Operatlng voltage: 120/208/240/277 Vac, 50/60 Hz
Maximum load:
1800 W @ 120 V / 15 A
3120 W @ 208 V / 15 A
3600 W @ 240 V / 15 A
4155 W @ 277 V / 15 A
Setpoint range: 41 ˚F to 97 ˚F (5 ˚C to 36 ˚C)
Display range: 32 ˚F to 99 ˚F (0 ˚C to 50 ˚C)
Resolution: ±1 ˚F (±0.5 ˚C)
Storage: -4 ˚F to 122 ˚F (-20 ˚C to 50 ˚C)
Operation: 32 ˚F to 122 ˚F (0 ˚C to 50 ˚C)
Compatible with an electric heating system such as:
• Baseboard heater
• Convector
• Fan-forced convector
• Radiant ceiling heating
OFF MODE TECHNICAL SPECIFICATIONS
3-year limited warranty
SINOPÉ TECHNOLOGIES INC. warrants the components of their products against
defects in material and workmanship for a 3 year period from the date of purchase,
under normal use and service, when proof of purchase of such is provided to the
manufacturer. This warranty does not cover any transportation costs that may be
incurred by the consumer. Nor does it cover a product that has been improperly
installed, misused or accidentally damaged. The obligation of SINOPÉ
TECHNOLOGIES INC., under the terms of this warranty, will be to supply a new unit
and this releases the manufacturer from paying the installation costs or other
secondary charges linked to replacing the unit or the components.
For more information, visit our Website:
660-0735-0026-A
ADVANCED SETTINGS
Setpoint Min
Scale
Load
Temperature scale
°C or °F (Default: °F)
Load power
0 W to 4155 W
Minimum setpoint
41 °F to 97 °F – (Default: 41 °F)
To change the thermostat’s settings, you need to:
Get the setpoint to its minimum and hold the button for
10 seconds to access the menu.
Press the or button to change the setting.
Press the and buttons simultaneously to save and go to
the next parameter. Continue to press until the end of the list
to exit the menu.
Name Parameters & settings Display
3
Setpoint Max
Maximum setpoint
41 °F to 97 °F – (Default: 97°F)
4
Backlight
Backlight control
ON, OFF or BED – (Default: ON)
ON (backlight always active, will dim
according to ambient light)
OFF (will only turn on when a button
is pressed)
BED (bedroom mode - backlight will dim
according to ambient light and will turn
OFF below 20% of luminosity)
5
Hold for 10 sec.
To put the thermostat in OFF mode, hold the buttons and
for 10 seconds.
To exit the OFF mode, hold the buttons and for
10 seconds or raise/lower the setpoint.
Hold for 10 sec.
Set
Set