14 Technical Information
Service Manual
If Tamb.7preset +2°C, the unit enters heating mode, in which case the four-way valve, the compressor and the outdoor fan will operate
simultaneously, and the indoor fan will run at preset speed in the condition of preset cold air prevention.
If Tamb.7preset +5°C, the compressor will stop, the outdoor fan will stop with a time lag of 30s, and the indoor fan will stop after 60-second blow
at low speed
If Tpreset +2°C<Tamb.< Tpreset +5°C, the unit will maintain its original operating status.
Under this mode, the four-way valve is energized and temperature can be set within a range of 16~30°C. The operating symbol, the
heating symbol and preset temperature are revealed on the display.
ĸCondition and process of defrost
When duration of successive heating operation is more than 45 minutes, or accumulated heating time more than 90 minutes, and one of
the following conditions is reached, the unit will enter the defrost mode after 3 minutes.
(1)Toutdoor ambient ˚5°C, Toutdoor tube&
&7outdoor ambient ˘5°C, Toutdoor tube&
&7outdoor ambient ˘-2°C, Toutdoor tube&
&7outdoor ambient ˘-5°C, Toutdoor tube-Tcompensatory7outdoor ambient-3°C)
(5)Toutdoor ambient ˘-10°C, Toutdoor tube-Tcompensatory7outdoor ambient-3°C)
(after energizing, Tcompensatory &GXULQJWKH¿UVWGHIURVWLQJLILWLVQRWWKH¿UVWGHIURVWLQJ7compensatoryLVFRQ¿UPHGE\7outdoor tube of quitting last
defrosting: a. when Toutdoor tube ˚2°C, Tcompensatory=0°C; b. when Toutdoor tube&7compensatory=3°C)
At that time, the indoor fan stops and the compressor stops, and after 30 seconds the outer fan will stop, and then after 30 seconds, the
four-way valve will stop. After 30 seconds, the compressor is initiated for raising the frequency to defrost frequency.
When the compressor has operated under defrost mode for 7.5 minutes, or Toutdoor ambient&WKHFRPSUHVVRUZLOOEHFRQYHUWHGWR+]
operation. After 30 seconds, the compressor will stop. And after another 30 seconds, the four-way valve will be opened, and after 60
seconds, the compressor and the outer fan will be started, the indoor fan will run under preset cold air prevention conditions, and H1 will be
displayed at temperature display area on the display panel. Defrost frequency is 85Hz.
ĹProtection
ƹCold air prevention
The unit is started under heating mode (the compressor is ON):
ķIn the case of Tindoor amb. <24°C: if Ttube&DQGWKHLQGRRUIDQLVDWVWRSVWDWHWKHLQGRRUIDQZLOOEHJLQWRUXQDWORZVSHHGZLWKDWLPH
lag of 2 minutes. Within 2 minutes, if Ttube>40°C, the indoor fan also will run at low speed; and after 1-minute operation at low speed, the
indoor fan will be converted to operation at preset speed. Within 1-minute low speed operation or 2-minute non-operation, if Ttube>42°C, the
fan will run at present speed.
ĸIn the case of Tindoor amb.&LI7tube&WKHLQGRRUIDQZLOOUXQDWORZVSHHGDQGDIWHURQHPLQXWHWKHLQGRRUIDQZLOOEHFRQYHUWHGWR
preset speed. Within one-minute low speed operation, if Ttube>42°C, the indoor fan will be converted to preset speed.
Note: Tindoor amb. indicated in ķand ĸrefers to, under initially heating mode, the indoor ambient temperature before the command to start
the compressor is performed according to the program, or after the unit is withdrawn from defrost, the indoor ambient temperature before
the defrost symbol is cleared.
ƹTotal current up and frequency down protection
If the total current Itotal$IUHTXHQF\ULVHZLOOEHDOORZHGLI,total$IUHTXHQF\ULVHZLOOQRWEHDOORZHGLI,total$WKHFRPSUHVVRUZLOOUXQDW
reduced frequency; and if Itotal$WKHFRPSUHVVRUZLOOVWRSDQGWKHRXWGRRUIDQZLOOVWRSZLWKDWLPHODJRIV
(4) Fan mode
Under the mode, the indoor fan will run at preset speed and the compressor, the outdoor fan, the four-way valve and the electric heater will
stop.
Under the mode, temperature can be set within a range of 16~30°C .
(5) AUTO mode
ķWorking conditions and process of AUTO mode
a. When Tambient &WKHXQLWZLOORSHUDWHLQFRROPRGH7KHVHWWHPSHUDWXUHLV&
b. When Tambient&WKHKHDWSXPSXQLWZLOORSHUDWHLQ+HDWPRGHVHWWHPSHUDWXUHEH&WKHFRROLQJRQO\XQLWZLOORSHUDWHLQ)DQ
mode, set temperature be 25°C.
F:KHQ&7ambient&WKHXQLWZLOORSHUDWHLQWKHSUHYLRXVVWDWH,ILWLVHQHUJL]HGIRUWKH¿UVWWLPHLWZLOORSHUDWHLQ)DQPRGH
d. Under auto mode, if its cooling mode, operation frequency is same as that under cooling mode; if its heating mode, operation frequency
is same as that under heating mode.
ĸProtection
a. In cooling operation, protection is the same as that under the cooling mode;
b. In heating operation, protection is the same as that under the heating mode;
c. When ambient temperature changes, operation mode will be converted preferentially. Once started, the compressor will
remain unchanged for at least 6 minutes.
(6) Common Protection Functions and Fault Display under COOL, HEAT, DRY and AUTO Modes
ķOverload protection
Ttube: measured temperature of outdoor heat exchanger under cooling mode; and measured temperature of indoor heat exchanger under
heating mode.