Smartgen HGM9510 User manual

HGM9510 Genset Parallel (With Genset) Unit
USER MANUAL
Smartgen Technology

Chinese trademark
English trademark
Smartgen —make your generator smart
Smartgen Technology Co., Ltd.
No. 28 Jinsuo Road
Zhengzhou city
Henan Province
P. R. China
Tel: +86-371-67988888/67981888
+86-371-67991553/67992951
+86-371-67981000(overseas)
Fax: 0086-371-67992952
Web: http://www.smartgen.com.cn
http://www.smartgen.cn
Email: [email protected]
All rights reserved. No part of this publication may be reproduced in any material form (including
photocopying or storing in any medium by electronic means or other) without the written
permission of the copyright holder.
Smartgen Technology reserves the right to change the contents of this document without prior
notice.
Version history
Date
Version
Contents
2013-02-18
1.0
Original release
2013-08-06
1.1
Modify the outside drawing and the main display description;
Modify some parameters’ default value; Add the description of
“Power Management Mode” and “Load Shedding Control”

HGM9510 GENSET PARALLEL UNIT
HGM9510 Genset Parallel Unit ISSUE 2013-08-06 Version 1.1Page 3 of 65
CONTENTS
1OVERVIEW.......................................................................................................5
2MODULES COMPARISON...............................................................................6
3PERFORMANCE AND CHARACTERISTICS...................................................7
4SPECIFICATION...............................................................................................9
5OPERATION...................................................................................................10
5.1 INDICATOR LIGHT........................................................................................................10
5.2 PUSHBUTTONS ...........................................................................................................10
5.3 LCD DISPLAY ...............................................................................................................11
5.3.1 MAIN DISPLAY..........................................................................................................11
5.3.2 USER MENU AND PARAMETERS SETTING MENU ...............................................13
5.4 AUTO START/STOP OPERATION...............................................................................16
5.5 MANUAL START/STOP OPERATION..........................................................................17
5.6 SWITCH CONTROL PROCEDURES............................................................................17
5.6.1 MANUAL TRANSFER PROCEDURES......................................................................17
5.6.2 AUTOMATIC CONTROL PROCEDURE....................................................................18
6PROTECTIONS...............................................................................................19
6.1 WARNING ALARMS......................................................................................................19
6.2 SHUTDOWNALARMS..................................................................................................21
6.3 TRIP AND STOP ALARMS............................................................................................23
6.4 TRIP ALARM.................................................................................................................24
7WIRING CONNECTION ..................................................................................25
8SCOPES AND DEFINITIONS OF PROGRAMMABLE PARAMETERS..........28
8.1 CONTENTS AND SCOPES OF PARAMETERS..........................................................................28
8.2 ENABLE DEFINITION OF PROGRAMMABLE OUTPUT PORTS..................................38
8.2.1 DEFINED PERIOD OUTPUT.....................................................................................41
8.2.2 DEFINED COMBINATION OUTPUT .........................................................................42
8.3 DEFINED CONTENTS OF PROGRAMMABLE INPUT PORTS (ALL ACTIVEWHEN
CONNECT TO GRAND (B~))....................................................................................................43
8.4 SELECTION OF SENSORS..........................................................................................45
8.5 CONDITIONS OF CRANK DINSCONNECT SELECTION.............................................46
9PARAMETERS SETTING...............................................................................47
10 SENSORS SETTING.......................................................................................48
11 COMMISSIONING...........................................................................................49

HGM9510 GENSET PARALLEL UNIT
HGM9510 Genset Parallel Unit ISSUE 2013-08-06 Version 1.1Page 4 of 65
11.1 STEP 1.SINGLE UNIT DEBUGGING............................................................................49
11.2 STEP 2: MANUAL PARALLEL OPERATION OFF-LOAD..............................................49
11.3 STEP 3: MANUAL PARALLEL OPERATION ON-LOAD................................................49
11.4 STEP 4:AUTOMATIC PARALLEL OPERATION...........................................................50
12 TYPICAL APPLICATION................................................................................51
13 INSTALLATION ..............................................................................................55
14 CONNECTIONS OF CONTROLLER WITH J1939 ENGINE ...........................57
14.1 CUMMINS ISB/ISBE......................................................................................................57
14.2 CUMMINS QSL9 ...........................................................................................................57
14.3 CUMMINS QSM11(IMPORT)........................................................................................58
14.4 CUMMINS QSX15-CM570 ............................................................................................58
14.5 CUMMINS GCS-MODBUS............................................................................................58
14.6 CUMMINS QSM11 ........................................................................................................59
14.7 CUMMINS QSZ13.........................................................................................................59
14.8 DETROIT DIESEL DDEC III /IV.....................................................................................59
14.9 DEUTZ EMR2................................................................................................................60
14.10 JOHN DEERE................................................................................................................60
14.11 MTU MDEC ...................................................................................................................60
14.12 MTU ADEC(SMART MODULE).....................................................................................61
14.13 MTU ADEC(SAM MODULE)..........................................................................................61
14.14 PERKINS.......................................................................................................................61
14.15 SCANIA.........................................................................................................................62
14.16 VOLVO EDC3................................................................................................................62
14.17 VOLVO EDC4................................................................................................................62
14.18 VOLVO-EMS2...............................................................................................................63
14.19 YUCHAI.........................................................................................................................63
14.20 WEICHAI.......................................................................................................................63
15 USB.................................................................................................................64
16 FAULT FINDING.............................................................................................65

HGM9510 GENSET PARALLEL UNIT
HGM9510 Genset Parallel Unit ISSUE 2013-08-06 Version 1.1Page 5 of 65
1 OVERVIEW
HGM9510 controller is designed for manual/auto parallel system generators with similar or
different capacity. Additionally, it is suitable for single unit constant power output and mains
paralleling. It allows automatic start/stop, parallel running, data measurement, alarm protection as
well as remote control, remote measurement and remote communication function. It fit with LCD
display, optional Chinese, English and other languages interface, and it is reliable and easy to
use.
Utilizing the GOV (Engine Speed Governor) and AVR (Automatic Voltage Regulator) control
function, the controller is able to synchronize and share load automatically; it can be used to
parallel with other HGM9510 controller.
HGM9510 controller also monitors the engine, indicating the operational status and fault
conditions accurately. When abnormal condition occurs, it splits bus and shuts down the genset,
simultaneously the exact failure mode information is indicated by the LCD display on the front
panel. SAE J1939 interface enables the controller to communicate with various ECU (ENGINE
CONTROL UNIT) which fitted with J1939 interface.
The powerful 32-bit Microprocessor contained within the module allows for precision parameters
measuring, fixed value adjustment, time setting and set value adjusting and etc..Majority
parameters can be configured from front panel, and all parameters can be configured by USB
interface (or RS485) to adjust via PC. It can be widely used in all types of automatic gen-set
control system with compact structure, advanced circuits, simple connections and high reliability.

HGM9510 GENSET PARALLEL UNIT
HGM9510 Genset Parallel Unit ISSUE 2013-08-06 Version 1.1Page 6 of 65
2 MODULES COMPARISON
HGM
9210
HGM
9220
HGM
9310
HGM
9320
HGM
9410
HGM
9420
HGM
9610
HGM
9620
HGM
9510
HGM
9520
LCD
Dimension
3.7”
4.3”
pixel
132 x 64
480 x 272
AMF
●
●
●
●
●
BUS Monitoring
●
Parallel connection
●
●
Expansion module
●
●
Input Port
7
7
7
7
7
7
8
8
7
7
Output Port
8
8
8
8
8
8
8
8
8
8
Sensor Number
5
5
5
5
5
5
5
5
5
5
Neutral (Earth)
current
●
●
Schedule function
●
●
●
●
●
●
●
●
●
●
ETHERNET
●
●
RS485
●
●
●
●
●
●
●
●
GSM
●
●
●
●
●
●
J1939
●
●
●
●
●
●
USB
●
●
●
●
●
●
●
●
●
●
LINK
●
●
Real-time clock
●
●
●
●
●
●
●
●
●
●
Event log
●
●
●
●
●
●
●
●
●
●
Micro SD card
●
●
NOTE:
(1) Two of the outputs are fixed: start output and fuel output.
(2)HGM9510’s analog sensors are composed by 3 fixed sensors (temperature, pressure, level)
and 2 configurable sensors.
NOTE: The features of HGM9210/HGM9220/HGM9310/HGM9320/HGM9410/
HGM9420/HGM9520/HGM9610/HGM9620 controllers mentioned in this document may change,
please check the corresponding user manual for accurate information.

HGM9510 GENSET PARALLEL UNIT
HGM9510 Genset Parallel Unit ISSUE 2013-08-06 Version 1.1Page 7 of 65
3 PERFORMANCE AND CHARACTERISTICS
With ARM-based 32-bit SCM, high integration of hardware and more reliable;
480x272 LCD with backlight, multilingual interface (including English, Chinese or other
languages) which can be chosen at the site, making commissioning convenient for factory
personnel;
Improved LCD wear-resistance and scratch resistance due to hard screen acrylic;
Silicon panel and pushbuttons for better operation in high/low temperature environment;
RS485 communication port enable remote control, remote measuring, remote communication
via ModBus protocol.
Fitted with CANBUS port and can communicate with J1939 genset. Not only can you
monitoring frequently-used data (such as water temperature, oil pressure, engine speed, fuel
consumption and so on) of ECU machine, but also control start, stop, raising speed and
speed droop via CANBUS port.
Suitable for 3-phase 4-wire, 3-phase 3-wire, single phase 2-wire, and 2-phase 3-wire systems
with voltage 120/240V and frequency 50/60Hz;
Collects and shows 3-phase voltage, current, power parameter and frequency of Bus/mains.
For Bus, controller has loss of phase and phase sequence wrong detection functions; For
generator, controller has over voltage, under voltage, over frequency, under frequency, over
current, over power, reverse power, loss of phase, phase sequence wrong detection
functions;
Synchronization parameters:Voltage Difference Between Bus and Mains, Frequency
Difference Between Bus and Mains, Phase Difference Between Bus and mains;
Multiple running modes in auto state: with load running, off load running, demand parallel
running;
Ramp on and ramp off function;
3 fixed sensors (temperature, oil pressure and liquid level);
2 configurable sensors can be set as sensor of temperature, oil pressure or fuel level;
More kinds of curves of temperature, oil pressure, fuel level can be used directly and users
can define the sensor curves by themselves;
Precision measure and display parameters about Engine,
Temp. (WT) °C/°F both be displayed
Oil pressure (OP) kPa/Psi/Bar all be displayed
Fuel level (FL) %(unit)
Speed (SPD) r/min(unit)
Battery Voltage (VB) V (unit)
Charger Voltage (VD) V (unit)
Hour count (HC) can accumulate Max. 65535 hours.

HGM9510 GENSET PARALLEL UNIT
HGM9510 Genset Parallel Unit ISSUE 2013-08-06 Version 1.1Page 8 of 65
Start times can accumulate Max. 65535 times
Protection: automatic start/stop of the gen-set, ATS(Auto Transfer Switch) control with perfect
fault indication and protection function;
All output ports are relay output;
Parameter setting: parameters can be modified and stored in internal EEPROM memory and
cannot be lost even in case of power outage; most of them can be adjusted using front panel
of the controller and all of them can be modified using PC via USB or RS485 ports;
Multiple crank disconnect conditions (speed sensor, oil pressure, generator frequency) are
optional;
Widely power supply range DC(8~35)V, suitable to different starting battery voltage
environment;
Event log, real-time clock, scheduled start & stop generator (can be set as start genset once a
day/week/month whether with load or not);
Accumulative total run time and total electric energy of A and B. Users can reset it as 0 and
re-accumulative the value which make convenience to users to count the total value as their
wish.
Can control engine heater, cooler and fuel pump.
With maintenance function. Actions (warning, trip and stop, shutdown) can be set when
maintenance time out;
All parameters used digital adjustment, instead of conventional analog modulation with
normal potentiometer, more reliability and stability;
IP55 waterproofness level can be achieved with the help of rubber-ring gasket between shell
and control panel.
Metal fixing clips enable perfect in high temperature environment;
Modular design, anti-flaming ABS plastic shell, pluggable terminal, built-in mounting,compact
structure with easy installation;

HGM9510 GENSET PARALLEL UNIT
HGM9510 Genset Parallel Unit ISSUE 2013-08-06 Version 1.1Page 9 of 65
4 SPECIFICATION
Parameter
Details
Working Voltage
DC8. 0V to 35. 0V, uninterruptible power supply
Overall Consumption
<4W (Standby mode: ≤2W)
AC Input:
3 Phase 4 Wire
3 Phase 3 Wire
Single Phase 2 Wire
2 Phase 3 Wire
AC 15V - 360V (ph-N)
AC 30V - 620V (ph- ph)
AC 15V - 360V (ph-N)
AC 15V - 360V (ph-N)
Alternator Frequency
50Hz/60Hz
Speed Sensor Voltage
1. 0 V to 24 V (RMS)
Speed Sensor Frequency
Maximum 10,000 Hz
Start Relay Output
16A DC28V power supply output
Fuel Relay Output
16A DC28V power supply output
Flexible Relay Output 1
7A DC28V power supply output
Flexible Relay Output 2
7A DC28V power supply output
Flexible Relay Output 3
7A DC28V power supply output
Flexible Relay Output 4
7A 250VAC passive output
Flexible Relay Output 5
7A 250VAC passive output
Flexible Relay Output 6
7A 250VAC passive output
Case Dimensions
266mm x 182mm x 45mm
Panel Cutout
214mm x 160mm
CT Secondary Current
Rated 5A
Working Conditions
Temperature: (-25~+70)°C Humidity: (20~93)%RH
Storage Conditions
Temperature:(-30~+80)°C
Protection Level
IP55 Gasket
Insulation Intensity
Apply AC2.2kV voltage between high voltage terminal and low
voltage terminal;
The leakage current is not more than 3mA within 1min.
Weight
0.95kg

HGM9510 GENSET PARALLEL UNIT
HGM9510 Genset Parallel Unit ISSUE 2013-08-06 Version 1.1Page 10 of 65
5 OPERATION
5.1INDICATOR LIGHT
NOTE: Selected light indicators description:
Warning indicator and Alarm indicator:
Alarm Type
Warning Indicator
Alarm Indicator
Warning
Slow flashing
Slow flashing
Trip Alarm
Slow flashing
Slow flashing
Shutdown Alarm
Off
Fast flashing
Trip and Stop Alarm
Off
Fast flashing
Running indicator: illuminated from crank disconnect to ETS while off during other periods.
Genenerator normal light:It is light on when generator is normal; flashing when generator state is
abnormal; off when there is no generator power.
5.2 PUSHBUTTONS
Stop
Stop running generator in Auto/Manual mode; Lamp test
(press at least 3 seconds); Reset alarm in stop mode;
During stopping process, press this button again to stop
generator immediately.
Start
Start genset in Manual mode.
Manual Mode
Press this key and controller enters in Manual mode.
Auto Mode
Press this key and controller enters in Auto mode.

HGM9510 GENSET PARALLEL UNIT
HGM9510 Genset Parallel Unit ISSUE 2013-08-06 Version 1.1Page 11 of 65
Mute/Reset
Alarm
Alarming sound off; If trip alarm occurs, pressing the button
at least 3 seconds can reset this alarm.
Close
Close breaker in manual mode.
Open
Open breaker in manual mode.
Up/Increase
1) Screen scroll;
2) Up cursor and increase value in setting menu.
Down/Decrease
1) Screen scroll;
2) Down cursor and decrease value in setting menu.
Left
1) Screen scroll;
2) Left move cursor in setting menu.
Right
1) Screen scroll;
2) Right move cursor in setting menu.
Set/Confirm
Select viewing area.
Exit
1)Return to main menu;
2) Return to previous menu in setting menu.
NOTE: Press and simultaneously in manual mode will force generator to
crank. Successful start will not be judged according to crank disconnect conditions, operator will
have to crank the starter motor manually; when operator decides that the engine has fired, he/she
should release the button and start output will be deactivated, safety on delay will be initiated.
WARNING: Default password is 00318, user can change it in case of others change the
advanced parameters setting. Please clearly remember the password after changing. If you forget
it, please contact Smartgen services and send all information in the controller page of “ABOUT” to
us.
5.3LCD DISPLAY
5.3.1 MAIN DISPLAY
Main screen show pages; use to scroll the pages and to scroll the screen.
★Main Screen, including as below,
Gen: voltage, frequency, current, active power, reactive power
Bus: voltage, frequency
Engine: speed, temperature, oil pressure
Some status
★Status, including as below,

HGM9510 GENSET PARALLEL UNIT
HGM9510 Genset Parallel Unit ISSUE 2013-08-06 Version 1.1Page 12 of 65
Status of genset and ATS
★Engine, including as below,
Engine speed, engine temperature, engine oil pressure, fuel level, flexible sensor 1, flexible
sensor 2, battery voltage, charger voltage, engine accumulated run, accumulated start times.
NOTE: If connected with J1939 engine via CANBUS port, this page also includes: coolant
pressure, coolant level, fuel temperature, fuel pressure, inlet temperature, exhaust temperature,
turbo pressure, total fuel consumption and so on. (Different engine with different parameters)
★Generator, including as below,
Phase voltage, line voltage, frequency, phase sequence, current, Active Power(positive and
negative), total active power (positive and negative), Reactive Power(positive and negative), total
reactive power (positive and negative), Apparent Power, total apparent power, Power
Factor(positive and negative), average power factor (positive and negative), accumulated
energy (kWh, kVarh, kVAh), multi power, earth current, negative sequence current.
NOTE: Power factor shows as following,
Remark:
P stands for active power
Q stands for inactive power
Note:
1. Input active power, generator send active power to load.
2. Output active power, load supply electricity to generator.
3. Input reactive power, generator send reactive power to load.
4. Output reactive power, load send reactive power to generator.
★Bus, including as below,
Phase voltage, line voltage, frequency, phase sequence
★SNYC, including as below,
Power
factor
Conditions
Active
power
Reactive
power
Remark
COS>0L
P>0,Q>0
Input
Input
Load is inductive resistance.
COS>0C
P>0,Q<0
Input
Output
Load is capacitance resistance.
COS<0L
P<0,Q>0
Output
Input
Load is equal to one under excitation
generator.
COS<0C
P<0,Q<0
Output
Output
Load is equal to one over excitation
generator.

HGM9510 GENSET PARALLEL UNIT
HGM9510 Genset Parallel Unit ISSUE 2013-08-06 Version 1.1Page 13 of 65
Volt difference, freq difference, angle difference, active power percentage, target active power
percentage, reactive power percentage, target reactive power percentage, GOV percentage, AVR
percentage and MSC status
★Alarm:
NOTE: For ECU alarms and shutdown alarms, if the alarm information is displayed, check
engine according to it, otherwise, please check the generator manual according to SPN alarm
code.
★Event log
Make records about all start/stop events (shutdown alarm, trip and stop alarm, manual /auto start
or stop) and the real time when alarm occurs.
★Others, including,
Time and Date, maintenance due, input/output ports status.
★About, including,
Issue time of software and hardware version, product PD number.
5.3.2 USER MENU AND PARAMETERS SETTING MENU
Press key for more than 3s to enter into user manual.
★Parameter
After entering the correct password (factory default password is 00318) you can enter parameter
settings screen.
★Language
Selectable Chinese, English and others (default: Espanol)
★Commissioning
On load, off load or custom commissioning can be chosen. Custom commissioning can configure
on load or not during commissioning, when to commissioning and select the mode after
commissioning (manual mode, auto mode and stop mode).
★Clear users’ accumulation
Can clear total run time A and B, total electric energy A and B.
Parameter setting including as following,
★Timer settings
★Engine settings
★Generator settings
★Load settings
★Breaker settings
★Analog sensor settings
★Input port settings
★output port settings
★Module settings

HGM9510 GENSET PARALLEL UNIT
HGM9510 Genset Parallel Unit ISSUE 2013-08-06 Version 1.1Page 14 of 65
★Scheduling and maintenance settings
★Synchronization settings
Return
>Start Delay
>Return Delay
>Preheat Delay
>Cranking Time
>Crank Rest Time
>Safety On Time
>Start Idle Time
>Warming Up Time
>Cooling Time
>Stop Idle Time
>ETS Hold Time
Form1: Use to scroll settings,
to enter settings (form 2), to exit
settings menu.
Timers >
Engine
Generator
Load
Breaker
Temp. Sensor
OP Sensor
Level Sensor
Config Sensor 1
Config Sensor 2
Return
> Start Delay
Form 2: Use to scroll settings,
to enter settings (form 4), to return to
previous menu. (form 1)
Timers >
> Return Delay
> Preheat Delay
> Cranking Time
> Crank Rest Time
> Safety On Time
> Start Idle Time
> Warming Up Time
> Cooling Time
> Stop Idle Time
> ETS Hold Time
Engine
Generator
Load
Breaker
Temp. Sensor
OP Sensor
Level Sensor
Config Sensor 1
Config Sensor 2
Return
> Start Delay
> Return Delay
> Preheat Delay
Form 3: Use to scroll settings,
to enter settings (form 4), to return to
previous menu. (form 1)
Timers >
Engine
Generator
Load
Breaker
Temp. Sensor
OP Sensor
Level Sensor
Config Sensor 1
Config Sensor 2
> Cranking Time
> Crank Rest Time
> Safety On Time
> Start Idle Time
>Warming Up Time
> Cooling Time
> Stop Idle Time
> ETS Hold Time

HGM9510 GENSET PARALLEL UNIT
HGM9510 Genset Parallel Unit ISSUE 2013-08-06 Version 1.1Page 15 of 65
> Start Delay
> Return Delay
> Preheat Delay
00008
Form 4:Press to enter settings (form
5), to return to previous menu. (form 6).
>Cranking Time
>Crank Rest Time
> Safety On Time
> Start Idle Time
> Warming Up Time
> Cooling Time
> Stop Idle Time
> ETS Hold Time
> Start Delay
> Return Delay
> Preheat Delay
00008
Form 5: Press to change cursor
position, are used for changing
cursor value, Confirm setting (form 4),
exit setting (form 4).
>Cranking Time
> Crank Rest Time
> Safety On Time
> Start Idle Time
> Warming Up Time
> Cooling Time
> Stop Idle Time
> ETS Hold Time
> Start Delay
> Return Delay
> Preheat Delay
00008
Form 6: are used for changing the
setting contents. Confirm setting (form
4), to return to previous menu. (form 1).
>Cranking Time
> Crank Rest Time
> Safety On Time
> Start Idle Time
> Warming Up Time
> Cooling Time
> Stop Idle Time
> ETS Hold Time
>Wait For Stop
NOTE: Pressing can exit setting directly during setting.

HGM9510 GENSET PARALLEL UNIT
HGM9510 Genset Parallel Unit ISSUE 2013-08-06 Version 1.1Page 16 of 65
5.4AUTO START/STOP OPERATION
Auto mode is selected by pressing the button; a LED besides the button will illuminate to
confirm the operation.
Automatic Start Sequence:
1. When “Remote Start” is active, “Start Delay” timer is initiated;
2. “Start Delay” countdown will be displayed on LCD;
3. When start delay is over, preheat relay energizes (if configured), “preheat delay XX s”
information will be displayed on LCD;
4. After the above delay, the Fuel Relay (if configured) is energized, and then one second later,
the Start Relay is engaged. The engine is cranked for a pre-set time. If the engine fails to fire
during this cranking attempt then the fuel relay and start relay are disengaged for the pre-set
rest period; “crank rest time” begins and wait for the next crank attempt.
5. Should this start sequence continue beyond the set number of attempts, the start sequence
will be terminated, the first line of LCD display will be highlighted with black and Fail to Start
fault will be displayed.
6. In case of successful crank attempt, the “Safety On” timer is activated, allowing Low Oil
Pressure, High Temperature, Under speed and Charge Alternator Failure inputs to stabilise
without triggering the fault. As soon as this delay is over, “start idle” delay is initiated (if
configured).
7. During “start idle” delay, under speed, under frequency, under voltage alarms are inhibited.
When this delay is over, “warming up” delay is initiated (if configured).
8. In the case of a single generator system, after the “warming up” delay, if generator status is
normal, its indicator will be illuminated. If generator voltage and frequency have reached
on-load requirements, then the generator close relay will be energized; genset will take load;
generator power indicator will illuminate and generator will enter into Normal Running status.
If voltage or frequency is abnormal, the controller will initiate shutdown alarm (alarm
information will be displayed on LCD).
9. In case of running in parallel, after the warming up delay:
a) If bus has no voltage, then the controller will send a closing signal to other waiting parallel
gensets and generator close relay will activate, this prevents other sets in the system from
attempting to close their own breakers at the same time.
b) If bus has voltage or other gensets are already closed, the controller will adjust speed and
voltage through GOV and AVR to synchronize the gensets to the bus; when synchronism
requirements has been achieved, breaker close signal will be initiated and the genset will be
paralleled with the bus. Once they are paralleled, the controller will control the generator to
gradually accelerate and share load with other paralleled gensets.

HGM9510 GENSET PARALLEL UNIT
HGM9510 Genset Parallel Unit ISSUE 2013-08-06 Version 1.1Page 17 of 65
Note: When started via “Remote Start (off Load)” input, same procedures as above but
generator close relay deactivated, moreover, genset off load. When started via “Remote Start
(Demand)” input,the genset will start, synchronization, parallel and load sharing automatically
according to the pre-set priority order.
Automatic Stop Sequence,
1) When the “Remote Start” signal is removed, the Stop Delay is initiated.
2) Once this “stop delay” has expired, the module will ramp the load from the generator to
remaining set. The Generator Breaker will open and the “Cooling Delay” is then initiated.
Should the Remote Start signal be re-activated during the cooling down period, the set will
return parallel status. Once the “Cooling Delay” expires, the “Stop Idle” delay is initiated.
3) During “Stop Idle” Delay (if configured), idle relay is energized.
4) “ETS Solenoid Hold” begins, ETS relay is energized while fuel relay is de-energized, complete
stop is detected automatically.
5) "Fail to Stop Delay" begins, complete stop is detected automatically.
6) When generator is stop completely, “After stop” delay will be initiated. Otherwise, fail to stop
alarm is initiated and the corresponding alarm information is displayed on LCD. ( If generator
is stop successfully after “fail to stop” alarm has initiated, “After stop” delay will be initiated and
the alarm will be removed)
7) Generator is placed into its standby mode after its “After stop” delay.
5.5MANUAL START/STOP OPERATION
1. Manual mode is selected by pressing the button; a LED besides the button will illuminate
to confirm the operation; then press button to start the gen-set; can detect crank
disconnect condition and generator accelerates to high-speed running automatically. With
high temperature, low oil pressure, over speed and abnormal voltage during generator
running, controller can protect genset to stop quickly (please refer to No.3~9 of Automatic
Start Sequence for detail procedures).
2. MANUAL STOP: Press can shuts down the running generators. (Please refer to
No.2~7 of Automatic Start Sequence for detail procedures).
NOTE: In “manual mode”, the procedures of ATS please refer to Switch Control Procedure of
generator in this manual.
5.6SWITCH CONTROL PROCEDURES
5.6.1 MANUAL TRANSFER PROCEDURES
When controller is in Manual mode, the switch control procedures will start through manual
transfer procedures. Users can control the loading transfer of ATS via pressing button to switch
on or off.

HGM9510 GENSET PARALLEL UNIT
HGM9510 Genset Parallel Unit ISSUE 2013-08-06 Version 1.1Page 18 of 65
Closing Operation:During genset normal running, press if generator voltage and frequency
have reached on-load requirements
1) In case of single unit running, generator closing relay outputs;
2) In case of running in parallel:
a) If bus has no voltage, then the controller will send a closing signal to other waiting parallel
gensets and generator close relay will activate, this prevents other sets in the system from
attempting to close their own breakers at the same time.
b) If bus has voltage or other gensets are already closed, the controller will adjust speed and
voltage through GOV and AVR to synchronize the gensets to the bus; when synchronism
requirements has been achieved, breaker close signal will be initiated and the genset will be
paralleled to the bus. Once they are paralleled, the controller will control the generator to
gradually accelerate and share load with other paralleled gensets.
Opening operation:Press ,
1) In case of single unit running, the controller sends open breaker signal.
2) During parallel operation, if button is pressed, first of all, the controller will transfer load
to other generators, and only then send an opening signal.
5.6.2 AUTOMATIC CONTROL PROCEDURE
When controller is in auto mode, the switch control procedure is automatic control procedure.
Note:The auxiliary close input should be configured necessarily and make sure the
connection is correct.

HGM9510 GENSET PARALLEL UNIT
HGM9510 Genset Parallel Unit ISSUE 2013-08-06 Version 1.1Page 19 of 65
6 PROTECTIONS
6.1WARNING ALARMS
Warnings are not shutdown alarms and do not affect the operation of the gen-set. Warning alarms
does not lead to shutdown. Warning alarms types are as follows:
No
Type
Description
1
Over Speed
When the controller detects that the engine speed has exceeded
the pre-set value, it will initiate a warning alarm.
2
Under Speed
When the controller detects that the engine speed has fallen
below the pre-set value, it will initiate a warning alarm.
3
Loss of Speed Signal
When the controller detects that the engine speed is 0 and the
action select “Warn”, it will initiate a warning alarm.
4
Gen Over Frequency
When the controller detects that the genset frequency has
exceeded the pre-set value, it will initiate a warning alarm.
5
Gen Under
Frequency
When the controller detects that the genset frequency has fallen
below the pre-set value, it will initiate a warning alarm.
6
Gen Over Voltage
When the controller detects that the generator voltage has
exceeded the pre-set value, the controller will initiate a warning
alarm.
7
Genset Under
Voltage
When the controller detects that the genset voltage has fallen
below the pre-set value, it will initiate a warning alarm.
8
Gen Over Current
When the controller detects that the genset current has exceeded
the pre-set value and the action select “Warn”, it will initiate a
warning alarm.
9
Fail To Stop
After “fail to stop” delay, if gen-set does not stop completely, it will
initiate a warning alarm.
10
Charge Alternator
Failure
When the controller detects that charger voltage has fallen below
the pre-set value, it will initiate a warning alarm.
11
Battery Under Volt
When the controller detects that start battery voltage has fallen
below the pre-set value, it will initiate a warning alarm.
12
Battery Over Volt
When the controller detects that start battery voltage has
exceeded the pre-set value, it will initiate a warning alarm.
13
Maintenance Due
When count down time is 0 and the action select “Warn”, it will
initiate a warning alarm.
14
Reverse Power
If reverse power detection is enabled, when the controller detects
that the reverse power value (power is negative) has fallen below
the pre-set value and the action select “Warn”, it will initiate a
warning alarm.
15
Over Power
If over power detection is enabled, when the controller detects that
the over power value (power is positive) has exceeded the pre-set
value and the action select “Warn”, it will initiate a warning alarm.
16
ECU Warn
If an error message is received from ECU via J1939, it will initiate
a warning alarm.
17
Gen Loss of Phase
If loss of phase detection is enabled, When controller detects the
generator loss phase, it will initiate a warning alarm.
18
Gen Phase
Sequence Wrong
When the controller detects a phase rotation error, it will initiate a
warning alarm.

HGM9510 GENSET PARALLEL UNIT
HGM9510 Genset Parallel Unit ISSUE 2013-08-06 Version 1.1Page 20 of 65
No
Type
Description
19
Switch Fail Warn
When the controller detects that the breaker close or open failure
occurs, and the action select “Warn”, it will initiate a warning
alarm.
20
Temperature Sensor
Open Circuit
When the controller detects that the temperature sensor is open
circuit and the action select “Warn”, it will initiate a warning alarm.
21
High Temperature
When the controller detects that engine temperature has
exceeded the pre-set value, it will initiate a warning alarm.
22
Low Temperature
When the controller detects that engine temperature has fallen
below the pre-set value, it will initiate a warning alarm.
23
Oil Pressure Open
Circuit
When the controller detects that the oil pressure sensor is open
circuit and the action select “Warn”, it will initiate a warning alarm.
24
Low Oil Pressure
When the controller detects that the oil pressure has fallen below
the pre-set value, it will initiate a warning alarm.
25
Level Sensor Open
Circuit
When the controller detects that the level sensor is open circuit
and the action select “Warn”, it will initiate a warning alarm.
26
Low Fuel Level
When the controller detects that the fuel level has fallen below the
pre-set value, it will initiate a warning alarm.
27
Flexible Sensor 1
Open Circuit
When the controller detects that the flexible sensor 1 is open
circuit and the action select “Warn”, it will initiate a warning alarm.
28
Flexible Sensor 1
High
When the controller detects that the sensor 1 value has exceeded
the pre-set value, it will initiate a warning alarm.
29
Flexible Sensor 1
Low
When the controller detects that the sensor 1 value has fallen
below the pre-set value, it will initiate a warning alarm.
30
Flexible Sensor 2
Open Circuit
When the controller detects that the flexible sensor 2 is open
circuit and the action select “Warn”, it will initiate a warning alarm.
31
Flexible Sensor 2
High
When the controller detects that the sensor 2 value has exceeded
the pre-set value, it will initiate a warning alarm.
32
Flexible Sensor 2
Low
When the controller detects that the sensor 2 value has fallen
below the pre-set value, it will initiate a warning alarm.
33
Digital Input
When digit input port is set as warning and the alarm is active, it
will initiate a warning alarm.
34
Earth Fault
If earth fault detection is enabled, when the controller detects that
the earth fault current has exceeded the pre-set value and the
action select “Warn”, it will initiate a warning alarm.
35
Negative Sequence
Current
When the controller detects the imbalance current has exceeded
the pre-set value and the action select “Warn” it will initiate a
warning alarm.
36
Fail to sync
When the controller does not detect synchronization signal within
the pre-set synchronization time, it will initiate a warning alarm.
37
MSC Too Few Sets
When the controller detects fewer modules on the MSC link than
the minimum number configured in the unit, it will initiate a warning
alarm. There are 2 possible reasons: a) Communication line
between the controllers disconnects, which interrupts
communication.
b) Other parallel gen-sets controllers have not been powered on.
38
Loss of Excitation
When the controller detects that the genset negative reactive
power has exceeded the pre-set value, it will initiate a warning
alarm.
Other manuals for HGM9510
2
Table of contents
Other Smartgen GSM/GPRS Module manuals