VENTING SYSTEM REGULAR INSPECTION
A. Inspect the system regularly for condensation, corrosion
and/or physical damage. A qualified professional should
service the boiler annually and include such an inspection at
that time. The homeowner should look over the system
monthly for damage, water stains, any signs of rust, other
corrosion or separation of the flue (vent) tubing and fittings.
B. Should an inspection turn up signs of condensation, corrosion
or damage, the boiler should be shut down immediately and
the condition should be corrected by a qualified professional.
C. All Victory II boilers are equipped with a built-in condensation
drain and trap. The trap loop must be filled with water. DO NOT
operate the boiler without filling the trap with water to prevent
flue gas discharge into space. Periodic inspection should be
made of this assembly for deterioration of the tubing and to
insure that the trap is not plugged. If it is plugged or appears to
have excessive sediment in it, it should be removed from the
drain assembly, straightened out to clear the obstruction,
reformed, filled with water and reinstalled as before.
GAS PIPING
A. Local installation codes apply. The pipe joint compound used
on threads must be resistant to the action of liquefied
petroleum gases.
B. The gas supply line to the boiler should be run directly from
the meter for natural gas or from the fuel tank for L.P. propane
gas. See page 2 for location of union and manual main shut-
off valve that may be specified locally.
Selecting pipe size for natural gas:
1. Measure or estimate the length of piping from the meter to
the installation site.
2. Consult gas supplier for heating value of gas (W/m)
(BTU/cu. ft.).
3. Divide boiler rated input by heating value to find gas flow
in piping (m3/hr.) (cu. ft. per hour).
4. Use table below to select proper pipe size.
Example: Boiler model VHS 150 is to be installed. Distance from
gas meter to the boilers is 9.1 m (30 ft). Heating value of natural
gas is 10 557 W/m3(1020 BTU/cu. ft.) Select proper pipe size.
At 9.1 m (30 ft.) length of pipe, match required capacity from
table on this page (choose higher capacity, in this case 4.3 m3/hr.
(152 cu. ft. per hour).) Required pipe size is 19 mm (3/4").
Improper gas pipe sizing will result in pilot flame outages,
insufficient heat and other installation difficulties. For more
information and also if other appliances are to be attached to the
piping system, see Appendix C of National Fuel Gas Code ANSI
Z223.1-latest edition or CSA B 149.1 latest edition for natural
gas and propane.
C. The boiler and its gas connection must be leak tested before
placing the boiler in operation. Use liquid soap solution for all
gas leak testing. DO NOT use open flame. This boiler and its
individual shutoff valve must be disconnected from the gas
supply piping system during any pressure testing of that
system at test pressures in excess of 3.5 kPa (1/2 PSIG). This
boiler must be isolated from the gas supply piping system by
closing its individual manual shutoff valve during any
pressure testing of the gas supply piping system at test
pressures equal to or less than 3.5 kPa (1/2 PSIG).
D. All gas piping used should be inspected thoroughly for
cleanliness before makeup. A sediment trap must be
provided, as illustrated on page 2.
E. The minimum and maximum gas supply pressure (at the inlet
of gas valve) are shown on the boiler rating plate for the type
of gas used. Gas supply pressure should never be less than
minimum or more than maximum pressure when the boiler
or any other appliance is turned on or off.
ELECTRICAL WIRING
DANGER:Before wiring, always turn off electric power
supply, otherwise, shock or death can result.
1. Power Supply
A separately fused circuit is recommended. Use a standard
15 Amp. fuse or breaker and 14 gauge conductors in BX
cable or conduit.
Provide disconnect means and overload protection as
required. See boiler wiring diagram (Figure 11a) and ladder
diagram (Figure 11b).
Boiler must be electrically grounded in accordance with the
requirements of the authority having jurisdiction, or, in the
absence of such requirements, with the Canadian Electrical
Code, CSA-C22-1, Part 1-latest edition.
2. Power Connection
A. Remove electrical junction box cover.
B. Hot connection lead is black. Neutral connection lead is red.
C. Connect ground wire to ground screw inside the junction box.
D. Replace junction box cover.
3. Thermostat Connections
Thermostat wire connections must be to T and TV screw
terminals on Aquastat.
See wiring diagram,Figure 11a.
4. Multi Zoning
For pump zoning system, see Figures 12 and 13, for zone
valve system, see Figure 14. DO NOT use boiler transformer
to power external accessories like zone valve and relays,
overload and/or burned-out transformer and boiler
malfunction can result.
Gas flow = 43 965 W/hr. = 4.16 m3/hr.
10 557 W/m3
(Gas flow = 150,000 BTU/hour = 147 cu. ft. per hour)
1020 BTU/cu. ft.
1/2” 3/4” 1” 1 1/4” 1 1/2”
mft
m3/hr cu.ft./hr. m3/ hr cu.ft./hr. m3/hr cu.ft./hr. m3/hr cu.ft./ hr. m3/hr cu.ft./hr.
3.0 10 3.7 132 7.9 278 14.7 520 29.7 1050 45.3 1600
6.1 20 2.6 92 5.4 190 9.9 350 20.7 730 31.1 1100
9.1 30 2.1 73 4.3 152 8.1 285 16.7 590 25.2 890
12.2 40 1.8 63 3.7 130 6.9 245 14.2 500 21.5 760
15.2 50 1.6 56 3.3 115 6.1 215 12.5 440 19.0 670
18.3 60 1.4 50 3.0 105 5.5 195 11.3 400 17.3 610
21.3 70 1.3 46 2.7 96 5.1 180 10.5 370 15.9 560
24.3 80 1.2 43 2.5 90 4.8 170 9.9 350 15.0 530
27.4 90 1.1 40 2.4 84 4.5 160 9.1 320 13.9 490
30.5 100 1.1 38 2.2 79 4.2 150 8.6 305 13.0 460
Length
of Pipe
Gas Flow In Piping
Pressure Drop = 8mm (.3”) in water Specific Gravity = 0.60
Iron Pipe Size (Ips) inches
At pressure drop of 0.3 in. water, specific gravity = 0.60.
14 VICTORY II VHS MODELS