Smarteh LPC-2.DT1B User manual

USER MANUAL
Longo programmable controller
LPC-2.DT1B
Light Switch Control panel
Version 1
SMARTEH d.o.o. / Poljubinj 114 / 5220 Tolmin / Slovenia / Tel.: +3 6(0)5 3 44 00 / e-mail: info@smarteh.si / www.smarteh.si

Longo programmable controller LPC-2.DT1B
Written by SMA TEH d.o.o.
Copyright © 2013, SMA TEH d.o.o.
User Manual
Document Version: 001
September 1, 2013
i

Longo programmable controller LPC-2.DT1B
STANDA DS AND P OVISIONS: Standards, recommendations,
regulations and provisions of the country in which the devices will
operate, must be considered while planning and setting up electrical
devices. Work on 230 V AC network is allowed for authorized
personnel only.
DANGE WA NINGS: Devices or modules must be protected from
moisture, dirt and damage during transport, storing and operation.
WA ANTY CONDITIONS: For all modules LONGO LPC-2 – if no
modifications are performed upon and are correctly connected by
authorized personnel – in consideration of maximum allowed
connecting power, we offer warranty for 24 months from date of sale
to end buyer. In case of claims within warranty time, which are based
on material malfunctions the producer offers free replacement. The
method of return of malfunctioned module, together with description,
can be arranged with our authorized representative. Warranty does
not include damage due to transport or because of unconsidered
corresponding regulations of the country, where the module is
installed.
This device must be connected properly by the provided connection
scheme in this manual. Misconnections may result in device damage,
fire or personal injury.
Hazardous voltage in the device can cause electric shock and may
result in personal injury or death.
NEVE SE VICE THIS P ODUCT YOU SELF!
This device must not be installed in the systems critical for life (e.g.
medical devices, aircrafts, etc.).
If the device is used in a manner not specified by the manufacturer,
the degree of protection provided by the equipment may be impaired.
Waste electrical and electronic equipment (WEEE) must be collected
separately!
LONGO LPC-2 complies to the following standards:
•EMC:EN 61000-6-2 (EN 50082), EN 61000-6-4 (EN 50081)
•LVD: IEC 61131-2
•Vibrations and climatic-mechanical: EN 60068-2-6, EN 60068-2-27,
EN 60068-2-29
Smarteh d.o.o. operates a policy of continuous development.
Therefore we reserve the right to make changes and improvements to
any of the products described in this manual without any prior notice.
MANUFACTU E :
SMA TEH d.o.o.
Poljubinj 114
5220 Tolmin
Slovenia
ii

Longo programmable controller LPC-2.DT1B
Longo programmable controller LPC-2.D 1B
1 DESC IPTION...................................................................................1
2 FEATU ES.......................................................................................2
3 OPE ATION.....................................................................................3
3.1 Operational modes.....................................................................3
3.2 Parameters..............................................................................3
4 INSTALLATION..................................................................................5
4.1 Connection scheme....................................................................5
4.2 Mounting frame selection............................................................7
4.3 Mounting instructions.................................................................8
4.4 Module labeling........................................................................9
5 TECHNICAL SPECIFICATIONS................................................................10
6 CHANGES .....................................................................................11
7 NOTES..........................................................................................12
iii

Longo programmable controller LPC-2.DT1B
1 DESCRIP ION
LPC-2.DT1B control panel (CP) is used to switch on and off four individual or group of lights.
Panel is equipped with four push buttons (PB), temperature sensor and light intensity sensor.
To switch on or off individual or group of lights , corresponding PB should be pressed respectively.
For example if first light is switched off, light symbol next to PB1 on LCD will represent off status.
After PB1 pressing, light symbol next to PB1 on LCD will represent on status and on command will be
sent to MCU. When PB1 is pressed next time, light symbol next to PB1 on LCD will change and show
off status. Light off command will be sent to MCU. From MCU side, remote on and off switching off
four individual or group of lights is also supported.
Color back ground LCD picture is possible to change by using Smarteh LCD Composer software.
Light intensity sensor controls LCD intensity.
It is possible to display real time clock (HH:MM). Enabling can be done by MCU enable commands.
All parameters are accessible on panel's communication port. When panel is connected to the LPC-2
main control unit (MCU) parameters can be viewed and modified with LPC Manager application.
LPC-2.DT1B parameters allows adaptation to desired panel functionality.
1

Longo programmable controller LPC-2.DT1B
2 FEA URES
Figure 1: LPC-2.DT1B module.
able 1: Features
4 touch buttons to switch light on/off
4 light symbols to show lights on/off status
Temperature measurement
Light intensity measurement
LCD intensity control
Color LCD with possibility of back ground picture changing1
1 For LCD background picture replacement, please refer to LCD Composer Help→.
2

Longo programmable controller LPC-2.DT1B
3 OPERA ION
Basic switching can be done with panel Push Buttons (PB).Modes of operation and commands can be
set via LPC Manager software.
It is advised to press touch-buttons respectively with finger not faster than 1 press per second.
Press should be done with whole finger tip. Brief pressing could not activate the action, because of
protection against the noise and other influence.
3.1 Operational modes
Normal mode
When CP is connected and communicating with MCU, all available functions are active
Error
In case of CP internal on communication fault, “E ” sign appear on LCD.
Set
When any of four buttons is pressed more than certain time, “SET” sign appear on LCD and buttons
functioning is enabled. After “SET” sign is off, push buttons functions are disabled.
3.2 Parameters
If parameter is set to logical “1”, is considered to be active, enabled or set. If parameter has
logical value “0” is considered to be inactive, disabled, or cleared.
Parameter can be status, command or both. When parameter is marked as status this means that
module is sending information to controller. On the other hand, command represents request from
MCU to module.
Light x (Off/On) status: When any of four statuses is active, command for individual light on is
requested. Corresponding light on symbol is present on LCD screen. If status is not active,
command for individual light off is requested. Corresponding light off symbol is present on
LCD screen.
Light x (Local/Remote) status: Active status is telling that corresponding light on/off command is
controlled by light on command from MCU. When this status is not active, local light on/off
commands are enabled.
Communication status: Feed back of communication flag, received from MCU. Used for
communication diagnose between MCU and CP.
Light Off MIN value: Feed back of Light Off MIN value received from MCU. Below this set value,
LCD back light will turn off. Value 0 .. 100 represents 0 .. 100 % light intensity.
3

Longo programmable controller LPC-2.DT1B
ctual temp.: Actual room temperature 0 .. 5000 represents 0.00 .. 50.00 °C.
ctual light: Actual room light intensity 0 .. 100 represents 0 .. 100%.
Light x (Off/On) command: remote On/Off command for individual light. This command is enabled
using corresponding Light x (Local/Remote) command.
Light x (Local/Remote) command: Enables corresponding light On/Off remote command.
Clock display enable command: Time Clock display enable command from MCU. When active, time
will be displayed on CP.
Light Off MIN set value: Below this set value, LCD back light will turn off. Value 0 .. 100
represents 0 .. 100 % light intensity.
Clock set value: Clock to be displayed on LCD in HH:MM format. High byte of an unsigned integer
variable represents hours (HH) and low byte represents minutes (MM). For example value
2592 ( [10*256]+32 = 2592) will be represented as 10:32.
Communication: Used for communication diagnose between MCU and CP. Normally this bit is
toggled every 1 second from MCU side and than Communication feed back status is
supervised on the MCU side.
4

Longo programmable controller LPC-2.DT1B
4 INS ALLA ION
4.1 Connection scheme
Figure 2: Connection scheme
5

Longo programmable controller LPC-2.DT1B
able 2: K1
K1.1 GND Ground
K1.2 7 .. 30 V DC Power supply input
K1.3 Standard S-485 A Data receive/send line A
K1.4 Standard S-485 B Data receive/send line B
able 3: LCD bars & Buttons
PB1
(Up-left) Light 1 Switch light 1 on/off, status is shown on LCD next to PB1
PB2
(Down-left) Light 2 Switch light 2 on/off, status is shown on LCD next to PB2
PB3
(Up-right) Light 3 Switch light 3 on/off, status is shown on LCD next to PB3
PB4
(Down-right) Light 4 Switch light 4 on/off, status is shown on LCD next to PB4
able 4: S1
RS-485
ADDRESS Switch 1 Switch 2
0 OFF OFF
1 OFF ON
2 ON OFF
3 ON ON
Interconnection cable can ordered from Smarteh or terminated on site, considering wiring scheme
bellow:
Interconnection
cable ICM-X.
6

Longo programmable controller LPC-2.DT1B
4.2 Mounting frame selection
Smarteh has verified following lines to be compatible with LPC-2.DT1B module:
●Bticino – Living, Light
●Gewiss – Playbus, System
●Vimar – Plana, Idea
●Tem – Modul Soft, Modul Line
●Master
Frames of other vendors most probably suits as well, but they were not verified by Smarteh. Before
installation verify compatibility of non listed frames.
Module housing has a fin on each side, which can be easily removed with knife cutter or pliers. This
adaptation enables housing to be build in various frame formats with two different depths. With
regard to frame used you may remove fin for housing to fit in.
Module with removable fin.
7

Longo programmable controller LPC-2.DT1B
4.3 Mounting instructions
Figure 3: Housing dimensions
Dimensions in milimeters.
All connections, module attachments and assembling must be done
while module is not connected to the main power supply.
Module should be positioned in the wall inside of the room. Avoid
direct sunlight or positioning near heating/cooling source object.
Usage of cover frames and holders made of metal, could cause the
decreased performance of touch buttons
ecommended installation height is 1.5 m above floor level.
1. Set the correct S-485 address (S1 switch) for LPC-2.DT1B (refer to the Table 4).
2. Connect interconnection cable to the connector K1. Max. allowed tensile force is 30 N.
3. Put the LPC-2.DT1B in mounting frames
4. Cover LPC-2.DT1B with cover plate
LPC-2.DT1B is connected to the main control unit with interconnection cable (e.g., SSK, ICM-7)
which must be ordered together with LPC-2.DT1B module. When more modules (e.g., LPC-2.C 1,
LPC-2.CH1, LPC-2.DP2 or up to four LPC-2.DT1B) are connected to main control unit, splitter (e.g.,
SPL-2) is also required (Figure 2). Module address on S-485 network is set with DIP switch on the
back of the module (Table 4).
NO E: Signal wires must be installed separately from power and high voltage wires in accordance
with general industry electrical installation standard.
8

Longo programmable controller LPC-2.DT1B
4.4 Module labeling
Figure 5: Labels
Label 1: Label 2:
Label 1 description:
•LPC-2.D 1B is the full product name
•P/N: 225DT1B10V01001 is the part number
•225 – general code for LPC-2 product family,
•DT1 – short product name,
•10 – year of code opening,
•V - denotes flush frame mounting module,
•01 – derivation code,
•001 – version code (reserved for future HW and/or SW firmware upgrades).
•D/C: 19/10 is the date code.
•19 – week and
•10 – year of production.
Label 2 description:
•S/N: DT1B-S9-0900000003 is the serial number.
•DT1B – short product name,
•S9 – user code (test procedure, e.g. Smarteh person xxx),
•10 – year (last two cyphers),
•00000003 – current stack number; previous module would have the stack number
00000002 and the next one 00000004.
9
S/N: DT1B-S9-1000000003
LPC-2.DT1B
P/N: 225DT1B10V01001
D/C: 19/10

Longo programmable controller LPC-2.DT1B
5 ECHNICAL SPECIFICA IONS
able 5: echnical specifications
Power supply from MCU
Interconnection connector type J-12 6/6
Power consumption 1 W
Dimensions (W x H x D) 75 x 49 x 29 mm
Weight 50 g
Maximum altitude 2000 m
Mounting position horizontal
Ambient temperature 0 to 50 °C
Ambient humidity max. 95 %, no condensation
Transport and storage temperature -20 to 60 °C
Protection class IP 20
10

Longo programmable controller LPC-2.DT1B
6 CHANGES
The following table describes all the changes to the document.
Date V. Description
1.9.2013 001 The initial version, issued as LPC-2.DT1B module UserManual.
11

Longo programmable controller LPC-2.DT1B
7 NO ES
12
Table of contents
Other Smarteh Control Panel manuals
Popular Control Panel manuals by other brands

Sigma
Sigma K1000 Series Operation & maintenance manual

DoorHan
DoorHan PCB-SW 24 Programming instructions

TRIATEK
TRIATEK L35 Series install guide

BOON EDAM
BOON EDAM Duotour DTAC Instruction card

Teletek electronics
Teletek electronics iRIS8 User Operation & Maintenance Manual

ATL
ATL ATL-9000 Series user manual