Simphoenix DL100 Series User manual


Preface
Thanks for choosing the DL100 series universal low-power inverter
produced by Shenzhen Sunfar Electric Technologies Co., Ltd.
This Manual is the operating manual for DL100 series universal low-power
inverters. It provides all relevant instructions and precautions for installation,
wiring, functional parameters, daily care and maintenance, fault diagnosis and
troubleshooting of DL100 series inverters.
In order to use this series of inverters correctly, guarantee product's best
performance and ensure safety of users and equipment, be sure to read this
manual carefully before using DL100 series inverters. Improper use may cause
abnormity and malfunction of the inverter, reduce its service life and even
damage equipments and lead to personal injury and death etc.
This user manual is delivered with the device. Please keep it properly for
future overhaul and maintenance.Owing to constant improvement of products,
all data may be changed without further notice.
User Manual of DL100 Series Universal Low-Power Inverter
Version V1.0
Revision Date: Oct 2021

目 录
1 Product Introduction.........................................................................................11
1.1 Description of inverter model..........................................................................
1.2 Model of inveter series.....................................................................................
1.3 Product appearance and name of components...........................................
1.4 Product technical indicators and specifications............................................
2 Inverter Installation...............................................................................................
2.1 Environmental requirements ...........................................................................
2.2 Installation dimension of inverters..................................................................
3 Inverter Wiring........................................................................................................
3.1 Wiring precautions............................................................................................
3.2 Wiring of peripheral elements.........................................................................
3.3 Basic wiring.......................................................................................................
3.4 Wiring of main loop terminal............................................................................
3.5 Wiring of control loop terminal........................................................................
4 Operating Panel.....................................................................................................
4.1 Panel instructions.............................................................................................
4.2 Panel operating method...................................................................................
4.3 List of status monitoring parameters..............................................................
4.4 Simple operation of the inverter......................................................................
4.4.1 Initial setting...............................................................................................
4.4.2 Simple running...........................................................................................
5 Function Parameter Table....................................................................................
1
1
1
2
3
5
5
6
8
8
9
11
12
13
15
15
16
18
18
18
19
20

6 Detailed Description of functions......................................................................
6.1 Basic operating parameter group...................................................................
6.2 Basic control parameter groups......................................................................
6.3 Motor parameter group....................................................................................
6.4 Digital input and analog parameter group.....................................................
6.5 Digital output and swing frequency operation parameter group................
6.6 Multi-speed section and PLC operating parameter group..........................
6.7 Communication setting parameter group......................................................
6.8 PID parameter group........................................................................................
7 Fault Diagnosis And Countermeasures...........................................................
7.1 Protection function and countermeasures.....................................................
7.2 Fault record query............................................................................................
7.3 Fault reset..........................................................................................................
AppendixⅠ: MODBUS Protocol Specification..................................................
AppendixⅡ: Brake Resistor Selection................................................................
27
27
34
38
41
45
51
54
56
59
59
60
61
62
67

DL100 Series Universal Low-Power Inverter
Precautions Ⅰ
Precautions
DL100 series universal low-power inverters are applicable to general industrial
single-phase and three-phase AC asynchronous motors. If this inverter is used for
equipment which is failed and may cause personal injury (e.g. nuclear control system,
aviation system, safety equipment and instruments), please take care and consult with the
manufacturer; if it is used for dangerous equipment, that equipment should be provided
with safety protecting measures to prevent accident expansion in the case of inverter
failure. The inverter is produced under strict quality assurance system. However, in order
to protect your personal safety and equipment and property safety, before using this
inverter, please read this chapter carefully and conduct transportation, installation,
operation, commissioning and inspection according to relevant requirements.
1.Precautions of unpacking inspection
When unpacking, please confirm if
(1) There is any damage during transportation and any components are
damaged or dropped.
(2) The model and specifications stated on the inverter nameplate is
consistent with your order. If there is any omission or damage, please
contact your supplier promptly.
Nameplate of the inverter
On the left side of the inverter body, there is a nameplate marked with the
model and rated parameters of the inverter.
Label on the outer box
Shenzhen Simphoenix Electric Technology Co.,Ltd
DL100-2S0007
1PH 220V 50/60Hz
1.9KVA 5.0A
XXXXXXXXXX
TYPE
SOURCE
OUTPUT
SERIAL No.
MADE IN CHINA
变频器型号
额定输入电压相数,电压及频率
额定输出容量及电流
产品系列号
二维码,认证标识
Inverter model
Rated input voltage phase, voltage and frequency
Rated output capacity and current
Product serial number
QR code, certification mark
TYPE
SOURCE
NET WEIGHT
GROSS WEIGHT
VOLUME
SERIAL NO.
DL100-2S0007
1PH 220V 50/60Hz
235*155*200(mm)
*XXXXXXXXXXXXXXX*
M A DE I N C H IN A
S h e n z h e n S im ph o e n ix E lec t ri c T echn o lo gy C o.,Ltd
变频器型号
额定输入电压相数,电压及频率
净 重
产品系列号
二维码,认证标识
毛 重
包装箱尺寸
0.7 KG
0.9 KG
Inverter model
Rated input voltage phase, voltage and frequency
Net weight
Gross weight
Carton size
Product serial number
QR code, certification mark

DL100 Series Universal Low-Power Inverter
ⅡPrecautions
Weight and dimension
Model
Net weight
(KG)
Gross weight
(KG)
Outer box
dimension(mm)
DL100-2S0004
0.75
0.95
225×145×185
DL100-2S0007/DL100-2S0015
0.75
0.95
225×145×185
DL100-4T0007/DL100-4T0015
0.75
0.95
225×145×185
DL100-2S0022
1.2
1.5
250×165×200
DL100-4T0022/DL100-4T0040
1.2
1.5
250×165×200
DL100-4T0055/DL100-4T0075
1.9
2.3
285×185×210
We have strict quality assurance system for the products in terms of
manufacturing, packing and transportation. In case of any careless omission,
please contact us or local agent immediately. We will address the problem at
first time.
2.Safety precautions
In this manual, the wordings of “Danger” and “Caution” are defined as below.
2.1 Installation
1. The inverter shall not be installed on combustibles.
2. The frequency inverter shall not be installed at places with direct sunlight.
3. The frequency inverter of this series shall not be installed in the environment
of explosive gases, for fear of the danger of explosion.
4. No foreign matter is allowed to be dropped into the frequency inverter, for
fear of causing fires or injury.
5. During installation, the frequency inverter shall be installed at the place able
to bear its weight; otherwise, it may fall down or damage properties.
Danger: Serious damage to the equipment or personal injuries may
be caused if operating without following requirements.
Caution: Moderate injuries or minor injuries of personnel and material
loss may be caused if operating without following requirements.
The inverter shall not be dismantled or modified without authorization.

DL100 Series Universal Low-Power Inverter
Precautions Ⅲ
2.2 Wiring
1. Wire diameter shall be selected according to applicable electric code, and
wiring shall be done by qualified technicians.
2. Wiring shall not be started unless the power supply of the inverter is
completely disconnected.
3. The grounding terminal of the inverter must be reliably grounded; otherwise,
there can be a danger of electric shock.
4. Before wiring, make sure the power supply has been disconnected for over 10minutes;
otherwise, there may be a danger of electric shock.
5. The electronic elements in the inverter is quite sensitive to static electricity,
hence no foreign articles shall be placed into the inverter or contact the main
board.
2.3 Maintenance
3.Precautions of use
In this manual, the wordings of “Tip” and “Attention” are defined as below:
1. The inverter shall be installed in the place with good ventilation.
2. The motor’s temperature can be a little higher than that of industrial frequency
power during operation of the inverter, which is abnormal.
3. With long-term operation at low speed, the operation life of motor can be
affected due to the poorer heat dissipation effect. In this case,special frequency
converter shall be selected or the motor’s load shall be decreased.
4. When the altitude is over 1000m, the inverter shall be derated. Increase of
altitude for every 1500 m shall be ground for derating by 10%.
Tip: To give some useful information.
Attention: To indicate any precautions during operation.
Wiring, inspection and other maintenance work shall not be
done until the power supply is disconnected for 10 minutes.
No alternating current power supply is allowed to be connected
onto the U, V, and W of the inverter.

DL100 Series Universal Low-Power Inverter
ⅣPrecautions
5. If the operating environment is beyond the allowed conditions of the inverter,
please consult the manufacturer.
4.Scrapping precautions
Following attentions shall be paid when the inverter and its components are
abandoned:
Explosion of the electrolytic capacitor: electrolytic capacitor in the frequency
converter may cause explosion while burning.
Waste gas from plastic burning: harmful and toxic gas may be produced during
combustion of plastic and rubber products of the converter.
Disposal: please dispose of inverters as industrial wastes.
The inverter’s output terminal shall not be connected to any
filter capacitor or other RC absorption equipment.

DL100 Series Universal Low-Power Inverter
Product Introdution 1
Chapter1 Product Introduction
1.1 Description of inverter model
DL100-2 S 0007 (B)
4 380V
2 220V 0004
0007
0015
0022
0040
0055
0075
B
0.4
0.75
1.5
2.2
4.0
5.5
7.5
T Three Phase
S Single Phase
Product senes number
Universal
low-power
inverter
Voltage grade
Power supply phase
Ddrived product model
With braking
unit and485
communication
Adaptive motor power
(KW)
DL100
1.2 Model of inverter series
Inverter model
Rated capacity
(KVA)
Rated output current
(A)
Adaptive motor power
(KW)
DL100-2S0004(B)
1.1
3.0
0.4
DL100-2S0007(B)
1.9
5.0
0.75
DL100-2S0015(B)
2.9
7.5
1.5
DL100-2S0022(B)
3.8
10.0
2.2
DL100-4T0007(B)
1.6
2.5
0.75
DL100-4T0015(B)
3.0
4.5
1.5
DL100-4T0022(B)
3.6
5.5
2.2
DL100-4T0040(B)
6.3
9.5
4.0
DL100-4T0055(B)
8.6
13
5.5
DL100-4T0075(B)
11.2
17
7.5

DL100 Series Universal Low-Power Inverter
2Product Introdution
1.3 Product appearance and name of components
Figure 1-2 Appearance and Component
Name of Category II Inverters
Applicable models:
DL100-2S0007(B)~DL100-2S0015(B)
DL100-4T0007(B)~DL100-4T0015(B)
Figure 1-1 Appearance and Part Name of Category I Inverters
Applicable models: DL100-2S0004(B)
Figure 1-3 Appearance and Component
Name of Category III Inverters
Applicable models:
DL100-2S0022(B)
DL100-4T0022(B)~DL100-4T0075(B)
Operating panel
Housing
Radiator
Control terminal
Main circuit terminal
Operating panel
Housing
Control terminal
Main circuit terminal
Fan assembly
Operating panel
Housing
Control terminal
Main circuit terminal
Fan assembly

DL100 Series Universal Low-Power Inverter
Product Introdution 3
1.4 Product technical indicators and specifications
I n p u t
Rated voltage,
frequency
Three phase (4T# series)
380V50/60Hz
Single phase (2S# series)
220V50/60Hz
Allowed variation
range of voltage
380 ~ 415V±10%
220V±10%
O u t p u t
Voltage
0 ~ input voltage
0 ~ input voltage
Frequency
0.00~600Hz
Overload capacity
110%--long term; 150%--1 minute; 180%--2 second
Control mode
V/F
C o n t r o l C h a r a c t e r i s t i c s
Frequency
set
resolution
Analog
terminal
input
0.1% of the maximum output frequency
Digital
setting
0.01Hz
Frequency
precision
Analog
input
Within 0.1% of the maximum output frequency
Digital
input
Within 0.1% of the set output frequency
V/F curve
(Voltage frequency
characteristics )
Reference frequency can be set within 5~600Hz, and multi-node
V/F curve can be randomly set.
Torque increase
Manual setting: 0.0~20.0% of rated output.
Automatic current
limiting and voltage
limiting
Automatically detect motor’s stator current and voltage and
control it within allowable range according to special algorithm,
regardless of any running process like acceleration, deceleration
or static running.
Under voltage limiting
during running
Especially for users of low-grid voltage and frequently fluctuating
grid voltage. Even within the voltage range lower than allowable
value, the system can maintain longest running time according to
special algorithm and residual capacity distribution strategy.
Ty p i c a l f u n c t i o n s
Multispeed cont0rol
7-section programmable multispeed control and 5 kinds of
running modes available for selection
Optional built-in PID
controller
Internal integrated optimized PID controller, allowing for simple
closed-loop control.
RS485 communication
and linkage control
MODBUS protocol.
Frequency
setting
Analog
input
DC voltage 0-10V, and DC current 0-20mA (optional)
Digital
input
Operating panel setting, potentiometer setting, RS485 port setting,
UP/DW terminal control, and multiple combined setting with
analog input.

DL100 Series Universal Low-Power Inverter
4Product Introdution
Output
signal
Relay and
OC output
One channel OC output and One channel relay output (TA, TC),
with up to 16 kinds of optional meanings.
Analog
output
One channel 0-10V voltage signal, and upper and lower limit can
be set.
Automatic voltage
regulation running
Three kinds of voltage regulation modes including dynamic, static
and none are available for selection according to different
requirements, so as to achieve most stable running effect.
Setting of acceleration
and deceleration time
0.1~600.0Sec continues setting.
Running function
Setting of upper and lower limiting frequency, REV running
limiting, RS485 communication, and control of progress increase
and decrease of frequency, etc.
Display
Display of
operation
panel
Running
status
Output frequency, output current, output voltage, motor
revolution, set frequency, module temperature, analog input and
output and
so on.
Alarm
content
The nearest 4 times of fault records, five items of running
parameter records at the time of latest fault trip including, the
output frequency, output current, output voltage, DC voltage and
modular temperature.
Protection/alarm function
Over current, overvoltage, under voltage, overheat, short circuit,
internal memory fault, etc
Environment
Surrounding
temperature
-10ºC to +45ºC (no freezing)
Surrounding
humidity
90% below (no frosting)
Surrounding
environment
Indoor (Free of direct sunlight, corrosion, flammable gas, oil mist
and dusts)
Altitude
0~1000m, the load is derated by 10% for each kilometer increase.
Protecting
grade
IP20
Cooling
mode
Forced air cooling
(Model 2S0004 is natural air cooling without fan)
Installation mode
wall-mounted
(Model 2S0004 must be mounted vertically on the wall)
Vibration
<6m/s²

DL100 Series Universal Low-Power Inverter
Inverter Installation 5
Chapter2 Inverter Installation
2.1 Environmental requirements
This series of inverters are wall-mounted products and shall be vertically
installed to facilitate air circulation and heat dissipation. Following attentions
shall be paid for selecting installation environments.
1. The ambient temperature shall be within -10℃-45℃.
High-temperature and humid places shall be avoided, and the
inverter shall be better placed in a place with humidity lower
than 90% and without frosting.
2. Direct sunshine should be avoided.
3. The inverter should be away from flammable, explosive and
corrosive gas and liquid.
4. The environment should be free of dust, floating fibers and
metal particles.
5. The installation surface should be solid without ventilation.
6. The inverter should be away from electromagnetic
interference sources.
7. If there is too much dust in the environment, please close the
cooling hole.(As show in figure 2-1-A)
Closed position of heat dissipation hole
Figure 2-1-A

DL100 Series Universal Low-Power Inverter
6Inverter Installation
If you have any special installation requirements, please contact us in
advance.
See Figure 2-1-B for installation spacing and distance requirement for single
inverter. Enough space should be leaved around the inverter. For installation of
multiple inverters, baffle plate should be applied between inverters to ensure
good heat dissipation, as shown in Figure 2-1-C.
Figure 2-1-B Installation Spacing Distance Figure 2-1-C Installation of Multiple Inverters
2.2 Installation dimension of inverters
W1
W
H
H1
DW1
W
H1
H
D
Category I and II inverters
DL100-2S0004(B)~ DL100-2S0015(B)
DL100-4T0007(B)~ DL100-4T0015(B)
Category III inverters
DL100-2S0022(B)
DL100-4T0022(B)~ DL100-4T0075(B)
导流隔板
变
频
器
变
频
器
Baffle plate
Inverter
WARNING
1.Refer to the instruction manual before installation
3.Do not remove any cover while applying power
and at least 10min. after disconnecting power.
4.Securely ground(earth) the equipment.
2.Do not connect AC power to output terminals UVW.
and operation.
!
风扇排气
50mm以上
120mm以上
50mm以上
120mm以上
Fan exhaust
50mm
above
50mm
above
120mm above
120mm above
Inverter

DL100 Series Universal Low-Power Inverter
Inverter Installation 7
The specific installation dimensions of DL100 series inverters are shown
infollowing table:
Inverter model
(three-phase 380V)
Inverter model
(single-phase 220V)
W1
W
H1
H
D
Screw
specification
DL100-2S0004(B)
59
68
139
148
110
M4
DL100-4T0007(B)
DL100-2S0007(B)
DL100-4T0015(B)
DL100-2S0015(B)
78
88
155
165
113
M4
DL100-4T0022(B)
DL100-2S0022(B)
DL100-4T0040(B)
DL100-4T0055(B)
99
109
199
209
135
M4
DL100-4T0075(B)

DL100 Series Universal Low-Power Inverter
8 Inverter Wiring
Chapter3 Inverter Wiring
3.1 Wiring precautions
(1) Make sure intermediate circuit breaker is connected between the
frequency inverter and power supply to avoid expanded accident
when the frequency inverter is faulty.
(2) In order to reduce electromagnetic interference, please connect surge
sorber on the coil of electromagnetic contactor, relay and etc. in the
surrounding circuit of the frequency inverter.
(3) Please use shielded wire of above 0.3mm² for the wiring of such
analog signals as frequency setting terminal AI and instrument loop
(AO), etc. The shielding layer shall be connected on the grounding
terminal E of the frequency inverter with wiring length less than
30m.
(4) The stranded wire or shielded wire of above 0.75mm² shall be
selected for the wiring of input and output loop (X1-X4) of relay; and
the shielded layer shall be connected to the common port CM of
control terminals, with wiring length less than 50 m.
(5) The control wire shall be separated from the power line of major
loop;it shall be at a distance of above 10cm for parallel wiring and
vertical for cross wiring.
(6) The connecting wire between the inverter and the motor shall be less than
30m; and when it is longer than 30m, the carrier frequency of the inverter
shall be appropriately reduced.
(7) All leading wires shall be fully fastened with terminals to ensure good
contact.
(8) The pressurization of all the leading wires shall be in compliance
with the voltage class of the frequency inverter.
Absorption capacitor or other RC absorbers shall not be
installed at U, V and W output end of the frequency
inverter, as shown in figure 3-1.
变频器
U
V
W
M
电 动 机
阻 容 吸 收 装 置
Figure 3-1 Forbidding connecting a RC absorber at the output terminal
RC absorber
Motor
Inverter

DL100 Series Universal Low-Power Inverter
Inverter Wiring 9
3.2 Wiring of peripheral elements
Power supply
The inverter shall be provided with power in accordance with specification
of input power supply designated by this operating manual
Air switch
1) When the frequency inverter is maintained or not in use for a long time,
2) the air switch will separate the frequency inverter from the power
supply;
3) When the input side of the frequency inverter has failures like short
circuit, the air switch can provide protection.
Contactor
It can conveniently control power-supply and power disconnection of the
inverter, and the power-on and power-off of the motor.
AC reactor
1) To promote power factor;
2) To reduce harmonic input of the inverter against the grid;
3) Weaken influenced caused by unbalanced voltage of three-phase power
supply.
Brake resistance
When the motor is at the dynamic braking status, it can avoid producing over
high pumping voltage in the DC loop.
Figure 3-2 Inverter Wiring
电 机
R/L1
S/L2
T
U
V
W
AC 电抗器
E550
AC 电源
PP
PB
空气开关
接触器
WARNING
1.Refer to the instruction manual before installation
3.Do not remove any cover while applying power
and at least 10min. after disconnecting power.
4.Securely ground(earth) the equipment.
2.Do not connect AC power to output terminals UVW.
and operation.
!
E550
制动电阻
Braking resistor
Air switch Contactor AC reactor
AC Power
supply
Motor

DL100 Series Universal Low-Power Inverter
10 Inverter Wiring
Recommended specifications are shown in following table:
Inverter model
Adaptive motor
(KW)
Wire specification
(main loop)
(mm2)
Air circuit breaker
(A)
Electromagnetic
contactor
(A)
DL100-2S0004
0.4
1.5
16
6
DL100-2S0007
0.75
2.5
20
12
DL100-2S0015
1.5
2.5
32
18
DL100-2S0022
2.2
4.0
32
18
DL100-4T0007
0.75
1.0
10
6
DL100-4T0015
1.5
1.5
16
12
DL100-4T0022
2.2
2.5
16
12
DL100-4T0040
4.0
4.0
32
18
DL100-4T0055
5.5
6
32
22
DL100-4T0075
7.5
6
40
32
Main loop terminal
Inverter model
Screw
spcification
Tightening torque
(N*m)
Recommended wire ear
model
DL100-2S0004
M3.5
0.7~0.9
PTV1.25-9
DL100-2S0007
M3.5
0.7~0.9
PTV2-9
DL100-2S0015
M3.5
0.7~0.9
PTV5.5-13
DL100-2S0022
M3.5
0.7~0.9
PTV5.5-13
DL100-2S0040
M3.5
0.7~0.9
PTV5.5-13
DL100-4T0007
M3.5
0.7~0.9
PTV1.25-9
DL100-4T0015
M3.5
0.7~0.9
PTV1.25-9
DL100-4T0022
M3.5
0.7~0.9
PTV2-9
DL100-4T0040
M3.5
0.7~0.9
PTV5.5-13
DL100-4T0055
M4
1.2~1.5
RNY5.5-4S
DL100-4T0075
M4
1.2~1.5
RNY5.5-4S
General control board and expansion card wiring terminal
General control
terminal
Screw
spcification
Tightening torque
(N*m)
Recommended wire ear
model
Control
board/extension card
terminal
M2
0.1~0.2
E0.5-6
Control
board/extension card
terminal
M3
0.3~0.4
E0.75-6
Wire ear model
W(mm)
F(mm)
L(mm)
H(mm)
d1(mm)
D(mm)
T(mm)
PVT/E
series
PVT1.25-9
1.9
9
19
10
1.7
4.2
0.8
PVT2-9
1.9
9
19
10
2.3
4.7
0.8
PVT5.5-13
2.8
13
26
13
3.4
6.5
1
E0.5-6
1.1
6
12
6
1
2.6
/
E0.75-6
1.1
6
12.3
6.3
1.2
2.8
/
Wire ear model
d2(mm)
W(mm)
F(mm)
L(mm)
H(mm)
d1(mm)
D(mm)
T(mm)
RNY
series
RNY
5.5-4S
4.3
7.2
5.9
22.5
13
3.4
6.7
1

DL100 Series Universal Low-Power Inverter
Inverter Wiring 11
PVT/E series RNY series
3.3 Basic wiring
Figure 3-3 Basic Wiring of Inverter
M
~
电动机
Ta
Tc
U
W
V
R
S
T
AO
GND
故障报警输出
电压表(0~10V)
三相电源
E
X1
X2
X3
CM
可编程输入端子
VS
AI
PB
外接制动电阻
接大地
×
×
×
三相断路器
PP
24V 辅助直流电源
0~10V(0~20mA)
频率设定
GND
E
CM
OC 开路集电极输出
X4
Frequency setting
To braking resistor
Auxiliary DC power supply
Voltmeter
(0-10V)
Open-circuit
collector output
Failure alarm output
To earth
Motor
Three-phase circuit breaker
Three-phase
power supply
Programmable
input terminal
d1
D
H
L
F
d2
W
T
T
L
FH
d1
D
W

DL100 Series Universal Low-Power Inverter
12 Inverter Wiring
3.4 Wiring of main loop terminal
Category I main loop terminal
Applicable models: DL100-2S0004(B)-2S0007(B)-4T0007(B)-4T0015(B)
Symbol
Function
PP
DC side voltage positive terminal
PB
Braking resistor can be
connected between PP and PB
R、L/S、N/T
To grid single-phase AC 220V/
three-phase 380V power supply;
L: Live wire,N: Neutral wire
U、V、W
To three-phase AC 220V motor
E
Earthing terminal
Category II main loop terminal
Applicable models: DL100-2S0022(B)-4T0022(B)-4T0040(B)
Symbol
Function
PP
DC side voltage positive terminal
PB
Braking resistor can be connected
between PP and PB
L/R、N/S、T
To grid single-phase AC 220V/
three-phase 380V power supply;
L: Live wire,N: Neutral wire
U、V、W
To three-phase AC 220V/380V
motor
E
Earthing terminal
Category III main loop terminal
Applicable models: DL100-4T0055(B)-4T0075(B)
EWV
U
PBPPTSR
Braking
resistor
The earth
Electric
motor
Three-phase
power input
Symbol
Function
PP
DC side voltage positive terminal
PB
Braking resistor can be
connected between PP and PB
R、S、T
To grid three-phase AC 380V
power supply
U、V、W
To three-phase AC 380V motor
E
Earthing terminal
Reverse connection of live wire and neutral wire is prohibited.
Braking
resistor
PBWVUPP
N/T
RL/S
E
Single-phase
/three-phase
power input
Electric
motor
The earth
PBWVUPP
T
N/S E
L/R
Single-phase
/three-phase
power input
Braking
resistor
The earth
Electric
motor
This manual suits for next models
20