Two
of these four relays are provided with two changeover
contacts each and the other two with one changeover
contact each.

8TB MRD1-G 11.01 E
4Working principle
In this chapter the individual functions and working
principle of the MRD1
are described.
4.1 Protective functions
4.1.1 Generator differential protection
Term Explanation
ID Bias current This is the current passing through the generator from the starpoint side to the grid
side. This current is representing the normal load.
Id Differential current The difference between grid side current and star point side current of one wind-
ing.
Ia Pickup current If the differential current exceeds the pickup current, the relay trips.
Fault current due to
operational condi-
tions
This kind of fault current is the component of the measured differential current
which, however, is not caused by a fault of the object to be protected but is of
systematic nature
Stabilization Under this heading all measures are compiled which stabilize the differential relay
against nuisance tripping. Stabilizing always means the pickup current is raised
and by this the differential relay becomes more intensitive, but is never completely
blocked.
ISStabilizing current This current develops from the bias current and represents the extent of stabilizing
measures necessary as result of the fundamental analysis. Parameters of the
pickup characteristic can be set.
mHarmonic stabilizing
factor
This factor, derived from the analysis of the harmonic frequency, is apart from IS
the second stabilizing factor and in case of rush and saturation by following a
special characteristic makes the differential relay stable against tripping errors.
d[Id] Characteristic Offset The characteristic curve is raised up by the value d[Id] immediately after a har-
monic stabilization factor “m” is measured to be greater than zero. This is to give
a basic stabilization after detection of inrush or ct-saturation during external fault
by means of harmonic measurement.
Pickup characteristic This characteristic defines the stabilizing current dependence on the pickup current
Table 1: Term definitions

TB MRD1-G 11.01 E 9
General idealized view
Differential protection is a strict selective object protec-
tion and is based on the current measuring principle at
the input and output side of the object being pro-
tected. Dependent on the earthing method used, the
neutral can also be included in measuring and bal-
ance.
The area between input and output CTs of the object
is classed as protection zone supervised by the
MRD1. Included in the protection zone are also CTs
and CT connection wire to the relay.
protected area
MRD
Mains
STAR
point
generator stator
Fig. 1: Definition of protection zone
The relay checks constantly if the incoming currents of
a winding are met by respective outgoing currents. If
the balance of the conductor currents shows a differ-
ence, this may suggest a fault within the protection
zone.
Note!
Motors and generators are to be handled from the dif-
ferential protection in the same way.
To distinguish between faults occuring within (inter-
nally) or outside (externally) of the protection zone is
the main purpose of the differential protection because
at internal faults the differential protection relay must
trip, but not so at external faults.
Examples:
External fault
During a short circuit occuring at the grid, the short cir-
cuit current flows through the generator. The difference
between incoming and outgoing currents of all genera-
tor terminals is small (in ideal cases = zero) I1-I2= 0.
The differential protection relay does not trip. (Switch-
ing off in such cases probably to be realized by an
overcurrent relay).
MRD
Mains
STAR
point
generator stator
I1I2
short circuit
current
Fig. 2: External fault
Internal fault
When an internal fault occurs the current balance is
different. Dependent on the kind of fault a deficit in the
total of incoming currents can be observed. A winding
short circuit, for instance, can be fed from both sides,
even if with different intensity. But this short circuit does
not go through the generator, it is fed from both sides
into the generator. So therefore the current balance
shows a difference.
MRD
Mains
STAR
point
generator stator
I1I2
short circuit
current
short circuit
current
Id
Fig. 3: Internal fault (example of a short circuit fed from
two sides)
Due to the chosen direction of the reference arrow,
current I2flows here in negative direction.
The differential relays detects a current difference of
I1-I2= Id and trips when Id has exceeded the set
threshold.

10 TB MRD1-G 11.01 E
Stabilizing
At first approximation this idealized view applies to
stationary states only. In reality other effects, especially
CT errors, may cause the established current difference
to rise, even if there is no internal fault. In such cases a
simple static differential relay would mistakenly trip
and to prevent this stabilizing measures have to be
taken. Possible sources of measuring errors are sys-
tematic and can be duly taken into account.
Stabilizing the MRD1
means always an action to
make the relay more insensitive.
Fundamental analysis
Distortion factors for differential current measuring are:
•Measuring errors of angle and value of the CTs
used
•Poor adjustment of rated CT data to rated genera-
tor data
By these factors a fault current is caused which mainly
depends on the biasing current. This fault current is be-
ing measured as a differential current, although a
generator fault must not necessarily have occured.
When the pickup current is set at a very sensitive
value, each of these factors can cause unintended
trippings. With increasing bias current the pickup cur-
rent has to be corrected upwardly.
The following pickup characteristic (exact characteris-
tic) gives an detailed study of the individual fault fac-
tors and the resulting fault current. In fig. 4 the ex-
pected fault current versus tripping characteristic is
shown.
If a real fault occurs, the measured differential current
exceeds the biasing current caused by operational
conditions. Therefore the pickup characteristic must ex-
ceed the biasing current characteristic by the required
sensitivity value. The exact course can be approxi-
mated by a simplified characteristic consisting of two
linear sections (I and II). The higher the characteristic
begins, the higher the permissible differential current. If
the characteristic begins at a very low point this means
maximum sensitivity. If the pickup characteristic is be-
low the biasing characteristic, systematic effects can
cause unintended trips.
Stabilisierungsstrom
stabilizing current
Is / In
Differenzstrom
differential current
Id / In
I
II
AUSLÖSUNG
TRIP
KEINE AUSLÖSUNG
NO TRIP
tatsächlicher Fehlerstromlinie
exact fault characteristic
Angenäherte Kennlinie
approximated characteristic
Fig. 4: Typical pickup characteristic (without considering transient processes)
Calculation of the differential current and stabilizing current resulting from the fundamental oscillation (current of
the positive phase sequence system) produces a point on the characteristic. If this point is within the tripping
range, the output relay picks up. In case of harmonics of 4th or 5th order in the differential current the characteristic
curve is raised up statically by the parameter d[Id] and dynamically by the measuring value m (characterizes the
harmonic contents).

TB MRD1-G 11.01 E 11
Tripping procedure
The protection program permanently checks the meas-
urements that the DSP (digital signal processor) deliv-
ers. When the DSP gives a new differential current the
protection task checks whether it lies within the tripping
limits. If this is the case the MRD1 is internally ener-
gized. Tripping occurs when the calculated difference
current is consecutively three times within the tripping
limits. To prevent the energized state from being reset
too quickly, a hysteresis of 75 % is programmed. This
means that a newly calculated difference current must
be smaller than 75 % of the present characteristic trip
value in order for the energized condition to be reset.
The total tripping time of the Relay is below 35 ms.

12 TB MRD1-G 11.01 E
4.2 Analogue measured value detection
4.2.1 Current measuring
For measuring the relevant currents there is a separate
transducer for each of the existing measured quantities.
This transducer provides galvanical isolation to the re-
lay electronics. Adjustment to the main CT rated cur-
rents is realized via the software. The input signal is
transmitted by internal CTs up to 64 times rated current
linear. To achieve an utmost accuracy there are two
current measuring ranges, changeover of which is
automatically.
Each channel has its own sample-and-hold circuit. All
channels are scanned simultaneously.
4.3 Digital signal processor
The digital signal processor (DSP) in the MRD1 is
mainly used for processing measured values by con-
trolling and monitoring data entry from the different
measuring channels. In addition all input signals are
digitally Fourier filtered. Among other values this proc-
essor calculates RMS values and stores digitalized sig-
nal sequences to the memory and the signal recorder
(option). Apart from data management and processing
the DSP keeps performing wide-ranging self-tests.
4.4 Digital main processor
The main processors is the highest control element
within the MRD1
and processes
the actual protection
program which interprets data obtained by the DSP
and so refers to the operational status of the object to
be protected and to the own device. Special protec-
tion mechanism enable the MRD1 to detect problems
in the own hardware. All communication between
MRD1
and
the outside world is also controlled by the
main processor. This does not only mean control of in-
dications or handling of key inputs but also harmoniz-
ing the different data interfaces as well as control of
output relays.

TB MRD1-G 11.01 E 13
4.5 Block diagram
∩
∩∩
∩
∩
∩∩
∩
RS
485
serial
ports
display and keyboard
CTs
real time
clock
CAN
Bus1
CAN
Bus2
LWL
CAN-
con-
tro-
ller
fault
memory
program
memory
analogue measurements
PCM
memory card
serial PC-interface
RS232
signal-
processor
main
processor
central module
extension module
base module
main processor bus
optional
communi-
cation
parameter-
memory
blocking
input
supply
5
output
relays
SOFTWARE
Relay
matrix
∩
∩∩
∩
#
##
#
RESET
input
dual ported
memory
5
output
relays
G
Mains
side
Star
point

14 TB MRD1-G 11.01 E
4.6 General functions
4.6.1 Event-Recorder
The MRD1 is provided with an event recorder for re-
cording events in a chronological order and then stores
them on a non-volatile memory. Any data entry has a
time stamp so that time of the event can always be
traced back. Data can be called off either via keys and
display or data interfaces.
Important events, such as trippings, are not only re-
corded in the memory but also shown on the display.
Pure informative events are stored in the recorder only
and are not displayed.
More details on calling off events and further information
on the event recorder can be found in chapter 5.
System messages are listed in chapter 9.1.
4.6.2 Fault-Recorder
At each tripping of the relays, the fault recorder records
all measured data and resulting quantities. Any tripping
event is automatically numbered consecutively in the re-
corder. Additionally to the measured data the following
details are also stored: the cause for tripping, serial
number of the incident as well as date and time at the
instant of tripping.
The MRD1
is able to record several incidents in a FIFO
memory. The longest stored data is overwritten when a
new incident occurs. Complete data of altogether 5 inci-
dents can always be called off.
More information on storage capacity and calling off re-
corder data via keyboard can be found in chapter 5.
4.6.3 Self-test relay
The self-test relay (relay 5) is energized during normal
operation of the MRD1 and deenergized in the follow-
ing events:
•failure of aux. voltage
•failure of internal partial power supply
•processor failure detected by the internal watchdog
•detection of an internal fault by software routines
•when protection function of the output relays is de-
coupled in OFFLINE TEST mode
•when the default parameterset was loaded and the
device automatically switched in OFFLINE TEST
mode
•self-test of the output relays is performed
•During power on initialisation

TB MRD1-G 11.01 E 15
4.6.4 Self-test
By pressing the TEST key several menu guided special
test routines can be started in the MRD1
for internal test
purposes. Some tests disable the generator protection.
These tests are locked by password.
The following tests and information can be performed/is
available:
Test / Inquiry Description Password
re-
quested
Protection
function
Software version number Number of version and date of software are in-
quired no remains active
LED-Test •all LEDs light-up red f. 2s
•all LEDs light up green f.2s no remains active
Test of output relays Sequence in one-second interval:
•self-test relay de-energizes
•all other relays de-energize
•all relays energize one after the other (with LED)
•relays return to actual position
•self-test relay energizes
yes inactive during the
test
Memory test Test of software and memory by checking the pro-
gram check sum no remains active

16 TB MRD1-G 11.97 E
4.6.5 Output relay settings
Reset time of the output relays:
With the exception of the self-supvervision relay, all exis-
ting output relays are assigned to the differential current
element. It is possible to define a proper reset time for
each individual relay. For this period - from the moment
of tripping - the relay remains in trip condition even if the
cause for the tripping does no more exist.
!Note:
If the time for which the relay has been energized ex-
ceeds the adjusted reset time, the relay will release ins-
tantaneously after trip condition is canceld. This is parti-
cularly important for relay tests (test of the reset time)
where the test current is not switched off immediately
with tripping.
TRIP condition
Auslösebedingung
Relay energized
Relais angezogen
RESET TIME
Mindestkommandozeit
t
RESET TIME
Mindestkommandozeit
1
0
1
0
Fig.: Reset time
If a relay is to remain self-holding after tripping, the reset
time has to be set to „exit“. Setting as per customer’s re-
quirements can be noted down in the „selection“line.
Relay
Basic equipment Option
12345678910
Function Idiff
Idiff >>
Idiff
Idiff >>
Idiff
Idiff >>
Idiff
Idiff >> ST Idiff
Idiff >>
Idiff
Idiff >>
Idiff
Idiff >>
Idiff
Idiff >>
Idiff
Idiff >>
Pre-adjustment
(in s) 0,20 0,20 0,20 0,20 •0,20 0,20 0,20 0,20 0,20
Custom setting •
Setting range: 0 -...1,00 s or exit (=latching- contact un-
til a DEVICE RESET is performed)
ST=Self-Test relay
•= no selection

TB MRD1-G 11.01 E 17
4.6.6 Parametrizing blocking
Blocking of protective function
The MRD1 offers a configurable blocking function.
When applying a voltage to terminals D8-E8 all protec-
tive functions are blocked that are configured for block-
ing. In case of active blocking the output relays don’t
act, but the device shows the fictive trip by means of
Trip-LED.
A minimum hold time can be set for the blocking. During
this time, starting from the begin of external blocking, all
protective functions are blocked, also in case the exter-
nal blocking may was released. In case of longer con-
tinuous external blocking the blocking can be stopped
after a maximum hold time tmax for enabling the relay to
trip in case of ongoing faults.
wirksame Blockierzeit
effective block. time
ext. Block. Eingang
ext. blockage input
t
min
t
t
max
!Note:
Repeated impulse at the blocking time within tmin restart
the hold times.
Assignment of functions to output relays
The MRD1 offers 5 output relays. Relay number 5 is
preassigned to the selftest function of the relay and is
working with zero-signal current principle. Output relays
1 –4, and 6 –10 are open-circuit relays and can be
assigned to internal logic functions.

18 TB MRD1-G 11.01 E
5Operation
5.1 General
5.1.1 Data organization
Data and settings in the MRD1 are subdivided into 4
groups and each of those are allocated to one menu
key or key combination. Related parameters or measur-
ing data of one group are combined on individual
pages. General settings can be made on the SYSTEM
parameter page. Test routines are also on separate
pages.
EVENT
Recorder
PARAMETER
measurements
data recorder
PARAMETER
page 3
parameter 3.1
parameter 3.2
parameter 3.3
...
...
...
...
PARAMETER
page 2
parameter 2.1
parameter 2.2
parameter 2.3
...
...
...
...
PARAMETER
page 1
parameter 1.1
parameter 1.2
parameter 1.3
...
TEST-
routines
TEST
routines
software version
relays test
LED test
memory test
4 parameter sets
SYSTEM-
parameter
SYSTEM
PARAMETER
clock setting
serial port options
work set selection
OFFLINE TEST m.
change password
restore default
rated frequency
FAULT
Recorder
...
...
...
+
DATA
page 1
measurement1.1
measurement 2.2
measurement 3.3
...
Statistic Data
Fig. 5.1: Data organization

TB MRD1-G 11.01 E 19
5.1.2 Parameter sets
MRD1 has access to four independent parameter sets.
Each of these data sets comprises a complete parameter
set which makes individual setting of the MRD1 possi-
ble. If required by the operational procedure several dif-
ferent settings can be stored and then called off when
needed.
Data of SYSTEM parameters (e.g. rated frequency,
slave address, date, time etc.) are not filled in the four
parameter sets, they do always apply.
EDIT-
memory
display / keyboard
serial interface
parameter set
1
parameter set
2
parameter set
3
parameter set
4
protection-
program
output
relay
message
display / LED
measurement
switch open in
Offline Test Mode
SYSTEM-
parameter
Generator
Fig. 5.1.2: Parameter sets, principle
For processing the selected set is loaded into the EDIT
memory (switch: Set to Edit). After parameters have been
changed, the EDIT memory is completely restored in the
parameter set memory. All changes are then jointly read-
in.
Another switch (Work Set) defines on which of the data
sets the protection program is based. All switches are
adjusted via software.
OFFLINE TEST mode is specified in chapter 5.1.6.

20 TB MRD1-G 11.01 E
5.1.3 Key function
Key
Function short actuated long actuated (2s)
a) from HOME POSITION:
View active parameter set
(VIEW mode)
b) leaf to next PARA page
from HOME POSITION:
"select one of the four parameter sets to edit
(EDIT-mode)
+
++
+#
from HOME POSITION:
"select SYSTEM-parameter page •
a) from HOME POSITION:
View DATA pages
b) leaf to next DATA page •
select the selftest routines page •
scrolling up / down
single step
scrolling up / down
fast
a) "change value. single step
b) move cursor
"change value, fast
a) confirm selection (YES)
b) toggle setting in EDIT mode
(yes/no ; on/off)
finish working in EDIT mode, perform parameter plausi-
bility check and save (if check passed) all modifications
a) reject selection (NO)
b) cancel modification
c) clear message
a) From HOME POSITION
DEVICE RESET
b) From Sub-Menu
back to home position
•- no operation
"- password protected
#- press and hold down PARA, press UP in addition to PARA, release both
!Note
NoteNote
Note
In the following paragraphs key symbols are mainly
used when explaining an operational procedure. Keys
with the term "long" on them have to be pressed for
about 2s for actuating the function. If there is nothing
stated, the respective key has only to be pressed briefly.
Fig.: Display in HOME POSITION
Table of contents
Other Seg Protection Device manuals
Popular Protection Device manuals by other brands

Ansell
Ansell HYD-TUF 52-547/10 Instructions for use

Safety Technology International
Safety Technology International STI-7522 Installation

Arcteq
Arcteq AQ-T256 instruction manual

Arcteq
Arcteq AQ 110 Series instruction manual

GE
GE Multilin 850 instruction manual

MSA
MSA V-TEC io1 Smart Hook PFL User instructions