INTRODUCTION The Model NRC Network Ring card from Siemens Industry,
Inc. is a card that networks multiple FireFinder-XLS systems
together in a Class X (Style 7) ring. The NRC can also be
configured for Class B (Style 4) operation in systems where
a ring is not required, as an alternative to the NIC-C card.
It provides communication between its host FireFinder-XLS
system and other FireFinder-XLS systems on an XNET network.
It replaces the NIC-C when a ring connection is needed.
The NRC can also be used to connect an NCCNT-G to the
XNET network. In this configuration, all events occurring on
the FireFinder-XLS network are displayed at the NCCNT-G.
One NRC is required in each FireFinder-XLS system on the
network.This NRC must reside in the same enclosure as the
PMI/PMI-2.
The NRC supervises the network to ensure proper opera-
tion. Any faults that are detected by the NRC are reported to
the PMI/PMI-2 for annunciation. In addition, the NRC has
diagnostic LEDs that indicate which faults have been found.
The NRC performs ground fault detection on its outgoing
ring port.
Features The NRC isolates faults to the individual link in trouble. When
wired for Class X (Style 7), network ring communication
continues unaffected.
An RJ-12 monitor jack is included for connection of XNET
diagnostic tools. In addition, RJ-45 and USB jacks are
included for firmware download. These jacks are located on
the front bezel.
Network Ring Card
Installation Instructions
Model NRC
NRC
RESET
POWER
CARD FAIL
TROUBLE
MONITOR
PORT
ETHERNET
USB
Figure 1
NRC Network Ring Card
A6V10322639_b_en_--

Siemens Industry, Inc.
Building Technologies Division
2 A6V10322639_b_en_--
Figure 2
Installing the NRC
OPERATION The NRC continuously monitors the network for activity and reports any problems to
the PMI/PMI-2. In some cases, a reset at the PMI/PMI-2 is required to clear network
troubles.
Controls and Indicators The front panel of the NRC contains one reset switch, three
LEDs, one Monitor port, one USB port, and one Ethernet port as shown in
Figure 1.
A reset switch is located on the top of the front panel. Pushing the reset switch
reinitializes the NRC.
The LEDs follow the reset switch and their functions are defined as follows:
POWER (Green) Normally ON. When illuminated, indi-
cates that power for the NRC is applied
to the card.
CARD FAIL (Yellow) Normally OFF. When illuminated, indicates
that the card microprocessor has failed.
TROUBLE (Yellow) Normally OFF. When illuminated, indi-
cates trouble in the Network such as
wire faults or module failure. The Trouble
LED will illuminate under the following
conditions:
1. Wire faults (open or short) in either
Port 1 (In) or Port 2 (Out)—See Figure 5.
2. Ground fault on outgoing port (Port 2).
3. XNET communications problems
between the PMI/PMI-2 and the NRC.
PRE-INSTALLATION The NRC does not have a network address but it does need to be included in the
Zeus configuration.
INSTALLATION The NRC plugs perpendicularly into one slot in the CC-2 or CC-5 card-cage via two
96-pin DIN connectors (only 64-pins are used) and can occupy any slot in the card
cage. (Refer to Figure 2.)
Slide the NRC card into the card guides front bezel up (lettering on the
front panel is legible) until the card cage connectors contact the
motherboard receptacles.
Verify that the card edge connectors align properly with the
motherboard receptacles. There is only one correct way to plug in the
card. If it does not align, DO NOT FORCE the card.
Place thumbs on the front panel adjacent to the captive screws and
gently apply even pressure on the card until the connectors plug firmly
into the motherboard receptacles. Secure the NRC to the card cage with
the captive screws.

Siemens Industry, Inc.
Building Technologies Division
3 A6V10322639_b_en_--
FIRMWARE UPGRADES From time to time, modules used in XLS systems are upgraded to improve their
operation or to add to their capabilities with new features. Firmware in the NRC is
field upgradable. Refer to the Zeus Quickstart Manual, P/N 315-033875, and Zeus
Help for additional details.
Find NRC Software Version To check for the current version of NRC software in an installed NRC, go to the PMI/
PMI-2 and press the Menu button, select Report, press the More Info button and
select the PMI. Press the Configuration soft key and “Touch” Appl Rev for the
Application Version.The NRC software version will be shown with the PMI software
version. Refer to Figure 3 for an example of a display.
Figure 3
Typical PMI Display of NRC Software Version
Menu:Report:Configuration:Appl.Rev:View
PHY:MultiXNet, FireFinder, PMI-C@253
Application Rev Report
Cancel Print
10:53
Category text information
Address Entity Software Version 100%
/1:253 PMI-C 07.00.0034
/1:253^1 NRC 01.00.0008
GoTo

Siemens Industry, Inc.
Building Technologies Division
4 A6V10322639_b_en_--
WIRING Remove all system power before installation, first battery then AC. (To power up,
connect the AC first, then the battery.)
All field wiring to the NRC is connected to the terminal blocks of the CC-2 or CC-5
card cage slot in which it is installed.
To connect the field wiring:
1. Loosen the screw of the terminal by turning it counterclockwise.
2. Insert the wire into the side of the terminal block.
3. Tighten the screw of the terminal block by turning it clockwise.
The screw terminals can accommodate one 12 - 22 AWG.
12345678
910111213141516
17 18 19 20 21 22 23 24
DO NOT USE
ONE SLOT OF CC-5
FIRST NRC
12345678
910111213141516
17 18 19 20 21 22 23 24
DO NOT USE
DO NOT USE
ONE SLOT OF CC-5
12345678
910111213141516
17 18 19 20 21 22 23 24
DO NOT USE
ONE SLOT OF CC-5
LAST NRC
DO NOT USE
DO NOT USE DO NOT USE DO NOT USE
DO NOT USE
Figure 5
NRC Network Wiring Style 7
Figure 4
NRC Wiring
15
26
37
48
TOP HEADER OF
TERMINAL BLOCK
ON THE CC-5/CC-2
PORT 1
PORT 2
A1
B1
A2
B2
B2 A2 B1 A1
NOTES:
1. No EOLR required.
2. 22 AWG min., 12 AWG max.
3. 3300 feet max. per pair
between NRCs.
Shielded or Unshielded
twisted pair with a minimum
of 3 twists per ft.
Refer to Table 1 for NRC
cable specifications.
4. Terminate shields at one end
only.
5. Power limited to NFPA 70.
6. All wires supervised.
7. Ground fault detected at
8.5K ohms or less.
1ELBAT snoitacificepSelbaCCRN
.elbacehtnotnemeriuqermuminimehtswohswolebelbatehT
zHK001tanoitaunettAxamBd
01
zHM1tanoitaunettAxamBd03
:stnemeriuqeresehtteemsepytelbacgniwollofehT E5-TACA2297nedleB
GWA81LU0235nedleB

Siemens Industry, Inc.
Building Technologies Division
5 A6V10322639_b_en_--
WIRING OF NRCTO FIBER MODULES FN2006 AND FN2007
NRC Class B (Style 4) Wiring
12345678
910111213141516
17 18 19 20 21 22 23 24
DO NOT USE
DO NOT USE
DO NOT USE DO NOT USE
ONE SLOT OF CC-5
FIRST NRC
12345678
910111213141516
17 18 19 20 21 22 23 24
DO NOT USE
DO NOT USE
DO NOT USE
ONE SLOT OF CC-5
12345678
910111213141516
17 18 19 20 21 22 23 24
DO NOT USE
DO NOT USE
DO NOT USE
ONE SLOT OF CC-5
LAST NRC
NOTES:
1. No EOLR required.
2. 22 AWG min., 12 AWG max.
3. 3300 feet max. per pair
between NRCs.
Shielded or Unshielded
twisted pair with a minimum
of 3 twists per ft.
Refer to Table 1 for NRC
cable specifications.
4. Terminate shields at one end
only.
5. Power limited to NFPA 70.
6. All wires supervised.
7. Ground fault detected at
8.5K ohms or less.
Figure 6
NRC Class B (Style 4) Network Wiring
Power B connections to the fiber module and monitoring of its trouble contacts are
not required, as the fiber modules must be installed in the same enclosure as the
power supplies that provide them power.
NRC with NCC
See the NCC-WAN IOM manual, P/N 315-049679, for information on connecting a
NCC Network Command Station to the NRC network.
See the FN2006/FN2007 Installation Instructions, P/N A6V10315048, for wiring and
fiber connections. Installation of the fiber modules in the XLS system requires one
bracket, model COM-BRK, per fiber module.The bracket is installed as described in
the installation instructions, P/N A6V10406085.
Each bracket takes up the same space as a CC-2 card cage.
The module mounting flange of the bracket is intentionally angled. Do notDo not
Do notDo not
Do not try to
straighten the mounting flange.

Siemens Industry, Inc.
Building Technologies Division
6 A6V10322639_b_en_--
FOM = Fiber Optic Module, Model FN2006 (Single mode) or FN2007 (Multi-mode).
NC NC
NRC
In Node 1 NRC
In Node 2 NRC
In Node n
PORT 2 PORT 1 PORT 2 PORT 1 PORT 2 PORT 1
NRC
In Node 1 NRC
In Node 2 NRC
In Node n
PORT 2 PORT 1 PORT 2 PORT 1 PORT 2 PORT 1
Figure 7
Typical Class B (Style 4) Installation with wire only
Figure 8
Typical Class X (Style 7) Installation with wire only
NRC
In Node 1 NRC
In Node 2 NRC
In Node n
FOM:
FN2006/
FN2007
NC NC
FOM:
FN2006/
FN2007
OPTICAL
FIBER PAIR OPTICAL
FIBER PAIR
FOM:
FN2006/FN2007
PORT 2 PORT 1 PORT 2 PORT 1 PORT 2 PORT 1
WIRE
CONNECTION WIRE
CONNECTION WIRE
CONNECTION WIRE
CONNECTION
NRC
In Node 1 NRC
In Node 2 NRC
In Node n
FOM:
FN2006/FN2007
OPTICAL
FIBER PAIR OPTICAL
FIBER PAIR
FOM:
FN2006/FN2007
OPTICAL
FIBER PAIR
WIRE
CONNECTION
WIRE
CONNECTION
FOM:
FN2006/FN2007
PORT 2 PORT 1 PORT 2 PORT 1 PORT 2 PORT 1
WIRE
CONNECTION WIRE
CONNECTION WIRE
CONNECTION WIRE
CONNECTION
Figure 9
Typical Class B (Style 4) Installation with optical fiber only
Figure 10
Typical Class X (Style 7) Installation with optical fiber only
The XLS network can be wired using copper wire, single-mode fiber, multi-mode
fiber or a combination of the three. The block diagrams below show the possible
configurations.
WIRING CONFIGURATIONS

Siemens Industry, Inc.
Building Technologies Division
7 A6V10322639_b_en_--
NRC
In Node 1 NRC
In Node 2 NRC
In Node n
FOM:
FN2006/
FN2007
FOM:
FN2006/
FN2007
NC NC
OPTICAL
FIBER PAIR
WIRE
CONNECTION
PORT 2 PORT 1 PORT 2 PORT 1 PORT 2 PORT 1
WIRE
CONNECTION WIRE
CONNECTION
Figure 11
Typical Class B (Style 4) Installation with optical fiber and wire
NRC
In Node 1 NRC
In Node 2 NRC
In Node n
FOM:
FN2006/
FN2007
OPTICAL
FIBER PAIR
FOM:
FN2006/
FN2007
OPTICAL
FIBER PAIR
WIRE
CONNECTION
WIRE
CONNECTION
WIRE
CONNECTION
FOM:
FN2006/FN2007
WIRE
CONNECTION WIRE
CONNECTION
PORT 2 PORT 1 PORT 2 PORT 1 PORT 2 PORT 1
rewoPtupnI
tnerruCenalPkcaBV42Am041
tnerruCV42lanimreTwercS0
tnerruCenalPkcaBV2.6Am02
tnerruCybdnatSV42Am541
ELECTRICAL RATINGS
Figure 12
Typical Class X (Style 7) Installation with optical fiber and wire
FOM = Fiber Optic Module, Model FN2006
(Single mode) or FN2007 (Multi-mode)

Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ
Siemens Canada Limited
Building Technologies Division
2 Kenview Boulevard
Brampton, Ontario L6T 5E4 Canada
Document ID A6V10322639_b_en_--P/N A5Q00059298
This page has been left intentionally blank.
Table of contents
Other Siemens Network Card manuals

Siemens
Siemens S5-135U/155U User guide

Siemens
Siemens SIMATIC NET CP 1623 User manual

Siemens
Siemens SIMATIC NET Series User manual

Siemens
Siemens DTU3005-B User manual

Siemens
Siemens TIWAY I TI505 User manual

Siemens
Siemens SIMATIC NET CP 343-1 User manual

Siemens
Siemens AFI5100 User manual

Siemens
Siemens SIMATIC PCS 7 Reference manual