Simplex 4100U-S1 User manual

4100U
Fire Alarm
FIRE
Operator's
Manual
SP1 Fire Indicator Panel
Operator’s Manual
4100U-S1 Fire Indicator
Pl
Operator’s
Manual
LT0395
Iss 1.0
Operator’s Manual


4100U-S1 Fire Panel Operator’s Guide
Fire detectors in the building are grouped into zones (searchable areas).
Zones can be Isolated by pressing the zone’s isolate pushbutton on the panel – this prevents an
alarm from activating the panel outputs.
When a non-isolated detector detects an alarm, the fire panel rings the bell, calls the fire brigade,
activates the Warning or Evacuation System and any other programmed functions.
The Fire Panel display consists of two sections – the Operator Interface (upper section) and the
Zone Isolate pushbutton switches & indicators (lower section).
The Operator Interface indicates common Alarm, Fault & Isolation Status on LEDs, and point
(detector) status on the LCD.
When an Alarm, Fault or Isolation occurs, the buzzer will operate until the corresponding
acknowledge (Ack) key is pressed.
The panel is reset by pressing SYSTEM RESET. If the alarm won’t reset the point may still be
activated. Press FIRE ALARM ACK when the point alarm is displayed, then press DISABLE, ENTER.
Press FAULT ACK (to acknowledge the fault caused by disabling a point), then press SYSTEM RESET
again. The disabled detector must be re-enabled when the condition is cleared.
Silence the Bell: Press the EXT BELL ISOLATE key.
Isolate signals to Evacuation System: Press the
WARN SYS ISOLATE key. This will turn off warning
sounders powered by the Fire Panel.
Isolate a Zone: Press the appropriate Zone Isolate
pushbutton and the Zone Isolated LED will turn on.
Acknowledge an Isolation: Press the ISOLATE ACK
key.
Acknowledge an Alarm: Press the FIRE ALARM ACK
key.
Acknowledge a Fault: Press the FAULT ACK key. Zone Isolate
Pushbuttons
Operator Interface

ii
Australian Standard AS 4428.1, Control and Indicating Equipment. SSL Listing No. afp1682
The 4100U-S1 is manufactured by Tyco Safety Products for : Tyco Services, Fire & Safety
47GilbyRoad
Notting Hill
VIC 3168
AUSTRALIA
©2006 Tyco Safety Products Westminster, Westminster, MA 01441-0001 USA.
All specifications and other information shown were current as of document revision date, and are
subject to change without notice.
Tyco, Simplex, the Simplex logo, MAPNET II, IDNet, TrueAlarm, SmartSync, WALKTEST,
MINIPLEX, and TrueAlert are trademarks of Tyco International Services AG or its affiliates in the U.S.
and/or other countries. VESDA is a trademark of Vision Products Pty Ltd.
Simplex fire alarm technology is protected by the following U.S. Patent Numbers:
TrueAlarm analog smoke detection: 5,155,468; 5,173,683 and 5,543,777. IDNet and
MAPNET II addressable communications; 4,796,025. TrueAlert addressable notification;
6,313,744 and 6,426,697. SmartSync horn/strobe control; 6,281,789.
No part of this document may be reproduced or transmitted in any form or by any means, electronic
or mechanical, for any purpose, without the express written consent of Tyco Safety Products.
Document Number : LT0395
Cross Reference : 579-197
Issue : 1.0 13 February 2006
11.10
23 March 2006 LT0395 Issue 1.0 Original based on LT0351 1.0-C
Manufacturer’s Details
Approvals
Manufacturer
Copyright and
Trademark
Information
Document
Firmware
Revision
Amendments

iii
If installed as per the Installation Manual this product complies with Class B limits of AS/NZS 3548.
4100U-S1 Panel Supplied by:
Installation Location
Contract/Job Number
As installed, FIP System Drawing Number
Panel Installation Date
Panel Commissioned Date
Weekly Battery Test Day & Time
Maintenance Company
Telephone
Service Contract
Some of the operation of the 4100U-S1, as described in this manual, is dependent on
custom configuration as performed by the field engineer. If the configuration is not as per
the recommended template, then operation may differ and compliance to AS4428.0 may
be invalid.
The 4100U-S1 has a facility to allow levels of passcode protection. The operation of all the
standard functions as described in this manual is to be programmed to not require entry of
a passcode.
ZONE ISOLATIONS - The zone isolate status is not stored in non-volatile memory, so if the panel
is powered down and back up, or if the CPU is reset, all zones will be de-isolated.
Product/Site
Cautions &
Warnings

iv
Approvals.....................................................................................................................ii
Manufacturer................................................................................................................ii
Copyright and Trademark Information.........................................................................ii
Document ....................................................................................................................ii
Firmware Revision.......................................................................................................ii
Amendments................................................................................................................ii
Product/Site................................................................................................................ iii
Cautions & Warnings.................................................................................................. iii
Chapter 1 Overview.........................................................................1-1
Introduction...............................................................................................................1-1
In this Chapter ..........................................................................................................1-1
Typical Panel Layout..............................................................................................1-2
Overview...................................................................................................................1-2
Basic System Description......................................................................................1-3
Overview...................................................................................................................1-3
Control Keys & Indicators......................................................................................1-6
Overview...................................................................................................................1-6
Control Keys & Indicator Functions..........................................................................1-6
Normal Appearance of Operator Interface...........................................................1-7
Description................................................................................................................1-7
Chapter 2 Managing Alarm Conditions.........................................2-1
Introduction...............................................................................................................2-1
In this Chapter ..........................................................................................................2-1
Acknowledging Alarms..........................................................................................2-2
What the System Does When an Alarm Occurs ......................................................2-2
Overview – Acknowledging Alarms..........................................................................2-2
Procedure.................................................................................................................2-3
Isolating (Silencing) the EWS or External Bell ....................................................2-4
Overview...................................................................................................................2-4
Isolating the EWS.....................................................................................................2-4
Isolating the External Bell.........................................................................................2-4
Isolating the Zone.....................................................................................................2-4
Isolating ACF Outputs............................................................................................2-5
Overview...................................................................................................................2-5
Operation..................................................................................................................2-5
Restoration ...............................................................................................................2-5
Resetting Air Conditioning Control ......................................................................2-6
Overview...................................................................................................................2-6
Indication ..................................................................................................................2-6
Resetting...................................................................................................................2-6
Displaying Event time ............................................................................................2-7
Procedure.................................................................................................................2-7
Resetting Points .....................................................................................................2-8
Overview...................................................................................................................2-8
Reset Procedure.......................................................................................................2-8
Chapter 3 Managing Fault and Isolate Conditions.......................3-1
Introduction...............................................................................................................3-1
In this Chapter ..........................................................................................................3-1
Acknowledging Fault or Isolate Conditions.........................................................3-2
How the 4100U-S1 Indicates the Presence of a Fault .............................................3-2
What Acknowledge Does .........................................................................................3-2
Panel Operating Procedure – Fault Condition..........................................................3-3
Resetting Fault Conditions .......................................................................................3-3
Viewing Fault or Isolate Conditions......................................................................3-4
Overview...................................................................................................................3-4
Chapter 4 Testing and Controlling Points.....................................4-1
Introduction...............................................................................................................4-1
In this Chapter ..........................................................................................................4-1
Table of Contents

v
Alarm and Fault Test for Zones.............................................................................4-2
Alarm Test ................................................................................................................4-2
Fault Test..................................................................................................................4-2
Isolating and De-isolating Zones ..........................................................................4-3
Overview...................................................................................................................4-3
Isolating a Zone........................................................................................................4-3
De-Isolating a Zone..................................................................................................4-3
Disabling and Enabling Points..............................................................................4-4
Disabling and Enabling Points..............................................................................4-4
Overview...................................................................................................................4-4
Disabling a point.......................................................................................................4-4
Enabling a point........................................................................................................4-4
Turning a Point ON or OFF....................................................................................4-5
Overview...................................................................................................................4-5
Turning a Point OFF.................................................................................................4-5
Turning a Point ON...................................................................................................4-5
Returning a Point to Automatic Operation................................................................4-5
Sounder (buzzer)......................................................................................................4-5
Chapter 5 Selecting Points for Status or Control.........................5-1
Introduction...............................................................................................................5-1
In this Chapter ..........................................................................................................5-1
Selecting Points from the Menu............................................................................5-2
Overview...................................................................................................................5-2
Procedure.................................................................................................................5-2
Selecting Points with the Entry Keypad...............................................................5-3
Overview...................................................................................................................5-3
Selecting Points........................................................................................................5-3
Chapter 6 Displaying and Modifying Detailed Point Attributes..6-1
Introduction...............................................................................................................6-1
In this Chapter ..........................................................................................................6-1
Display-Only Attributes..........................................................................................6-2
Select a Point............................................................................................................6-2
See the Attributes.....................................................................................................6-2
Summary of Display-Only Attributes.........................................................................6-2
Modifiable Point Attributes....................................................................................6-4
Overview...................................................................................................................6-4
Select a Point............................................................................................................6-4
See the Attributes.....................................................................................................6-4
Summary of Modifiable Attributes.............................................................................6-4
Chapter 7 Setting Access Levels and Logging In ........................7-1
Introduction...............................................................................................................7-1
In this Chapter ..........................................................................................................7-1
Operator Access Levels.........................................................................................7-2
Overview...................................................................................................................7-2
Logging In and Out of the System........................................................................7-3
Introduction...............................................................................................................7-3
Log In Procedure......................................................................................................7-3
Log Out Procedure ...................................................................................................7-4
Chapter 8 Viewing and Clearing Historical Logs..........................8-1
Introduction...............................................................................................................8-1
In this Chapter ..........................................................................................................8-1
Viewing and Clearing the Historical Alarm and Fault Logs ...............................8-2
Viewing Logs ............................................................................................................8-2
Clearing the Logs......................................................................................................8-2
Chapter 9 Service-Related Operations..........................................9-1
Introduction...............................................................................................................9-1
In this Chapter ..........................................................................................................9-1
Setting Time and Date............................................................................................9-2
Procedure.................................................................................................................9-2

vi
Displaying Software Revision ...............................................................................9-3
Overview...................................................................................................................9-3
Viewing Card Status Information..........................................................................9-4
Overview...................................................................................................................9-4
Procedure.................................................................................................................9-4
Power Supply/Charger Voltage and Current Readings............................................9-4
Displaying Network Node Information .................................................................9-5
Overview...................................................................................................................9-5
Procedure.................................................................................................................9-5
Lamp Test................................................................................................................9-6
Procedure.................................................................................................................9-6
Displaying IDNet & Mapnet Device Status...........................................................9-7
Introduction...............................................................................................................9-7
IDNet Display Information.........................................................................................9-7
IDNet Point Addressing............................................................................................9-7
How to Display an IDNet System Point....................................................................9-7
What To Do If an IDNet Point Will Not Reset...........................................................9-7
TrueAlarm Sensor Display Values............................................................................9-7
Chapter 10 System Test Procedures...........................................10-1
Introduction.............................................................................................................10-1
In this Chapter ........................................................................................................10-1
Walk Test™ ...........................................................................................................10-2
Overview.................................................................................................................10-2
WalkTest™by Group..............................................................................................10-2
Zone Coding Option ...............................................................................................10-2
Silent Walk Test......................................................................................................10-3
Enabling Walk Test.................................................................................................10-3
Walk Test Operation...............................................................................................10-4
Walk Test™ FEATURES.......................................................................................10-5
Introduction.............................................................................................................10-5
Abort Audible and Delay on Reactivation...............................................................10-5
Active/Not Active.....................................................................................................10-5
Auto Abort on Alarm...............................................................................................10-5
Auto Abort on Time-Out..........................................................................................10-5
Control List..............................................................................................................10-5
Delay Before Reset ................................................................................................10-6
Logging Option (Log/No Log).................................................................................10-6
Monitor Zone List....................................................................................................10-6
Programmer Configuration.....................................................................................10-6
Sig/No Sig (Silent Walk Test™ Selection)..............................................................10-6
System Fault...........................................................................................................10-6
Fault Audible...........................................................................................................10-7
Zone Code/Zero Code............................................................................................10-7
Walk Test™ PROCEDURES.................................................................................10-8
How to Enter Walk Test Mode...............................................................................10-8
How to Exit Walk Test Mode ..................................................................................10-9
How to Turn a Point Off........................................................................................10-10
How to Turn a Point On........................................................................................10-10
How to Return a Point to Auto..............................................................................10-11
How to Enable a Disabled Point...........................................................................10-12
What to do in Case of System Malfunction ..........................................................10-13
Chapter 11 Printing Reports.........................................................11-1
Introduction.............................................................................................................11-1
In this Chapter ........................................................................................................11-1
Setting Printer Options ........................................................................................11-2
Available Options....................................................................................................11-2
Printing a Report...................................................................................................11-3
Overview.................................................................................................................11-3
Procedure...............................................................................................................11-3
Chapter 12 Maintenance Procedures ..........................................12-1
Introduction.............................................................................................................12-1

vii
In this Chapter ........................................................................................................12-1
Weekly Tests.........................................................................................................12-2
Procedure...............................................................................................................12-2
Battery Test ............................................................................................................12-2
Monthly Tests........................................................................................................12-3
Procedure...............................................................................................................12-3
Annual Tests .........................................................................................................12-4
Procedure...............................................................................................................12-4

viii

1-1
This chapter provides an overview of the 4100U-S1 operator interface and describes the
normal appearance of the operator interface.
Refer to the page number listed in this table for information on a specific topic.
Topic See Page #
Typical Panel Layout 1-2
Basic System Description 1-3
Control Keys 1-6
Normal Appearance of Operator Interface 1-7
Chapter 1
Overview
Introduction
In this Chapter

1-2
The 4100U-S1 is supplied with an Operator Interface plus one Expansion Bay in a 21U sized
cabinet.
The Zone Isolate modules are fitted into the Expansion bays from left to right. The first zone
is at the top of the leftmost module.
Typical Panel Layout
Overview
Figure 1-1. Zone detail
Emergency Operating I nstructions
SYSTEM IS NORMAL
08:23:43 am
MON 11 -DEC-00
Fire Control
Figure 1-1. Typical Panel Layout
Operator Interface
A
lphanumeric display, Keypad,
Acknowledge & Control Keys.
Zone Isolate Modules
Red LED indicates alarm,
Yellow LED indicates isolation,
Pushbutton isolates & de-isolates Ancillary
Controls
These are optional,
panel (site) specific
controls
Isolate
Pushbutton Red Alarm
LED
Y
ellow
Isolate
LED

1-3
The Simplex 4100U-S1 Fire Alarm Control Panel (FIP) has three general functions.
• It monitors fire alarm initiating points (smoke detectors, heat detectors etc.).
• It activates fire alarm notification devices (bells, strobes, brigade call) when an initiating
point activates.
• It monitors and controls ancillary building equipment (fan controls, relays, etc).
Note: The term point is used extensively throughout this manual. It is a generic
term used to refer to an individual component of the system, such as a single
smoke detector, a single break-glass manual call point, etc.)
The operator interface, shown in Figure 1-2, allows a system operator to control and monitor
the site-specific components connected to the 4100U-S1 FIP.
Figure 1-2. Operator Interface
Table 1-1. Components of the Operator Interface
LED/ Description Refer To
Zone Alarm LED This LED flashes when any Zone
Alarm LED is on and the zone is not
isolated. It goes steady when all
zones in alarm are isolated.
Control Keys Typical functions include: Alarm Test,
Fault Test, Bell Isolate, Warning
System Isolate & ACF Isolate. Chapter 1
ALARMS
Fire Alarm LED
The Fire Alarm LED flashes to
indicate the presence of an
unacknowledged alarm condition.
Other components of the system,
such as the horns and strobes, also
activate to indicate the presence of
an alarm.
Chapter 2
Fire Alarm Ack Key The Fire Alarm Ack key allows you to
indicate that you have observed the
presence of an alarm. Chapter 2
Priority 2 Alarm LED and
Ack Key Not normally used in Australia. N/A
Continued on next page
Basic System Description
Overview
Control Keys
& Indicators
Entry
Keypad

1-4
Table 1-1. Components of the Operator Interface (continued)
LED/Key Description Refer To
SYSTEM WARNINGS
The System Warning LEDs –
Isolation and Fault – indicate when
abnormal, non-fire conditions occur. Chapter 3
Isolate LED and Ack Key When any zone is isolated, this LED
turns on and the buzzer sounds until
Isolate Ack is pressed. Chapter 3
Fault LED and Ack Key When any fault occurs this LED turns
on and the buzzer sounds until Fault
Ack is pressed. Chapter 3
Alarm Silenced LED/Alarm
Silence Key Not normally used in Australia N/A
AC Power LED Indicates the presence of AC power
at the panel. N/A
System Reset Key
Pressing this key directs the panel to
reset all attached devices and clear
all acknowledged alarms, faults, and
isolation conditions.
Chapter 2
Event Time Key Used to display the time at which an
acknowledged alarm, fault, or
isolation condition occurred. Chapter 2
Entry Keypad Used to call up points for monitoring
and control. Chapter 5
Enable & Disable Keys Pressing these keys allows you to
enable or disable devices attached to
the panel. Chapter 4
On/Off/Auto Keys
Pressing these keys allows you to
force a device (such as a relay) ON
or OFF. The Auto key returns
control of the device to the panel.
Chapter 4
Arm & Disarm Keys Used with security points. These
keys allow you to turn security
devices on (arm) or off (disarm). N/A
More Info. Used in some options to request
information. Chapter 9
Lamp Test Pressing this turns on all LEDs to
show that they operate. Chapter 9
Menu / Next / Previous /
< / >
Press the Menu key to display the
menu options on the LCD. Next &
Previous allow stepping through
options/events, < & > allow cursor
movement in the LCD.
Chapter 5 on
Continued on next page
Basic System Description, Continued
Overview,
(continued)

1-5
Table 1-1. Components of the Operator Interface (continued)
LED/Key Description Refer To
Alphanumeric Display
Displays text describing abnormal
conditions for devices attached to the
panel (e.g., smoke detector in main
lobby is in alarm). Also displays
system prompts and messages.
Important Note: The degree to which you are allowed to control the system depends
on the passcode assigned to you. See Chapter 7 for details on this. Standard Fire
Fighter operations do not require logging in.
Basic System Description, Continued
Overview,
(continued)

1-6
The control keys and indicator LEDs are located on the far left of the Operator Interface.
A control key is pressed to perform the labelled function, and the associated LED turns on to
show the function is active. Pressing the key again de-selects the function and turns off the
LED.
CAUTION: OPERATION OF THESE KEYS MAY CAUSE ALARM SIGNALS TO
SOUND OR FAULT CONDITIONS TO BE GENERATED BY THE SYSTEM.
These keys can be pressed at any time. The key feedback (beep on buzzer) and the LED
turning on/off may be the only acknowledgment of the action.
Control Keys & Indicators
Overview
Control Keys &
Indicator Functions
Figure 1-3. Control Keys &
LEDs
• Zone Alarm - The red indicator is on when
there is an active (non-isolated) alarm in any
zone.
• Fault Test On – This indicator lights when
zone fault tests have been enabled by pressing
the ALARM/FAULT TEST key. When this
indicator is on, and a zone isolate key is
pressed, a fault test is performed on that zone.
• Alarm/Fault Test –This key cycles between
Alarm Test, Fault Test, and Normal for zone
test modes. The indicator lights when zone
alarm tests are enabled, the Fault Test On
indicator lights when fault tests are enabled,
and both these indicators are off when
alarm/fault tests are not enabled.
When this indicator is on, and a zone isolate
key is pressed, an alarm test is performed on
that zone. Any programmed outputs will
operate (including the Brigade signal). If the
zone was already isolated then the test will not
de-isolate it, i.e. the programmed outputs will
not operate.
• A/C Auto/Reset – The indicator lights when
the air conditioning system has been
automatically controlled by the 4100U.
Pressing the key will reset the air conditioning
system to normal operation.
• ACF Isolate – When this key is active, it
prevents ancillary controls: door holders,
security trips etc. from operating.
• Bell Isolate - When this key is active, it
prevents the fire alarm bell from operating.
• Warn Sys Isolate - When this key is active, it
prevents the Warning System from operating.

1-7
The 4100U-S1 operator interface panel shows the following under normal conditions.
• Green AC Power LED is ON – indicating the panel is receiving AC Power.
• All other LEDs off.
• Alphanumeric display reports that the system is normal and shows the current time
and date, as shown below.
Note: If the appearance of the operator interface is not as shown
above, refer to the information in Chapters 2 and 3 for instructions
on managing the alarm, fault, or isolate condition.
Normal Appearance of Operator Interface
Description
SYSTEM IS NORMAL
08:23:45 MON 18-SEPT-00

1-8

2-1
An alarm condition occurs when an actuating device (such as a manual call point, smoke
detector, etc.) activates. The 4100U-S1 indicates the presence of the alarm condition through
messages it displays on the alphanumeric display, by illuminating the ALARM indicator
LEDs, and by activating the building’s EWS and external bell.
This chapter describes using the Operator Interface Panel keys to investigate and manage
alarm conditions.
Refer to the page number listed in this table for information on a specific topic.
Topic See Page #
Acknowledging Alarms 2-2
Isolating (Silencing) the EWS or External Bell 2-4
Isolating ACF Outputs 2-5
Resetting Air Conditioning Control 2-6
Displaying Event time 2-7
Resetting Points 2-8
Chapter 2
Managing Alarm Conditions
Introduction
In this Chapter

2-2
When the first alarm condition is detected by the 4100U-S1, the panel does the following to
indicate the presence of the alarm.
• Red Fire Alarm and common Zone Alarm LED indicators flash
• Red Zone Alarm LED flashes on the display module showing the affected zone.
• Sounder (buzzer) pulses
• Emergency Warning System (EWS) and External bell activate
• Alphanumeric display on the operator interface shows the location and type (smoke, call
point, etc.) of the point in the alarm condition. An example is shown in Figure 2-1.
• Any programmed outputs, including the Brigade connection, operate.
Figure 2-1. Alphanumeric Display Showing Typical Alarm
The first step in managing an alarm condition is to acknowledge the alarm. Acknowledging
an alarm does two important things:
• It records the time and date at which you observed the presence of the alarm and stores
that information in the system’s historical log.
• If multiple alarms are present, the system displays specific data for the next alarm when
you press the <FIRE ALARM ACK> key.
Acknowledging Alarms
What the System
Does When an
Alarm Occurs
Overview –
Acknowledging
Alarms
Other manuals for 4100U-S1
1
Table of contents
Other Simplex Firefighting Equipment manuals
Popular Firefighting Equipment manuals by other brands

babcockdavis
babcockdavis BHRVE15C-P manual

Tyco
Tyco LFII Series manual

Global Fire Equipment
Global Fire Equipment INT-TCP/IP-WEB Configuration manual

Rapid Spray
Rapid Spray FIRE MARSHAL Operator's handbook

Task Force Tips
Task Force Tips TORNADO Instructions for installation, operation and maintenance

Tyco
Tyco K17-231 quick guide