Seitron RD ADA1 User manual

RDADA10001SE 029094 220917 ENGLISH
STARTING UP
Immediately after powering, the controller tart the en or
heating pha e; the di play how the me age "HEAt" with
the icon " " fla hing.
Later, during normal operation, the di play will how the CO
2
level detected.
The " " icon i alway on.
ON/OFF
By pre ing the key " ", if enabled, it i po ible to witch
the controller on and off ( ee tep 8 in the "In tallation"
paragraph).
BACKLIGHT
Pre ing any key activate the backlight of the di play which
will witch off automatically after approximately 30 econd .
TEST FUNCTION
To verify correct operation of the controller, pre and hold the
"TEST" key for more than 20 econd ; the "OUT 1" output
key will be activated and the di play will light up the " "
icon for approximately 30 econd and the me age in motion
"- - - -" will be hown to indicate that the te t i in progre .
Pre the key " " to exit the "TEST" function at any time.
ALARM THRESHOLD DISPLAY
During normal operation, by pre ing the "▲" or "▼" key ,
will how on the di play (for approximately 6 econd ) the CO
2
thre hold et.
RESET
To re et the controller remove voltage from the device for a
few econd and then witch it back on again.
Note: the data et will not be re et; the device will ju t be
activated again.
OPERATION
In normal operation, the LCD di play the " " icon
and the concentration of CO
2
(in ppm) mea ured in the
environment in which it i in talled.
If the device detect a concentration of CO
2
that i
greater
than the value et in the u er parameter 'CO2t', the output
OUT1 will be activated. Activation of the output will be
indicated on the di play by the icon " ".
The output will be di abled if the concentration of CO
2
fall
below the value et in the u er parameter "CO2t" minu the
hy tere i value of the device.
OUT 1 OUTPUT ACTIVATION GRAPH
Legend:
HYS: hy tere i value (fixed and immutable)
CO
2
T: alarm thre hold et
CO
2
R: CO
2
detected
FAULT CONDITION
The controller con tantly perform a diagno i of the internal
circuit to verify it correct operation.
Where a fault condition i detected, the di play will how the
'FAULT' icon and an indication of the type of fault detected
while the OUT1 output will be activated.
CALIBRATION:
The controller continuou ly perform a en or auto-calibration ,
ba ed on the mea urement of the la t 14 day , without
requiring the intervention of the operator.
LEVEL
TEST
LEVEL
OUT 1
HYS (CO
2
T) (CO
2
R) ppm
Relay status
N.C.
Position
N.O.
Position
ERROR MANAGEMENT
Sen or Fault
If the device detect an anomaly on the internal en or, the
di play will how the me age:
"SnEH" or "SnI2"
"SnEH": Fault
upper limit on the CO
2
Sen or.
Thi fault may be linked to environmental
condition : change the air in the environment and
wait a few hour .
If the fault per i t , replace the device.
"SnI2": Fault
communication with the CO
2
en or.
Thi fault can be re olved by re etting the device.
If the problem per i t , replace the device.
The e report will be pre ent until the fault i removed.
Internal memory fault
In the event that the device detect a data torage fault, the
di play will how the me age "SnE2" with the " " icon
fla hing.
Thi type of problem can be olved by re toring the device
default data, by acce ing the u er parameter 4 "dEFt" and
electing "dFon".
If the problem i re olved, it i po ible to manually re et all
the data to the value before re et.
Conver ely, if the fault per i t , replace the device.
USER PARAMETER SETTING
To adju t the u er parameter of the device, proceed a
follow :
1. Pre and hold for more than 20 econd the
key " ";
the di play will how the "PARAMETER" icon and the fir t
u er parameter " CO2t ".
2. Repeatedly pre the key " " to cyclically croll through
the u er parameter :
"
CO2T
" alarm thre hold
"
T_LO
"
lower limit thre hold
"
T_UP
"
upper limit thre hold
"
dEFt
"
DEFAULT DATA Management
3. Pre the "
▲
" or "
▼
" key to modify the parameter
elected; the "SET" icon will fla h
4. Pre the "
▲
" or "
▼
" key again to change the value;
each modification i tored automatically
.
5. To et the u er parameter pre the key " ".again
6. To exit the elected u er parameter modification mode,
pre the key " ".
7. To exit programming of the u er parameter , pre the key
" " again or wait 30 econd without pre ing any key.
PARAMETER 1: CO2t
Setting thi parameter enable definition of the value of
CO
2
beyond which the device enter the alarm pha e and activating
the OUT1 output.
ATTENTION
The adju tment range i linked to the value et in the
T-LO and T-UP u er parameter .
PARAMETER 2: T_LO
Thi parameter et the value of the lower bound for the alarm
thre hold adju tment, which can be et in the u er parameter
"CO
2
t".
PARAMETER 3: T_UP
Thi parameter et the value of the upper bound for the alarm
thre hold adju tment, which can be et in the u er parameter
"CO
2
t".
Data Regulation range Default
CO
2
t T_LO .. T_UP 900ppm
Data Regulation range Default
T_LO 500 .. 2000 ppm 900ppm
PARAMETER 4: dEFt
U ing thi parameter, by electing the "dFon" data, it i
po ible to re tore, in the device, the default value et in the
factory.
Conver ely, by etting "no" the tored data i maintained.
Note: re etting the DEFAULT data, new heating of the en or
i activated.
TECHNICAL SPECIFICATIONS
Power: 85-264V~ 47-440Hz
Ab orption: 2.0 VA max.
Screen re olution 1ppm.
Hy tere i (HYS): 75ppm - non-modifiable
Timeout parameter : 20 ec. Approximately from la t
pre ing
Sen or type NDIR
Detection range: 0 .. 2000 ppm
Preci ion: ±30ppm ±3% of reading
Rated current: 5(1)A 250V~ SPDT (Voltage-free)
Backlight Off
: 20 ec.
Approximately from la t pre ing
Action type: 1
Overvoltage category: II
Pollution degree 2
Tracking Index (PTI): 175
Cla of protection again t
electric hock : II
Impul e voltage rated: 2500V
Number of manual cycle : 50000
Number of automatic cycle : 100000
Software cla : A
EMC te ting voltage: 230V~ 50Hz
EMC te ting current: 34mA
Exclu ion di tance tolerance
Short circuit fault mode ±0.15mm
Temperature
ball pre ure te t: 75°C
Degree of protection: IP30
Operating temp: 0°C. 40°C.
Storage temp: - 10°C. + 50°C.
Humidity limit : 20%. 80% RH
non-conden ing
Dimen ion : 132 x 87 x 23.6 (LxAxP)
Container: Material: ABS V0 elf-extingui hing.
Colour: Signal white (RAL 9003)
Mounting: Wall or on rece ed box 503.
WARRANTY
In the view of a con tant development of their product , the
manufacturer re erve the right for changing technical data
and feature without prior notice. The con umer i guaranteed
again t any lack of conformity according to the European
Directive 1999/44/EC a well a to the manufacturer’
document about the warranty policy. The full text of warranty
i available on reque t from the eller.
Data Regulation range Default
T_UP 500 .. 2000 ppm 1200ppm
Data Regulation range Default
dEFt NO / dFon NO
Via del commercio, 9/11
I-36065 Ca oni di Mu olente (VI)
Tel.: +39.0424.567842 - Fax.: +39.0424.567849
http://www. eitron.it - e-mail: info@ eitron.it
RD ADA1
CARBON DIOXIDE CONTROLLER (CO
2
)
- Information, on the LCD di play, of the level of CO
2
mea ured by the internal en or
- Equipped with a voltage-free contact output
- Te t function to en ure correct operation of the controller
- Option to change the alarm thre hold

RDADA10001SE 029094 220917 ENGLISH
INSTALLATION
WARNING
- For correct mea urement of carbon dioxide (CO
2
) in the
room, it i advi able to in tall the device approximately
1.5 m from the floor and away from ource of heat
and draught .
- The controller mu t be wired to the electric main
through a witch capable of di connecting all pole in
compliance with the current afety tandard and with
a contact eparation of at lea t 3 mm in all pole .
- In tallation and electrical wiring of thi controller
mu t be made by qualified technician and in
compliance with the current tandard .
- Before wiring the controller be ure to turn the main
power off.
In tallation of the device i intended for in tallation in flu h-
mounted (or wall) tandard junction boxe with two or three
module or directly on the wall u ing the plug upplied.
To in tall the device proceed a follow :
Relea e the plate attached to the controller ba e by
pu hing it to the left. Thi relea e the teeth hown in
Fig. 1.
2
1
Fig. 1
1
DESCRIPTION OF CONTROLS
A Start the TEST function of the controller.
B Dual function key:
- In normal operation, if enabled, witch the controller on
or off.
- In "u er parameter etting" exit programming.
C Acce the u er parameter li t.
D Dual function key:
- In normal operation, the alarm thre hold et i di played.
- In "u er parameter etting" change the parameter
elected (increa ing the value).
E Dual function key:
- In normal operation the alarm thre hold et i di played
- In "u er parameter etting" change the elected
parameter (decrea ing the value).
DISPLAY VIEW
The ymbol that can be hown on the di play are de cribed in
the following table:
B
C
D
E
The figure hown i the value of CO
2
detected in the environment.
It indicate that a u er parameter i being
di played.
Selected u er parameter modification mode
ha been entered.
The output i enabled.
The Te t function ha been tarted.
The controller ha identified a fault
condition.
The controller ha detected a data torage
fault.
LEVEL
SET
P R METER
OUT 1
TEST
F ULT
2
Fig. 2
Pu h the pla tic tab in the lower lot u ing a
crewdriver, lightly lifting the cover (Fig. 2).
3
Fig. 3
Turn the cover, while pre ing it lightly, until it i
extracted (Fig. 3).
6
Fig. 6
- Connect the controller ba e to the wall plate (pa
the wire through the rectangular opening ). Align
the ba e hole with the pecial wall plate teeth,
then pre the ba e to the left until the plate’
pla tic teeth click (Fig. 6).
- Fix the controller ba e to the wall with the upplied
crew.
Fig. 8
8
ON/OFF BUTTON ' ' ENABLE.
A
B
A
B
Enable turn on and turn off with button ' '.
Di able turn on and turn off with button ' '.
Jumper et-up:
5
Fix the plate to the wall, u ing the two crew eat
with centre di tance of 60 mm or 85 mm (u e the
upplied wall plug and/or crew ). Pa the wire
through the rectangular opening (Fig. 5).
83mm
60mm
Fig. 5 Fig. 9
1
3
1
2
Perform the following operation to clo e back the
controller:
- Po ition the two teeth on the upper part of the cover
in the pecial notche .
- Turn the cover and pu h the pla tic tab inwardly on
the lower part of the ba e ( ee the arrow in Fig. 9).
Pre it o that the pla tic fixing tab in ide the
pecial hole click .
6
4
Fig. 4
Identify the correct po itioning of the device (Fig. 4).
YES
7
Make the electrical connection by pa ing the wire
through the rectangular opening of the wall plate
(Fig. 6) according to the connection diagram of Fig. 7.
----: Reinforced in ulation
Fig. 7
85-264V~
47-440Hz
Other Seitron Controllers manuals
Popular Controllers manuals by other brands

Mazak
Mazak MAZATROL M32 Service engineer's manual

Federal Signal Corporation
Federal Signal Corporation ultravoice UV Description, Specifications, Installation, Operation, and Service Manual

Emerson
Emerson Fisher 749B instruction manual

Novus
Novus N321 operating manual

Remote Control Systems
Remote Control Systems ALPHA-3-CO quick start guide

B&C
B&C AVC1 quick start guide