Are your rooms too warm/too cold?
+
–
Press + or – to increase or decrease the room
temperature setpoint in increments of 0.5 °C /
1 °F. Proceed as follows:
•Press +or –to adjust the setpoint
temporarily.
Press or to save the value or wait
for the program to exit automatically.
•To permanently modify the temperature
setpoints, use parameters P05 and P07.
To lock the setpoints, use parameters P06
and P08.
Does symbol appear on the display?
(Only with battery-powered version)
Symbol is displayed when the batteries are low.
Replace them with 2 new alkaline batteries type AAA.
Proceed as follows:
•Get 2 new alkaline batteries type AAA
•Remove the battery holder, then the batteries, insert
the new batteries and, within 1.5 minutes, replace the
battery holder
•Ensure the exhausted batteries are disposed of
correctly, in compliance with environmental
requirements
Do you want to lock the buttons?
Press and hold for at least 7 seconds to
activate a button lock. Repeat to unlock.
The unit operates normally when the buttons are
locked, but no changes are possible while the
buttons are locked.
Do you want to change parameters?
+
–
If you want to change control parameters,
proceed as follows:
•Press +and – simultaneously for 5 seconds
•Release them and parameter "P02" is
displayed on the bottom segment
•Press +or – to scroll to the parameter that
needs to be adjusted
•Press to select this parameter
•Press +or – to adjust the value
•Press to confirm the adjusted value
•Select and modify other parameters
•Press to exit the parameters without
saving or wait for the program to exit
automatically
Parameter list
Parameter
no. Description Setting range (default)
P02 Selection of °C
or °F 1 = °C (default)
2 = °F
P03 Standard
temperature
display
1 = room temperature
(default)
2 = setpoint
P04 Temperature
sensor
calibration
-3…3 °C
Step 0.5 °C
(-6…6 °F, step 1 °F)
Default: 0 °C
P05 Comfort
setpoint 5…35 °C, step 0.5 °C
(41…95 °F, step 1 °F)
Default: 20 °C, 68 °F
P06 Comfort
setpoint lock 0 = OFF (default)
1 = ON –> locked according
to setting in P05
P07 Economy
setpoint 5…35 °C, step 0.5 °C
(41…95 °F, step 1 °F)
Default: 16 °C, 61 °F
P08 Economy
setpoint lock 0 = OFF (default)
1 = ON –> locked according
to setting in P07
P09 Buzzer 0 = OFF
1 = ON (default)
P10 Show frost
protection icon 0 = OFF (default)
1 = ON
P21 Button
scanning rate
for the
capacitive
buttons
Note: a shorter
scanning rate
means shorter
battery life.
0.2 = 0.25 s
0.5 = 0.5 s
1.0 = 1.0 s (default)
1.5 = 1.5 s
P22 Reload factory
settings 0 = OFF (default)
1 = reload
P23 Software
version
information
No adjustment possible