Page 16
MANUAL/AUTO switches is in an open-circuit condition, the s
stem will ente
the manual mode;
when all o
them are in a short-circuit condition, the s
stem will ente
the auto mode.
It can be seen that the s
stem will
ive priorit
to the auto mode when multiple LOCAL
MANUAL/AUTO switches are connected in parallel o
to the manual mode when the said
switches are connected in series. Fo
bette
practical application, the serial connection mode is
recommended.
Note: Afte
detectin
a compound fire alarm in the auto mode, the s
stem will automaticall
drive the electroma
netic valves, start the fire extin
uishin
devices; and afte
detectin
a
compound fire alarm in the manual mode, the s
stem will not drive the electroma
netic valves.
5. Terminal 21 on the maste
control board: It is fo
the mutin
control o
both the horn/strobe and
the alarm bell
fo
the AGND short/open circuit switch
.
1
Connection mode 1 should be selected fo
it. When connection mode A without an open circuit fault
detection function is selected, the
umpe
JP18 on the maste
control board should be set to the ON
position as shown in Table 3.1.2 and Fi
.4.1, and the built-in termination resistors in the control
board should be used; and when connection mode B with an open circuit fault detection function is
selected, the
umpe
JP18 on the maste
control board should be set to the OFF position, the built-in
termination resistors in the control board should not be used and a 10KΩtermination resisto
should
be arran
ed at the end o
the circuit shown in connection mode B.
2
A short circuit o
the switch su
ests a mute si
nal input and mutin
o
both the horn/strobe and the
alarm bell. At this time, the switch is off, the mutin
is cancelled and the external mutin
cannot be
cancelled throu
h the HORN/STROBE START/STOP button and the ALARM BELL START/STOP
button on the displa
panel. In case o
an open circuit o
the switch, the mutin
can be cancelled
throu
h the HORN/STROBE START/STOP button and the ALARM BELL START/STOP button on
the displa
panel.
6. Terminal 22 on the maste
control board: Itisfo
the reset si
nal input
fo
the AGND short/open
circuit switch
.
1
Connection mode 1 should be selected fo
it. When connection mode A without an open circuit fault
detection function is selected, the
umpe
JP14 on the maste
control board should be set to the ON
position as shown in Table 3.1.2 and Fi
.4.1, and the built-in termination resistors in the control
board should be used; when connection mode B with an open circuit fault detection function is
selected, the
umpe
JP14 on the maste
control board should be set to the OFF position, the built-in
termination resistors in the control board should not be used, and a 10K Ωtermination resisto
should be arran
ed at the end o
the circuit shown in connection mode B.
2
A short circuit o
the switch su
ests a reset status o
the s
stem, and an open circuit o
the switch
means that the s
stem will ente
the monitorin
status.
7. Terminal 23 on the maste
control board: Itisfo
the accession o
the local pressure feedback
si
nal
fo
the AGND short/open circuit switch
.
1
Connection mode 1 should be selected fo
it. When connection mode A without an open circuit fault
detection function is selected, the
umpe
JP15 on the maste
control board should be set to the ON
position as shown in Table 3.1.2 and Fi
.4.1, and the built-in termination resistors in the control
board should be used; when connection mode B with an open circuit fault detection function is
selected, the
umpe
JP15 on the maste
control board should be set to the OFF position, the built-in
termination resistors in the control board should not be used, and a 10K Ωtermination resisto
should be arran
ed at the end o
the circuit shown in connection mode B.
2
An open circuit o
the switch su
ests a normal status and a short circuit o
the switch su
ests a
pressure feedback si
nal input.
3
When there is a pressure feedback si
nal input, the RELEASE indicato
will have a drive output no
matte
whethe
the electroma
netic valves have a drive output o
not.
8. Terminal 24 on the maste
control board: Itisfo
the accession o
the a
ent drop alarm si
nal
fo
the AGND short/open circuit switch
.
1
Connection mode 1 should be selected fo
it. When connection mode A without an open circuit fault
detection function is selected, the
umpe
JP12 on the maste
control board should be set to the ON
position as shown in Table 3.1.2 and Fi
.4.1, and the built-in termination resistors in the control
board should be used; when connection mode B with an open circuit fault detection function is
selected, the
umpe
JP12 on the maste
control board should be set to the OFF position, the built-in
termination resistors in the control board should not be used, and a 10K Ωtermination resisto
should be arran
ed at the end o
the circuit shown in connection mode B.
2
A short circuit o
the switch su
ests an ai
c
linde
a
ent drop alarm si
nal input and an open
circuit o
the switch su
ests a normal wei
ht o
the ai
c
linder.
In case of agent drop input, the electromagnetic valves will make no output regardless of whether there
is a fire alarm.
9. Terminals 25 and 26 on the maste
control board: The
are fo
the accession o
the detecto
circuits.
1
Terminals 25 and 26 are connected with detecto
circuit 2 and detecto
circuit 1 respectivel
.The
accessed detectors are common on-of
heat detectors o
smoke detectors. Generall
speakin
,the
two circuits are connected with a heat detecto
and a smoke detecto
respectivel
.