Fire-Lite Alarms MS-9200UD User manual

Fire Alarm Control Panel
MS-9200UD/MS-9200UDE
PN: 51906:A ECN 02-398
IMPORTANT! The SLC Manual Document #51309 must be referenced in addition to this
manual when installing or servicing the Fire Alarm Control Panel.
Document #51906
12/10/02 Revision: A

LimWarLg.p65 01/10/2000
An automatic fire alarm system–typically made up of smoke
detectors, heat detectors, manual pull stations, audible warn-
ing devices, and a fire alarm control with remote notification
capability–can provide early warning of a developing fire.
Such a system, however, does not assure protection against
property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detec-
tors be located throughout a protected premise following the
recommendations of the current edition of the National Fire
Protection Association Standard 72 (NFPA 72),
manufacturer's recommendations, State and local codes, and
the recommendations contained in the Guide for Proper Use
of System Smoke Detectors, which is made available at no
charge to all installing dealers. A study by the Federal Emer-
gency Management Agency (an agency of the United States
government) indicated that smoke detectors may not go off in
as many as 35% of all fires. While fire alarm systems are de-
signed to provide early warning against fire, they do not guar-
antee warning or protection against fire. A fire alarm system
may not provide timely or adequate warning, or simply may not
function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors. Smoke detectors
also may not sense a fire on another level or floor of a build-
ing. A second-floor detector, for example, may not sense a
first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire
may not reach the sensing chambers of smoke detectors be-
cause:
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not reach
the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air
outlets.
•Smoke particles may be drawn into air returns before
reaching the detector.
The amount of "smoke" present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm at
various levels of smoke density. If such density levels are not
created by a developing fire at the location of detectors, the
detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing
limitations. Detectors that have photoelectronic sensing
chambers tend to detect smoldering fires better than flaming
fires, which have little visible smoke. Detectors that have ion-
izing-type sensing chambers tend to detect fast-flaming fires
better than smoldering fires. Because fires develop in differ-
ent ways and are often unpredictable in their growth, neither
type of detector is necessarily best and a given type of detec-
tor may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and violent
explosions (caused by escaping gas, improper storage of
flammable materials, etc.).
Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a prede-
termined rate or reaches a predetermined level. Rate-of-rise
heat detectors may be subject to reduced sensitivity over time.
For this reason, the rate-of-rise feature of each detector
should be tested at least once per year by a qualified fire pro-
tection specialist.
Heat detectors are designed to protect
property, not life.
IMPORTANT!
Smoke detectors must be installed in the
same room as the control panel and in rooms used by the sys-
tem for the connection of alarm transmission wiring, communi-
cations, signaling, and/or power.
If detectors are not so lo-
cated, a developing fire may damage the alarm system, crip-
pling its ability to report a fire.
Audible warning devices such as bells may not alert people
if these devices are located on the other side of closed or
partly open doors or are located on another floor of a building.
Any warning device may fail to alert people with a disability or
those who have recently consumed drugs, alcohol or medica-
tion. Please note that:
•Strobes can, under certain circumstances, cause seizures
in people with conditions such as epilepsy.
•Studies have shown that certain people, even when they
hear a fire alarm signal, do not respond or comprehend the
meaning of the signal. It is the property owner's responsibil-
ity to conduct fire drills and other training exercise to make
people aware of fire alarm signals and instruct them on the
proper reaction to alarm signals.
•In rare instances, the sounding of a warning device can
cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical
power. If AC power fails, the system will operate from standby
batteries only for a specified time and only if the batteries
have been properly maintained and replaced regularly.
Equipment used in the system may not be technically com-
patible with the control. It is essential to use only equipment
listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a
premise to a central monitoring station may be out of service
or temporarily disabled. For added protection against tele-
phone line failure, backup radio transmission systems are rec-
ommended.
The most common cause of fire alarm malfunction is inade-
quate maintenance. To keep the entire fire alarm system in
excellent working order, ongoing maintenance is required per
the manufacturer's recommendations, and UL and NFPA stan-
dards. At a minimum, the requirements of Chapter 7 of NFPA
72 shall be followed. Environments with large amounts of
dust, dirt or high air velocity require more frequent mainte-
nance. A maintenance agreement should be arranged
through the local manufacturer's representative. Maintenance
should be scheduled monthly or as required by National and/
or local fire codes and should be performed by authorized pro-
fessional fire alarm installers only. Adequate written records
of all inspections should be kept.
While a fire alarm system may lower insurance
rates, it is not a substitute for fire insurance!
Fire Alarm System Limitations

LimWarLg.p65 01/10/2000
WARNING -
Several different sources of power can be con-
nected to the fire alarm control panel.
Disconnect all sources
of power before servicing. Control unit and associated equip-
ment may be damaged by removing and/or inserting cards,
modules, or interconnecting cables while the unit is energized.
Do not attempt to install, service, or operate this unit until this
manual is read and understood.
CAUTION -
System Reacceptance Test after Software
Changes.
To ensure proper system operation, this product
must be tested in accordance with NFPA 72 Chapter 7 after
any programming operation or change in site-specific soft-
ware. Reacceptance testing is required after any change, ad-
dition or deletion of system components, or after any modifica-
tion, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software func-
tions known to be affected by a change must be 100% tested.
In addition, to ensure that other operations are not inadvert-
ently affected, at least 10% of initiating devices that are not
directly affected by the change, up to a maximum of 50 de-
vices, must also be tested and proper system operation veri-
fied.
This system meets NFPA requirements for operation at
0-49°C/32-120°F and at a relative humidity of 85% RH (non-
condensing) at 30°C/86°F. However, the useful life of the
system's standby batteries and the electronic components
may be adversely affected by extreme temperature ranges
and humidity. Therefore, it is recommended that this system
and all peripherals be installed in an environment with a nomi-
nal room temperature of 15-27°C/60-80°F.
Verify that wire sizes are adequate for all initiating and
indicating device loops. Most devices cannot tolerate more
than a 10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to light-
ning-induced transients. Although no system is completely
immune from lightning transients and interferences, proper
grounding will reduce susceptibility.
Overhead or outside
aerial wiring is not recommended, due to an increased sus-
ceptibility to nearby lightning strikes.
Consult with the Techni-
cal Services Department if any problems are anticipated or
encountered.
Disconnect AC power and batteries prior to removing or in-
serting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure. When possible, make
all cable entries from the sides or rear. Before making modifi-
cations, verify that they will not interfere with battery, trans-
former, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in reduced
terminal contact pressure and difficulty with screw terminal
removal.
Though designed to last many years, system components
can fail at any time. This system contains static-sensitive
components. Always ground yourself with a proper wrist strap
before handling any circuits so that static charges are re-
moved from the body. Use static-suppressive packaging
to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and
programming manuals. These instructions must be followed
to avoid damage to the control panel and associated
equipment. FACP operation and reliability depend upon
proper installation by authorized personnel.
Adherence to the following will aid in problem-free
installation with long-term reliability:
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual, may
cause interference to radio communications. It has
been tested and found to comply with the limits for class
A computing device pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when operated in a
commercial environment. Operation of this equipment in
a residential area is likely to cause interference, in which
case the user will be required to correct the interference
at his own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A
limits for radiation noise emissions from digital
apparatus set out in the Radio Interference Regulations
of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits
radioelectriques depassant les limites applicables aux
appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par le
ministere des Communications du Canada.
FCC Warning
Installation Precautions

4MS-9200UD PN 51906:A 12/10/02
Notes

MS-9200UD P/N: 51906:A 12/10/02 5
SECTION 1: Product Description ........................................................................................................................12
1.1: Features and Options...................................................................................................................................12
1.2: Specifications ..............................................................................................................................................14
1.2.1: Current Availability...........................................................................................................................15
1.3: Controls and Indicators ...............................................................................................................................16
1.4: Circuits ........................................................................................................................................................17
1.5: Digital Alarm Communicator/Transmitter..................................................................................................17
1.6: Components.................................................................................................................................................18
1.6.1: Intelligent Addressable Detectors: Newer Series..............................................................................18
1.6.2: Intelligent Addressable Modules: Newer Series ...............................................................................19
1.6.3: 300 Series Intelligent Addressable Devices......................................................................................20
1.6.4: Addressable Device Accessories.......................................................................................................20
1.7: Optional Modules........................................................................................................................................21
1.8: Accessories..................................................................................................................................................21
1.8.1: PK-Plus Programming Utility...........................................................................................................21
1.8.2: Dress Panel........................................................................................................................................21
1.8.3: Battery Box .......................................................................................................................................22
1.8.4: Battery Charger .................................................................................................................................22
1.8.4.1 CHG-75 Battery Charger ........................................................................................................22
1.8.4.2 CHG-120F Battery Charger ....................................................................................................22
1.8.5: Annunciators .....................................................................................................................................23
1.9: Getting Started.............................................................................................................................................24
1.10: Telephone Requirements and Warnings ....................................................................................................25
1.10.1: Telephone Circuitry.........................................................................................................................25
1.10.2: Digital Communicator.....................................................................................................................25
1.10.3: Telephone Company Rights and Warnings .....................................................................................26
SECTION 2: Installation .......................................................................................................................................27
2.1: Mounting Backbox......................................................................................................................................27
2.2: Mounting Transformer ................................................................................................................................28
2.3: Power...........................................................................................................................................................31
2.3.1: AC Power and Earth Ground Connection.........................................................................................31
2.3.2: Battery Power....................................................................................................................................31
2.3.3: DC Power Output Connection ..........................................................................................................31
2.4: Relays ..........................................................................................................................................................32
2.5: Notification Appliance Circuits ..................................................................................................................32
2.5.1: Configuring NACs ............................................................................................................................33
2.5.2: Style Y (Class B) NAC Wiring .........................................................................................................33
2.5.3: Style Z (Class A) NAC Wiring ........................................................................................................34
2.6: Remote Synchronization Output .................................................................................................................34
2.7: UL Power-limited Wiring Requirements ....................................................................................................35
2.8: Digital Communicator.................................................................................................................................36
2.9: Optional Module Installation ......................................................................................................................37
2.9.1: 4XTMF Transmitter Module Installation..........................................................................................38
2.9.2: Printer/PC..........................................................................................................................................40
2.9.3: Digital Communicator and Annunciators .........................................................................................41
2.9.3.1 ACM-8RF Relay Control Module ..........................................................................................41
2.9.3.2 BRKT-9600 Universal Bracket Installation ............................................................................41
2.9.3.3 ACM and AFM Series Annunciators ......................................................................................43
SECTION 3: Programming ...................................................................................................................................44
3.1: Programming Data Entry ............................................................................................................................44
3.2: User Programming ......................................................................................................................................45
3.3: Initial Power-up...........................................................................................................................................46
Table of Contents

Table of Contents
6MS-9200UD P/N: 51906:A 12/10/02
3.4: Programming Screens Description ..............................................................................................................46
3.5: Programming and Passwords ......................................................................................................................46
3.6: Master Programming Level.........................................................................................................................48
3.6.1: Autoprogram .....................................................................................................................................49
3.6.2: Point Program....................................................................................................................................50
3.6.2.1 Detector Programming ............................................................................................................50
3.6.2.1.1 Add Detector ........................................................................................................................50
3.6.2.1.2 Delete Detector .....................................................................................................................51
3.6.2.1.3 Edit Detector ........................................................................................................................51
3.6.2.2 Module Programming .............................................................................................................60
3.6.2.2.1 Add Module .........................................................................................................................60
3.6.2.2.2 Delete Module ......................................................................................................................61
3.6.2.2.3 Edit Module Screen for Monitor Module .............................................................................61
3.6.2.2.4 Edit Module Screen for Control Modules ............................................................................70
3.6.3: Zone Setup.........................................................................................................................................77
3.6.3.1 Enable ......................................................................................................................................77
3.6.3.2 Disable .....................................................................................................................................78
3.6.3.3 Zone 97, 98 and 99 ..................................................................................................................78
3.6.3.4 Zones Installed ........................................................................................................................79
3.6.3.5 Zones Enabled .........................................................................................................................79
3.6.3.6 Zones Disabled ........................................................................................................................79
3.6.3.7 Zone Type ...............................................................................................................................80
3.6.3.8 Zones Available ......................................................................................................................81
3.6.4: Loop Setup ........................................................................................................................................81
3.6.4.1 Style .........................................................................................................................................81
3.6.4.2 Loop Protocol ..........................................................................................................................81
3.6.5: System Setup .....................................................................................................................................82
3.6.5.1 Trouble Reminder ...................................................................................................................83
3.6.5.2 Banner .....................................................................................................................................83
3.6.5.3 Time-Date ...............................................................................................................................84
3.6.5.3.1 Time .....................................................................................................................................84
3.6.5.3.2 Date ......................................................................................................................................85
3.6.5.3.3 Clock Format ........................................................................................................................85
3.6.5.3.4 Daylight Savings Time .........................................................................................................85
3.6.5.4 Timers .....................................................................................................................................86
3.6.5.4.1 PAS (Positive Alarm Sequence) Delay ................................................................................86
3.6.5.4.2 Pre-signal Delay ...................................................................................................................87
3.6.5.4.3 Waterflow Delay ..................................................................................................................87
3.6.5.4.4 AC Loss Delay .....................................................................................................................88
3.6.5.5 NAC (Notification Appliance Circuit) ....................................................................................88
3.6.5.5.1 Enabled .................................................................................................................................89
3.6.5.5.2 Type ......................................................................................................................................90
3.6.5.5.3 Silenceable ...........................................................................................................................90
3.6.5.5.4 Auto Silence .........................................................................................................................91
3.6.5.5.5 Coding (only for NACs not programmed as Sync Strobe Type) .........................................91
3.6.5.5.6 Zone ......................................................................................................................................92
3.6.5.5.7 Silence Inhibited ...................................................................................................................92
3.6.5.5.8 Sync Type .............................................................................................................................92
3.6.5.6 Relays ......................................................................................................................................93
3.6.5.7 Canadian Option ......................................................................................................................94
3.6.5.8 Waterflow Silenceable ............................................................................................................94
3.6.6: Verify Loop .......................................................................................................................................94
3.6.7: History...............................................................................................................................................95
3.6.7.1 View Events ............................................................................................................................95
3.6.7.2 Erase History ...........................................................................................................................95
3.6.8: Walktest .............................................................................................................................................96

MS-9200UD P/N: 51906:A 12/10/02 7
Table of Contents
3.6.9: Option Modules................................................................................................................................97
3.6.9.1 Annunciators/UDACT ............................................................................................................97
3.6.9.2 Onboard DACT .......................................................................................................................98
3.6.9.2.1 Onboard DACT Enable ........................................................................................................98
3.6.9.2.2 Primary Phone ......................................................................................................................99
3.6.9.2.3 Secondary Phone ..................................................................................................................99
3.6.9.2.4 Service Terminal ..................................................................................................................100
3.6.9.2.5 Central Station ......................................................................................................................102
3.6.9.2.6 Trouble Call Limit (Dialer Runaway Prevention) ...............................................................103
3.6.9.2.7 Manual Dial Mode ...............................................................................................................115
3.6.9.3 Printer/PC ................................................................................................................................116
3.6.10: Password Change ............................................................................................................................117
3.6.11: Clear Program .................................................................................................................................118
3.6.12: Program Check................................................................................................................................119
3.7: Maintenance Programming Level ...............................................................................................................121
3.7.1: Disable Point .....................................................................................................................................122
3.7.2: History...............................................................................................................................................123
3.7.3: Program Check..................................................................................................................................124
3.7.4: Walktest.............................................................................................................................................125
3.7.5: System...............................................................................................................................................125
3.7.6: Zone Setup ........................................................................................................................................127
SECTION 4: Operating Instructions ....................................................................................................................129
4.1: Panel Control Buttons .................................................................................................................................129
4.1.1: Acknowledge/Step ............................................................................................................................129
4.1.2: Alarm Silence....................................................................................................................................129
4.1.3: Drill/Hold 2 Sec ................................................................................................................................129
4.1.4: Reset..................................................................................................................................................129
4.2: LED Indicators ............................................................................................................................................130
4.3: Normal Operation........................................................................................................................................131
4.4: Trouble Operation .......................................................................................................................................131
4.5: Alarm Operation..........................................................................................................................................133
4.6: Supervisory Operation.................................................................................................................................134
4.7: Process Monitor Operation..........................................................................................................................135
4.8: Hazard/Tornado Condition Operation .........................................................................................................135
4.9: Medical Alert Condition Operation.............................................................................................................135
4.10: NAC Operation .........................................................................................................................................135
4.11: Programmed Zone Operation ....................................................................................................................136
4.12: Disable/Enable Operation .........................................................................................................................136
4.13: Waterflow Circuits Operation ...................................................................................................................136
4.14: Detector Functions ....................................................................................................................................136
4.15: Time Functions: Real-Time Clock ............................................................................................................136
4.16: Synchronized NAC Operation ..................................................................................................................137
4.17: Coded Operation .......................................................................................................................................137
4.18: Presignal ....................................................................................................................................................137
4.19: Positive Alarm Sequence ..........................................................................................................................138
4.20: Special System Timers ..............................................................................................................................139
4.20.1: Silence Inhibit Timer.......................................................................................................................139
4.20.2: Autosilence Timer ...........................................................................................................................139
4.20.3: Trouble Reminder ...........................................................................................................................139
4.20.4: Waterflow Retard Timer..................................................................................................................139
4.20.5: Alarm Verification (None or One Minute)......................................................................................140
4.21: Walktest .....................................................................................................................................................140
4.22: Read Status................................................................................................................................................141
4.22.1: System Point ...................................................................................................................................142

Table of Contents
8MS-9200UD P/N: 51906:A 12/10/02
4.22.2: Zones ...............................................................................................................................................143
4.22.3: Power...............................................................................................................................................144
4.22.4: Trouble Reminder............................................................................................................................145
4.22.5: Timers..............................................................................................................................................145
4.22.6: NAC ................................................................................................................................................146
4.22.7: Relays ..............................................................................................................................................146
4.22.8: Program Check................................................................................................................................147
4.22.9: History.............................................................................................................................................147
4.22.10: Annunciators .................................................................................................................................148
4.22.11: Phone Line.....................................................................................................................................148
4.22.12: Central Station...............................................................................................................................149
4.22.13: Service Terminal............................................................................................................................150
4.22.14: Printer/PC ......................................................................................................................................150
4.22.15: Print ...............................................................................................................................................151
4.22.16: Time-Date......................................................................................................................................153
SECTION 5: Central Station Communications ...................................................................................................154
5.1: Transmittal Priorities ...................................................................................................................................157
SECTION 6: Remote Site Upload/Download .......................................................................................................159
6.1: Downloading Program.................................................................................................................................159
6.1.1: Security Features ...............................................................................................................................160
6.2: Downloading Initiated at Control Panel ......................................................................................................162
6.3: Downloading Initiated at a Service Terminal ..............................................................................................162
6.4: Uploading Initiated at a Service Terminal...................................................................................................163
SECTION 7: Power Supply Calculations .............................................................................................................164
7.1: Overview .....................................................................................................................................................164
7.2: Calculating the AC Branch Circuit..............................................................................................................164
7.3: Calculating the System Current Draw.........................................................................................................165
7.3.1: Overview ...........................................................................................................................................165
7.3.2: How to Use Table 7.3 on page 166 to Calculate System Current Draw ...........................................165
7.4: Calculating the Battery Size ........................................................................................................................167
7.4.1: NFPA Battery Requirements .............................................................................................................167
7.4.2: Selecting and Locating Batteries.......................................................................................................167
APPENDIX A: Software Zones ............................................................................................................................168
A.1: Correlations ...............................................................................................................................................168
APPENDIX B: Default Programming .................................................................................................................174
APPENDIX C: NFPA Standard-Specific Requirements ...................................................................................175
APPENDIX D: Wire Requirements .....................................................................................................................179

MS-9200UD PN 51906:A 12/10/02 9
It is imperative that the installer understand the requirements of the Authority Having Jurisdiction
(AHJ) and be familiar with the standards set forth by the following regulatory agencies:
• Underwriters Laboratories Standards
• NFPA 72 National Fire Alarm Code
NFPA Standards
NFPA 72 National Fire Alarm Code
NFPA 70 National Electrical Code
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers–Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1610 Central Station Burglar Alarm Units
UL 1638 Visual Signaling Appliances
UL 1971 Signaling Devices for Hearing Impaired
Other:
EIA-232E Serial Interface Standard
EIA-485 Serial Interface Standard
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction (LAHJ)
Fire•Lite Documents:
Fire•LiteDevice Compatibility Document #15384
SLC Wiring Manual Document #51309
AFM-16ATF & AFM-32AF Document #15970
AFM-16AF Annunciator Document #15210
ACS Series Annunciators Document #51480
CHG-120F Battery Charger Document #50888
CHG-75 Battery Charger Document #51315
LDM Series Lamp Driver Modules Document #50055
LCD-80F Remote Fire Annunciator Document #51338
ACM-8RF Relay Control Module Document #50362
Before proceeding, the installer should be familiar with the following documents.

10 MS-9200UD PN 51906:A 12/10/02
PS2 Keyboard Interface DACT Phone Line Jacks
(Non Power Limited)
DB9F
Resettable Power - 24 VDC filtered, power-limited
(0.500 amps maximum) to smoke detectors (IDC).
Supervision required.
Nonresettable or Resettable Power
Jumper selectable by JP4, 24 VDC filtered,
power-limited (0.500 amps maximum)
Supervision required. Nonresettable
Power suitable for powering annunciators,
Resettable Power suitable for powering
smoke detectors..
NAC #1 & #2
Style Z (Class A)
2.5 amps max. per circuit.
JP6 configured for Class A
using NACKEY card.
(Power Limited)
NAC #1 NAC #2
NAC #1, #2, #3 & #4, Style Y (Class B) (Power Limited)
2.5 amps max. per circuit. JP6 configured
for Class B using NACKEY card.
(See Style Z illustrated near right edge of board).
Contact Ratings:
2.0 amps @ 30 VDC (resistive)
0.5 amps @ 30 VAC (resistive)
Contacts shown below in normal
condition (AC power with no alarm,
trouble or supervisory activity).
A Fail Safe Trouble
relay switches to the
NO position during
trouble conditions and
under loss of all power.
For EDP-listed equipment or
personal computer with FACP
Upload/Download Utility.
50 foot maximum within same room.
Refer to the SLC Wiring
Manual for detailed
information on wiring
addressable devices
for Style 4, 6 and 7.
ACS (EIA-485)
to ACS Annunc.
(power-limited,
supervised)
ELRs 4.7K, ½W
DC Power Outputs (24 VDC)
Supervise with a power supervision relay A77-716B
Battery
Basic System Connections
Notification Appliance Circuits
Notification Appliance Circuits
2 Programmable Relays &
1 Fixed Trouble Relay
EIA-232
to printer or
personal computer
SLC Loop
OR
OR
B
+B
+
B
-
B
-
A
+A
+
A
-
A
-
NO NC C NC NO CNO NC C
Alarm* Trouble
Supervisory*
5 4 3 2 1
9 8 7 6
Green
Black
White
Red
T
XR
C
V
TB8 (option to DB-25)
TB3
TB8
TB8
TB4
5 4 3 2 1
25 24 23 22 21 20 19 18 17 16 15 14
9 8 7 613 12 11 10
CAUTION! HIGH VOLTAGE
NC NO C
+
+
+
+
+
+
120 VAC, 60 HZ, 3.0 amps
220/240 VAC, 50 Hz, 1.5 amps
24 VDC, nonpower-limited
18 Amp Hour maximum
T
XR
C
V
D
T
R
G
N
D
G
N
D
+ 24V -
NON-RST
POWER
+ 24V -
RST
POWER
REMOTE PWR
SUPPLY SYNC NAC 1 CLASS A
NAC 1 & 3 CLASS B
NAC 2 CLASS A
NAC 2 & 4 CLASS B
RELAY 3 RELAY 1
HOT NEUT EARTH
- +
BATTERY
LCD DISPLAY
REMOVE TO
DISABLE GND. FLT.
CUT TO
MONITOR
4XTMF
KISSOFF
PRI. ACTIVE SEC. ACTIVE
SEC. PHONE LINE
PRI. PHONE LINE
4XTMF
MINI DIN
KEYBOARD CONN.
KEYPAD
I/F
RELAY 2
TRANSFORMER 1
TRANSFORMER 2
+ -
B+ A+ A- B- B+ A+ A- B-
1B+ 3B+ 3B- 1B- 2B+ 4B+ 4B- 2B-
NO NC C NO NC C NO NC C B+ A+ B- A- A B
ACS
SHIELDSLCSLC
SLC
SLC
OUT+ I N+ OUT- IN -
TB5 TB6 TB8 TB9 TB10
JP2
JP3
SW1
JP7
JP5
JP6
1
2
3
TB11
J10
J3
J13 J12
J7
J5
J1 J4
J9
J6
J11
CAUTION!
HIGH VOLTAGE
(* )Factory default relay programming
shield
B
+B
-
BA
+A
-
A
TERM
(EIA-485)
to LCD-80F
I
N
+
O
U
T
+
I
N
-
O
U
T
-
+
-
Remove this jumper
to disable the FACP
battery charger when
using external charger.
Transformer 2 Connector
Transformer 1 Connector
Flash Memory Load Enable Switch.
UP is normal position for switch.
DOWN position allows loading of
factory software upgrades.
Cut this jumper to enable
Supervisory relay when
4XTMF module is installed
Cut this jumper to supervise
the 4XTMF module when
installed (see J5 & J6)
To disable ground fault detection,
remove jumper/shunt from JP7
Configure NACs for Claa A or
Class B wiring using NACKEY
card. Factory default is Class B.
NAC #1 NAC #3
NAC
Number
-
++
+
+
B
+B
-
11
B
+B
-
33
NAC #4 NAC #2
B
+B
-
++
++
++
B
+B
-
22
44
TB3 TB4 TB7
2
1
2
1
4
3
+ +
- -
TB1 TB2
JP4
+
-
+
+
D
T
R
Remote Synchronization Output
24 VDC filtered, supervised and power-limited.
0.040 amps maximum, follows NAC1 control circuit.
Requires 4.7kohm End-of-Line resistor.

068'31$
Peripheral Devices and Their Documents:
1
Ack/ Step Silence Reset
Drill
Hold2 se c.
-
+
-
+
JP1
JP3
SW1
JP4
TB 3 TB 4
TB 2
ENABLE
AC DELAY
16 HR
DELAY
TENS
ONES
CUT F OR
240VAC
GND FLT
DISABLE
AM-1 ENABLE
ADDR ESS
ON OFF
AM-1
JP5
JP2
F1 F2
J4
J1 J2 J3
F3
TB 1
HOT
OUT
+
BAT
+ OU T
-
BAT
-
EARTHNEUT
15 15
A- B- A+ B+ NC NO C
0
439 2
6
1
578
12
13
15
14
10
11
0
439 26
1
578
12
13
15
14
10
11
LCD-80F
Doc. #51338
AFM-16AF
Doc. #15210
LDM-32F
Doc. #50055
AFM-16ATF &
AFM-32AF
Doc. #15970
ACM-16ATF &
ACM-32ATF
Doc. # 51480
ACM-8RF
Doc. #50362
Addressable Devices and SLC Wiring
Doc. #51309
CHG-120F Charger
Doc. #50888
TERM (EIA-485)
Annunciators
ACS (EIA-485)
Annunciators
SLC Loop
Battery Connector
92udperi.cdr
CHG-75 Charger
Doc. # 51315

3URGXFW'HVFULSWLRQ )HDWXUHVDQG2SWLRQV
068'31$
SECTION 1 Product Description
The Fire•Lite MS-9200UD is a combination FACP (Fire Alarm Control Panel) and
DACT (Digital Alarm Communicator/Transmitter) all on one circuit board. This
compact, cost effective, intelligent addressable control panel has an extensive list of
powerful features. The combination of Fire•Lite’s newer series devices and legacy 300
Series devices, along with the MS-9200UD FACP, offer the latest in fire protection
technology. The power supply and all electronics are contained on a single circuit
board housed in a metal cabinet, providing a complete fire control system for most
applications. Optional modules, which plug into the main circuit board, are available
for special functions. Available accessories include LED, graphic and LCD
annunciators, reverse polarity/city box transmitter, local and remote upload/download
software and remote power expansion.
The integral DACT transmits system status (alarms, troubles, AC loss, etc.) to a Central
Station via the public switched telephone network. It also allows remote and local
programming of the control panel using the PK-Plus Upload/Download utility. In
addition, the control panel may be programmed or interrogated off-site via the public
switched telephone network. Any personal computer with Windows95 or greater,
and compatible modem with a speed of 14.4 kbps or faster and Fire•Lite Upload/
Download software kit PK-Plus, may serve as a Service Terminal. This allows
download of the entire program or upload of the entire program, history file, walktest
data, current status and system voltages.
Note: Unless otherwise specified, the term MS-9200UD is used in this manual to refer
to both the MS-9200UD and the MS-9200UDE FACPs (Fire Alarm Control Panels).
Inventory
When the MS-9200UD shipment is received, check to make certain that all parts have
been included in the shipment. The MS-9200UD shipment should consist of one of
each of the following:
✓main circuit board with display
✓backbox with door
✓plastic bag containing screws, cables, key, etc.
✓manual
1.1 Features and Options
• Built-in DACT (Digital Alarm Communicator/Transmitter)
• Single addressable SLC loop which meets NFPA Style 4, 6 and 7 requirements
• 198 addressable device capacity (99 detectors and 99 control/relay/monitor
modules)
• 99 software zones
• Onboard NACs (Notification Appliance Circuits) which can be configured as
four Style Y (Class B) or two Style Z (Class A) circuits
• 3.0 amps total power for NACs and 24 VDC auxiliary power outputs expandable
to 6.0 amps
• 3.6 amps total system power (includes battery charger) expandable to 6.6 amps
• Two programmable relay outputs and one fixed trouble relay
• Synchronization output for remote power supply applications
• Built-in Programmer
• Telephone Line Active LEDs
• Communication Confirmation (Kissoff) LED
• Touchtone/Rotary dialing
• Programmable Make/Break Ratio

)HDWXUHVDQG2SWLRQV 3URGXFW'HVFULSWLRQ
068'31$
• EIA-232 Printer/PC interface (variable baud rate)
• 80-character LCD display (backlit)
• Real-time clock/calendar with daylight savings time control
• History file with 1,000 event capacity
• Advanced fire technology features:
✓Automatic drift compensation
✓Maintenance alert
✓Detector sensitivity test capability (NFPA 72 compliant)
✓Automatic device type-code verification
✓Point trouble identification
• Waterflow selection per module point
• Alarm verification selection per detector point
• Walktest, silent or audible
• PAS (Positive Alarm Sequence) and Pre-signal per point (NFPA 72 compliant)
• Silence inhibit timer option per NAC
• Autosilence timer option per NAC
• Continuous, March Time, Temporal or California code for main circuit board
NACs with two-stage capability
• Selectable strobe synchronization per NAC
• Remote Acknowledge, Alarm Silence, Reset and Drill via addressable modules,
AFM annunciators or LCD-80F Remote annunciator
• Auto-program (learn mode) reduces installation time. Reports two devices set to
the same address
• Password and key-protected nonvolatile memory
• User programmable password
• Fully programmable from local keypad or optional keyboard
• Upload/Download (local or remote) of program and data via integral DACT
• SLC operates up to 10,000 ft. (3,000 m) with twisted, shielded wire or 3,000 ft
(900 m) with untwisted, unshielded wire
• Compatible with Fire•Lite’s newer series devices
✓CP350, CP355: addressable Ionization Smoke Detector
✓SD350(T), SD355(T), AD355: addressable Photo Smoke Detector (T= with
Thermal Sensor)
✓H350(R), H355(R), H355HT: Fast Response Heat Detector (R=Rate-of-Rise
option, HT=High Temperature 190RF)
✓D350P(R): addressable Photo Duct Detector (R=alarm relay option)
✓B501BH & B501BHT Sounder Base
✓B224RB Relay Base
✓B224BI Isolator Base
✓MMF-300: Monitor Module
✓MMF-300-10: Monitor Module (10 Input Class B or 5 Input Class A)
✓MDF-300: Dual Monitor Module (uses two consecutive SLC addresses)
✓MMF-301: Miniature Monitor Module
✓MMF-302: 2-wire Detector Module
✓MMF-302-6: 2-wire Detector Module (6 Input Class B or 3 Input Class A)
✓CMF-300: Control Module
✓CMF-300-6: Control Module (6 Output Class B or 3 Output Class A)
✓CRF-300: Relay Module
✓CRF-300-6: Relay Module (6 Form-C relays)
✓BG-12LX: Manual Pull Station
✓I300: Isolator Module

Product Description Specifications
14 MS-9200UD PN 51906:A 12/10/02
• Compatible with legacy Fire•Lite 300 Series devices:
✓CP300: addressable Ionization Smoke Detector
✓SD300(T): addressable Photoelectric Smoke Detector (T= Thermal Sensor)
✓C304: Control Module
✓M300: Monitor Module
✓M301: Miniature Monitor Module
✓M302: 2-wire Detector Module
✓BG-10LX: Manual Pull Station
• Optional 4XTMF module (conventional reverse polarity/city box transmitter)
• Annunciators:
✓ACM Series-LED Zone Annunciators
✓LDM Graphic Annunciator Series
✓LCD-80F Liquid Crystal Display point annunciator
✓ACM-8RF Relay Module
1.2 Specifications
Refer to Illustration on page 10 for terminal locations and connections.
AC Power - TB11
MS-9200UD: 120 VAC, 60 Hz, 3.0 amps
MS-9200UDE: 240 VAC, 50 Hz, 1.5 amps
Wire size: minimum 14 AWG (2.00 mm2) with 600 V insulation
Battery (Lead Acid Only) - J9
Maximum Charging Circuit: Normal Flat Charge - 27.6 VDC @ 0.80 amp
Maximum Battery Charger Capacity: 18 Amp Hour (MS-9200UD cabinet holds
maximum of two 18 Amp Hour batteries. For greater than 25 Amp Hour up to 120
Amp Hour batteries, use the CHG-75 or CHG-120F Battery Charger and BB-55F
Battery Box.
Note: Jumper JP5, on the FACP main circuit board, must be removed to disable the
FACP battery charger when using an external battery charger.
Communication Loop - TB10
24 VDC nominal, 27.6 VDC maximum
Maximum length is 10,000 ft. (3,000 m) total twisted, shielded pair length or 3,000 ft.
(900 m) untwisted, unshielded pair length
Maximum loop current is 400 mA (short circuit) or 100 mA (normal)
Maximum loop resistance is 40 ohms
Supervised and power-limited circuit requires ferrite bead per FCC requirement
Refer to SLC Loop manual for wiring information
Notification Appliance Circuits - TB3 & TB4
Each Terminal Block provides connections for two Style Y (Class B) or one Style Z
(Class A) for a total of Four Style Y (Class B) or two Style Z (Class A) NACs
Style is configured using NACKEY card plugged into JP6 on main board
Power-limited circuitry
Maximum voltage drop in wiring: 2.0 VDC
Nominal operating voltage: 24 VDC
Current-limit: fuseless, electronic, power-limited circuitry
Maximum signaling current per circuit: 2.5 amps (see Figure 1.1 on page 15)
End-of-Line Resistor: 4.7 kΩ, ½ watt (P/N 71252 UL listed) for Style Y (Class B) NAC
Refer to Fire•Lite Device Compatibility Document for listed compatible devices
Two Programmable Relays and One Fixed Trouble Relay - TB5, TB6 & TB7
Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive)
Form-C relays
Refer to Figure 2.6 on page 32 for information on power-limited relay circuit wiring

Specifications Product Description
MS-9200UD PN 51906:A 12/10/02 15
Nonresettable Power (24 VDC Nominal) - TB1, Terminals 1 (+) & 2 (-)
Jumper selectable (JP4) for conversion to resettable power output
Maximum ripple voltage: 10mVRMS
Total DC current available from each output is up to 0.5 amps (see Figure 1.1)
Power-limited circuit requires ferrite bead per FCC requirements
Four-Wire Resettable Smoke Detector Power (24 VDC nominal) - TB3,
Terminals 3 (+) & 4 (-)
Maximum ripple voltage: 10 mVRMS
Up to 0.5 amps is available for powering 4-wire smoke detectors (see Figure 1.1)
Power-limited circuit requires ferrite bead per FCC requirements
Refer to Fire•Lite Device Compatibility Document for listed compatible devices
Remote Sync Output - TB2
Remote power supply synchronization output
24 VDC nominal
Maximum current is 40 mA
End-of-Line Resistor: 4.7KΩ
Output linked to NAC 1 control
Supervised and power-limited circuit requires ferrite bead per FCC requirements
EIA-485 (TERM) or EIA-232 (ACS) - TB8
EIA-485 Terminal Mode annunciator connections: Terminal 1 (Out +), 2 (In +),
3 (Out -), 4 (In -)
EIA-232 PC/Printer applications connections: Terminal 1 (Transmit), 2 (Receive),
3 (Ground)
EIA-485 (ACS) - TB9
ACS annunciator connector, Terminal 1 (+) and Terminal 2 (-), requires ferrite bead
1.2.1 Current Availability
The following figure illustrates the maximum current that is possible for each panel
circuit and the total current available from the FACP with optional second transformer.
0.5 amps max
per circuit
0.5 amps max
per circuit
2.5 amps max
per circuit
2.5 amps max
per circuit
2.5 amps max
per circuit
2.5 amps max
per circuit
Resettable Power
for 4-Wire Smoke Detectors
Nonresettable or
Resettable Power
NAC #1
NAC #3
NAC #2
NAC #4
Standby
1 amp max
per panel
Alarm
6 amps max
per panel
1
2
3
4
1
2
3
4
1
2
3
4
TB3
TB4
TB1
Figure 1.1 Current Availability
powerdist9200ud.cdr
Refer to the battery calculations section for additional information.
Note: If NACs are
configured as two Style Z
(Class A) circuits, each
circuit can handle 2.5
amps maximum.
6.0 amps with optional second
XRM-24(E) transformer.
3.0 amps max. with only
standard transformer installed.

3URGXFW'HVFULSWLRQ &RQWUROVDQG,QGLFDWRUV
068'31$
1.3 Controls and Indicators
LCD Display
The FACP uses an 80-character
(4 lines X 20 characters) high
viewing angle LCD display. The
display includes a long life LED
backlight that remains illuminated. If
AC power is lost and the system is
not in alarm, the LED backlight will turn off to conserve batteries.
LED Indicators
LED indicators are provided to annunciate the following conditions:
• AC Power (green)
• Fire Alarm (red)
• Supervisory (yellow)
• Trouble (yellow)
• Maintenance/presignal (yellow)
• Alarm Silenced signals (yellow)
• Disabled (yellow)
• Battery fault (yellow)
• Ground fault (yellow)
Key Panel
Mounted on the main circuit board, the key panel includes a window for the LCD
display and LED indicators as listed above. The key panel, which is visible with the
cabinet door closed, has 25 keys, including a 16 key alpha-numeric pad similar to a
telephone keypad.
Function keys:
• Acknowledge/Step
• Alarm Silence
• Drill
• Reset (lamp test)
Service/program keys:
• Keys labeled 1 to 9
• * key
• # key
• 0 (recall) key
•1stEventkey
• Clear key
• Escape key
• Mode key
• Four cursor keys (up, down, left and right)
• Enter key
Local Piezo Sounder
A piezo sounder provides separate and distinct pulse rates for alarm, trouble and
supervisory conditions.
FIRE-LITE ALARMS INC
SYSTEM ALL NORMAL
10:00A 012102
1
4
*
2
5
0
3
6
#
1
st
EVENT
ABC DEF
GHI JKL MNO
PRS TUV WXY
QZ
-/.
CLR
78 9
ESC
ENTER
RECALL
ACK/STEP
ALARM
SILENCE
DRILL
HOLD 2 SEC
RESET
MODE
MAINTENANCE
ALARM
SILENCED
DISABLED
BATTERY
GROUND
SUPERVISORY
TROUBLE
AC POWER
FIRE ALARM
Figure 1.2 Membrane/Display Panel
9600kypd.cdr

&LUFXLWV 3URGXFW'HVFULSWLRQ
068'31$
1.4 Circuits
SLC Communication Loop
One SLC loop is provided standard on the FACP main circuit board. The SLC loop,
configurable for NFPA Style 4, 6 or 7, provides communication to addressable
detectors, monitor (initiating device) and control (output device) modules. Refer to the
SLC Wiring manual for information on wiring devices.
Output Circuits
The following output circuits are available on the FACP:
• 24 VDC Resettable (smoke detector power) output - 0.5 amps maximum
• 24 VDC Nonresettable or Resettable power output - 0.5 amps maximum
• 24 VDC Battery Charger (up to 18 AH batteries)
NAC (Notification Appliance Circuits)
NACs configurable for four Style Y (Class B) or two Style Z (Class A) using NACKEY
card in JP6, are provided with various programmable features.
Relays
One fixed and two fully programmable Form-C dry contact relays are provided. The
fixed fail-safe relay monitors system trouble and the two programmable relays are
factory default programmed for system alarm and system supervisory. Contacts are
rated 2.0 amps @ 30 VDC (resistive) and 0.5 amps @ 30 VAC (resistive). The
programmable relays can be programmed for the following operations:
• fire alarm
• trouble
• supervisory
• supervisory auto-resettable
• DACT communication failure
• process monitor
• process monitor auto-resettable
• hazard alert
• medical alert
•ACloss
1.5 Digital Alarm Communicator/Transmitter
Two modular phone jacks allow easy connection to telephone lines. Modular jacks are
labeled PH1 for Primary Phone Line and PH2 for Secondary Phone Line. Two
telephone line active red LEDs are provided as well as a green Kissoff LED. The
integral digital communicator provides the following functions:
• Line Seizure: takes control of the phone lines disconnecting any premises phones
• Off/On Hook: performs on and off-hook status to the phone lines
• Listen for dial tone: 440 Hz tone typical in most networks
• Dialing the Central Station(s) number: default is Touch-Tone, programmable to
rotary
• For tone burst or touchtone type formats: discern proper Ack and Kissoff tone(s).
The frequency and time duration of the tone(s) varies with the transmission
format. The control panel will adjust accordingly.
• Communicate in the following formats:
✓12 Tone Burst types: 20 pps
(3+1, 4+1, 4+2, 3+1 Exp., 4+1 Exp., 4+2 Exp.)
✓3 Touchtone Types
4+1 Ademco Express
4+2 Ademco Express
Ademco Contact ID
Reference
Manual

Product Description Components
18 MS-9200UD PN 51906:A 12/10/02
1.6 Components
Main Circuit Board
The main circuit board contains the system’s CPU, power supply, other primary
components and wiring interface connectors. The 4XTMF option module plugs in and
is mounted to the main circuit board. The circuit board is delivered in the MS-9200UD
kit and must be mounted to the backbox (refer to circuit board illustration on page 10).
Cabinet
The MS-9200UD cabinet is red with a navy blue front overlay.
The backbox provides space for two batteries (up to 18 Amp
Hour). Ample knockouts are provided for system wiring. Also
available is an optional dress panel, which mounts to the inside
of the cabinet (required by ULC for Canadian installations).
The dress panel must be installed to meet FM requirements.
Transformer Assembly
One 100VA transformer is provided standard
with the panel (3.6 amps maximum). An
optional 100 VA transformer XRM-24
(XRM-24E for the MS-9200UDE) is available
to provide maximum system and accessory
power (6.6 amp total).
Batteries
The MS-9200UD cabinet provides space for
two batteries (up to 18 Amp Hour). Batteries
larger than 18 Amp Hour require an external
charger such as the CHG-75 or CHG-120F
and a UL listed battery box such as the BB-
55F. Batteries must be ordered separately.
1.6.1 Intelligent Addressable Detectors: Newer Series
Intelligent, addressable detectors provide information to the control panel on an SLC
Signaling Line Circuit (refer to the SLC Wiring Manual for detailed information on
device installation, wiring and operation). This allows the control panel to continually
process the information to determine the status (alarm, trouble, maintenance or normal)
of each detector. Each detector responds to an SLC address that is set in the detector
head using built-in rotary decimal switches. Note that a blinking LED on an intelligent
detector indicates communication between the detector and the control panel. Refer to
the Fire•Lite Device Compatibility Document for a list of approved detectors.
Smoke Detectors (Photoelectric)
The SD350 is an intelligent, addressable low profile photoelectric smoke detector
which provides smoke sensing technology. The SD350T includes a 135ofixed thermal
sensor.
Smoke Detector (Ionization)
The CP350 is an intelligent, addressable low profile ionization smoke detector which
measures the level of combustion products in its chamber using the ‘ionization
principle.’
See Page
ms9200UD.cdr
Standard
XRM-24(E)
Optional
XRM-24(E)
9200xfor.cdr
-
-
+
+
Battery Cable P/N 75287
9200batt.cdr

&RPSRQHQWV 3URGXFW'HVFULSWLRQ
068'31$
Smoke Detector (Duct)
The D350P is an intelligent, addressable photoelectric duct smoke detector. The
D350RP includes an alarm relay.
Heat Detectors
The H350 is an intelligent heat detector with a thermistor sensing circuit for fast
response, designed to provide open area protection with 50 foot (15 m) spacing
capability. The H350R incorporates a thermal Rate-of-Rise circuit of 15RF (9.4RC).
Detector Bases
The B501BH is a standard sounder base and the B501BHT is a temporal tone sounder
base for intelligent, addressable smoke detectors.
The B224RB is a relay base with one Form-C relay for intelligent, addressable smoke
detectors. It may be used to control auxiliary functions.
The B224BI is an isolator base for intelligent, addressable smoke detectors. It
functions similar to the I300 isolator module which allows loops to operate under fault
conditions and automatically restore when the fault is removed.
1.6.2 Intelligent Addressable Modules: Newer Series
The newer series of Control Modules and Monitor Modules provide an interface
between the control panel and conventional notification and initiating devices. Each
module can be set to respond to an address with built-in rotary switches. A blinking
LED on a monitor module indicates communication between the module and the
control panel. These devices can also be used when installed on older systems. Refer
to the Fire•Lite Device Compatibility Document for a list of approved notification and
initiating devices.
Monitor Modules
The MMF-300, MMF-300-10, MDF-300, MMF-302 and MMF-302-6 are addressable
monitor modules for monitoring conventional initiating devices. The MMF-300 is used
for normally open contact alarm initiating devices, such as manual pull stations, four-
wire smoke detectors, heat detectors, waterflow, security contacts and supervisory
devices. The MMF-300-10 functions the same as the MMF-300 except it provides 10
Class B or 5 Class A inputs. The MDF-300 is a dual monitor module (Class B only)
which occupies two consecutive SLC addresses, with each module functionally the
same as the MMF-300. The MMF-302 is used primarily for two-wire smokes detectors
in addition to normally open contact devices. The MMF-302-6 functions the same as
the MMF-302 except it provides 6 Class B or 3 Class A inputs. The supervised IDCs
(Initiating Device Circuits) can be wired to the modules as NFPA Style B (Class B) or
Style D (Class A) circuits. The modules are supplied with a thermoplastic cover for
mounting to a 4-inch mounting box.
Monitor Module (miniature)
The addressable MMF-301 module is functionally similar to an MMF-300 but offered
in a smaller package for mounting directly in the electrical box of the monitored device.
Control Module
The CMF-300 and CMF-300-6 are an addressable Control Modules used to connect
NACs (Notification Appliance Circuits) to power and supervise compatible, UL-listed
notification appliances. The CMF-300 provides one Class B or Class A output while
the CMF-300-6 provides 6 Class B or 3 Class A outputs. The NACs can be wired to the
module as supervised NFPA Style Y (Class B) or Style Z (Class A) circuits. The
modules are supplied with a thermoplastic cover for mounting to a 4-inch square
mounting box.
Reference
Manual

3URGXFW'HVFULSWLRQ &RPSRQHQWV
068'31$
Relay Module
The CRF-300 and CRF-300-6 are a Control Relay Modules which are functionally
similar to the CMF-300 but used as Form-C relay modules. The CRF-300 provides one
Form-C relay while the CRF-300-6 provides six Form-C relays.
Isolator Module
The I300 loop isolator module is an automatic switch which opens the circuit voltage to
the SLC loop branch(es) whenever a wire-to-wire short circuit is detected on that loop.
The remainder of the communications loop leading up to the I300 will continue to
operate, unaffected by the short. The isolator module is bidirectional, meaning that it
can detect a fault condition between the input SLC terminals or output SLC terminals.
The I300 is required to meet NFPA Style 7 requirements.
Detector Annunciator
The RA400Z is a remote single LED annunciator that can be wired directly to an
addressable detector for annunciation of that detector’s alarm status.
Manual Pull Station
The BG-12LX is an addressable manual pull station featuring a key-lock reset. The
pull station responds to an address set by the installer using the built-in rotary decimal
switches on the pull station. The manual pull station includes the Fire•Lite key.
1.6.3 300 Series Intelligent Addressable Devices
Fire•Lite’s 300 Series Intelligent Addressable Devices are fully compatible with the
MS-9200UD FACP. The address of 300 Series devices cannot be set above 99.
Compatible devices include:
• SD300 Photoelectric Detector
• SD300T Photoelectric Detector with Thermal Sensor
• CP300 Ionization Detector
• M300 Monitor Module
• M301 Miniature Monitor Module
• M302 2-wire Monitor Module
• C304 Control/Relay Module
• BG-10LX Manual Pull Station
1.6.4 Addressable Device Accessories
End-of-Line Resistor Assembly Fire•Lite P/N R-47K
The 47 kΩEnd-of-Line Resistor assembly (P/N: R-47K) is used to supervise the
MMF-300, MDF-300, MMF-301 and CMF-300 module circuits. The 3.9 kΩEnd-of-
Line Resistor assembly is used to supervise the MMF-302 module circuit. The resistors
are included with each module.
Power Supervision Relay
The UL listed End-of-Line power supervision relay is used to supervise the power to 4-
wire smoke detectors and notification appliances.
N-ELR Mounting Plate
The N-ELR is a single End-of-Line resistor plate. An ELR, which is supplied with each
module and fire alarm control panel, is mounted to the ELR plate. Resistors mounted to
the N-ELR plate can be used for the supervision of a monitor and control module
circuit.
This manual suits for next models
1
Table of contents
Other Fire-Lite Alarms Control Panel manuals

Fire-Lite Alarms
Fire-Lite Alarms MRP-4424 User manual

Fire-Lite Alarms
Fire-Lite Alarms FIRE COMMAND 25 Supplement

Fire-Lite Alarms
Fire-Lite Alarms MS-5024UD User manual

Fire-Lite Alarms
Fire-Lite Alarms ES-200XC User manual

Fire-Lite Alarms
Fire-Lite Alarms MicroScan-2410B User manual

Fire-Lite Alarms
Fire-Lite Alarms MS-4012 User manual

Fire-Lite Alarms
Fire-Lite Alarms MS-4412B User manual

Fire-Lite Alarms
Fire-Lite Alarms MS-9600LS User manual

Fire-Lite Alarms
Fire-Lite Alarms MS-5210UD User manual

Fire-Lite Alarms
Fire-Lite Alarms MS-5UD Series User manual