Smarti DIS-4X-INTAS User manual

Page 1of 19
Door Interlock Systems
Installation & Operation Manual
(DIS-4X-INTAS; DIS-4SV-INTAS; DIS-2X-INTAS)
Door Interlock Systems revised Ver. 2.0
On date 31 Jan 2019
Due to continuous technology up-gradation, product specifications and features are
subject to change without notice at any time.
It is Smart I’s goal to supply accurate and reliable documentation. If you discover a
discrepancy in this document or Need Help, please e-mail your comments to
support@smartisystems.com

Page 2of 19
TABLE OF CONTENT
WARNING & CAUTION ___________________________________________ 3
INTRODUCTION ________________________________________________ 4
PRODUCT FEATURE ____________________________________________ 4
PRODUCT SPECIFICATION _______________________________________ 5
BLOCK DIAGRAM FOR 2 DOORS DIS ______________________________ 6
BLOCK DIAGRAM FOR 4 DOORS DIS ______________________________ 7
GENERAL ARRANGEMENT DIAGRAM OF SYSTEM FOR 4DIS SYSTEM __ 8
MASTER 2-DIS BOARD CONNECTION DETAILS ______________________ 9
MASTER 4-DIS MASTER BOARD CONNECTION DETAILS _____________ 10
SLAVE 4-DIS SLAVE BOARD CONNECTION DETAILS ________________ 11
4 DIS PCB CONNECTOR DETAILS ________________________________ 12
4 DIS PCB LED DETAILS ________________________________________ 14
DIS-FP1-ALEMBIC CONNECTION DETAILS _________________________ 16
DIS-FP1-ALEMBIC LED DETAILS _________________________________ 17
SYSTEM OPERATION___________________________________________ 18
KEYPAD FUNCTION DETAILS FOR 4 DIS SYSTEM ___________________ 18
DIS INTEGRATION WITH ACCESS CONTROLLER SYSTEM____________ 19

Page 3of 19
WARNING & CAUTION
∅Do not open system or places it near other heavy electrical equipments. The
system is sensitive to Electro Static Discharge (ESD)
∅Do not power on the system without reading this manual. Ensure proper power
supply with Earthing.
∅Note down the serial number and model no. of the device for future reference
and quote in all support and service requests.
∅Mounting the unit in strong sunlight may affect user visibility of the LCD. Ensure
that the LCD and LED’s are clearly visible in all lighting conditions.
∅Do not use this unit near water.
∅Never insert objects of any kind into the unit or through the cabinet slots as they
may touch voltage points and/or short circuit parts possibly resulting in fire or
electric shock. Never spill liquid of any kind on the unit.
∅Power up the controller only when installation is complete.
Important instructions
1. Care should be taken identifying the wires. Improper wiring may render
permanent damage to the device or personal injury.
2. Check the earthing at the site before installing the controllers. Normally the
earthing should be between 1V to 2V only. Earthing on the higher side may
damage the controller or its various other components.
3. Max allowable cable distance between 4- Door Master DIS & Slave DIS is up
to 1.5 mtr to 2 mtr.
4. The door which is not in use Magnetic Contacts (MC+ and MC-) should be
short circuited using wire for proper functioning of DIS Board.

Page 4of 19
Introduction
DIS is designed and manufactured state-of-the-art door interlock/access systems for
clean rooms, containment suites, laboratories - in fact any critical area that requires door
access control with additional security.
DIS has Master-Slave Configuration and can be configured up to maximum 8 doors in
loop.
Product Feature
1. Programmable Micro controller based Door Interlock unit
2. One “4 - DIS Master” system can control up to 4 Doors
3. By adding “4-DIS Slave” system can control up to 8 Doors
4. Master & slave configuration. (Max. salves 1 no.)
Each Master & slave control 4 Doors in DIS (i.e. totally 8 Doors)
5. One time based Emergency / Fire input is used to open all doors automatically
on following events
•Fire input activated by alarm output of fire panel, connected to only at Master
unit
•Emergency input activated by user, using Emergency button connected to
only Master unit

Page 5of 19
Product Specification
A)
Specifications of 4 Door DIS MASTER
Type Microcontroller based 4 Door DIS system
Display & Keypad 16 X 2 Alphanumeric display & 12 Keys Keypad
using Pro Keypad (Used only in Programming Logic mode)
Outputs Potential free o/p X4 nos for Lock
Contact Rating : 0.5 amp for 230 V AC
1.0 amp for 24 V DC
Door LOCK LED indication X 4 nos
Door OPEN LED indication X 4 nos
DOTL Buzzer X 4nos
Inputs Total 9 Optically Isolated inputs
Magnetic contact X 4 nos
Fire / Emergency I/P X 1nos
Max. Slave Output One with Parallel Interface ( To make 8 door DIS)
Power supply 12V @ 5A
Dimensions in mm 390 mm (L) X 90 mm (W) X 320 mm (H)
Weight Approx 3kg
B)
Specifications of 4 Door DIS SLAVE
Type Digitally control based 4 Door DIS system
Outputs Potential free o/p X4 nos for Lock
Contact Rating
0.5 amp for 230 V AC
1.0 amp for 24 V DC
Door LOCK LED indication X 4 nos
Door OPEN LED indication X 4 nos
DOTL Buzzer X 4nos
Inputs Total 8 Optically Isolated inputs
Magnetic contact X 4 nos
Power supply 12V @ 5A
Dimensions in mm 390 mm (L) X 90 mm (W) X 320 mm (H)
Weight Approx 3kg

Page 6of 19
Block Diagram for 2 Doors DIS
System Requirement for 2 Doors
DIS Board : 1 No
Power Supply : 12VDC, @2A
Magnetic contact Switch : 2 No
Electro-magnetic Lock : 2 No

Page 7of 19
Block Diagram for 4 Doors DIS
System Requirement for 4 Doors
DIS Board : 1 No
Power Supply : 12VDC, @5A
Magnetic contact Switch : 4 No
Electro-magnetic Lock : 4 No

Page 8of 19
General Arrangement Diagram of system for 4DIS system
Cable Specification
Cable-A (Lock Cable) => 2 core cable (14/36; 22AWG) max 100 meter
Cable-B (MC Cable) => 2 core cable (14/36; 22AWG) max 100 meter

Page 9of 19
Master 2-DIS Board Connection Details
RL1 RL2
DOOR 1
DOOR 2
POWER
BZ
NC
P
NO
MC1+
MC1-
12V
G
LOCK
OPEN
EG1+
DOTL1
NC
P
NO
MC2+
MC2-
12V
G
LOCK
OPEN
EG2+
DOTL2
uc
12 V
GND
Tamper
JP1
JP23
J5
JP2
JP4
JP8
JP6
JP7
JP5
JP3
JP9
J1 J13 J9
J14
J10
J6
E+ E- EL+ EL-
J7
J8
FIRE
LD12 LD4
LD14 LD3 LD6
LD15
LD5

Page 10 of 19
Master 4-DIS Master Board Connection Details
RL1 RL2
RL4RL3
DOOR 1 DOOR 2
DOOR 3 DOOR 4
KEYPAD
POWER
MASTER
BZ
NC
P
NO
MC1+
MC1-
12V
G
LOCK
OPEN
EG1+
DOTL1
NC
P
NO
MC2+
MC2-
12V
G
LOCK
OPEN
EG2+
DOTL2
NC
P
NO
DOTL 4
EG4+
OPEN
LOCK
G
12 V
MC4-
NC
P
NO
DOTL 3
EG3+
OPEN
LOCK
G
12 V
MC3-
MC3+
uc
12 V
GND
Tamper
JP1
JP23
J5
JP2
JP4
JP8
JP6
JP7
JP5
JP3
JP9
J1 J13 J9
J14
J10
J2A
J6
J12
J16
J11
J15
E+ E- EL+ EL-
J7
J8
FIRE
LD12 LD4
LD14 LD3 LD6
LD15
LD5
LD9
LD7
LD8
LD16
LD10
LD17
MC4+

Page 11 of 19
Slave 4-DIS Slave Board Connection Details
RL1 RL2
RL4RL3
DOOR 5 DOOR 6
DOOR 7 DOOR 8
POWER
NC
P
NO
MC1+
MC1-
12V
G
LOCK
OPEN
EG1+
DOTL1
NC
P
NO
MC2+
MC2-
12V
G
LOCK
OPEN
EG2+
DOTL2
NC
P
NO
DOTL 4
EG4+
OPEN
LOCK
G
12 V
MC4-
NC
P
NO
DOTL 3
EG3+
OPEN
LOCK
G
12 V
MC3-
MC3+
12 V
GND
JP2
JP4
JP8
JP6
JP7
JP5
JP3
JP9
J13 J9
J14
J10
J12
J16
J11
J15
SLAVE
E+ E
-
EL+ EL
-
J7
J2
J8
FIRE
LD14 LD3 LD15
LD5
LD8
LD16
LD10
LD17
LD4
LD6
LD9
LD7
MC4+

Page 12 of 19
4 DIS PCB Connector Details
J1
Connection Details:
-
(Keypad and Display)
Pin No.
Description
1 to 16 KEYPAD and DISPLAY
J2 Connection Details:
-
(Slave)
Pin No.
Legend
Description
1 to 16 - FRC cable is connected here which comes
from Master board when we have to use it as
8-DIS.(Slave pin)
Max distance slave to master 1.5 to 2 meter.
J2A Connection Details:
-
(Master)
Pin No.
Legend
Description
1 to 16 - FRC cable is connected here which other end
is connected at Slave board when we have to
use it as 8-DIS.(Master pin)
J6
Connection Details:
-
(Tamper)
Pin No
Legend
Description
1 to 2 - TAMPER switch is Connection
J7 Connection Details:
-
(Fire)
Pin No.
Legend
Description
E+ Emergency Switch or Fire Button is
Connected or it is Short Circuited using wire
for Slave purpose.
E-
EL+
EL-
J8 Connection Details:
-
(Power Supply)
Pin No.
Legend
Description
1 VCC For Power Supply purpose. 12V @ 5A
2 GND

Page 13 of 19
J9 Connection Details:
-
(Door 1)
Pin No.
Legend
Description
1 MC1+ Connect to magnetic contact sensor or in
LOCK
2 MC1-
3 12V Connect to P of J13
4 GND Connect to –ve of EML lock.
5 Lock ----
6 Open ----
7 EG1+ ----
8 DOTL1 ----
J10 Connection Details:
-
(Door 2)
Pin No.
Legend
Description
1 MC2+ Connect to magnetic contact sensor or in
LOCK
2 MC2-
3 12V Connect to P of J14
4 GND Connect to –ve of EML lock.
5 Lock ----
6 Open ----
7 EG2+ ----
8 DOTL2 ----
J11 Connection Details:
-
(Door 3)
Pin No.
Legend
Description
1 MC3+ Connect to magnetic contact sensor or in
LOCK
2 MC3-
3 12V Connect to P of J15
4 GND Connect to –ve of EML lock.
5 Lock ----
6 Open ----
7 EG3+ ----
8 DOTL3 ----
J12 Connection Details:
-
(Door 4)
Pin No.
Legend
Description
1 MC4+ Connect to magnetic contact sensor or in
LOCK
2 MC4-
3 12V Connect to P of J16
4 GND Connect to –ve of EML lock.
5 Lock ----
6 Open ----
7 EG4+ ----
8 DOTL4 ----

Page 14 of 19
J13 Connection Details:
-
(Door 1)
Pin No.
Legend
Description
1 NC Potential free contacts of Relay1.
2 P
3 NO
J14 Connection Details:
-
(Door 2)
Pin No.
Legend
Description
1 NC Potential free contacts of Relay2.
2 P
3 NO
J15 Connection Details:
-
(Door 3)
Pin No.
Legend
Description
1 NO Potential free contacts of Relay3.
2 P
3 NC
J16 Connection Details:
-
(Door 4)
Pin No.
Legend
Description
1 NO Potential free contacts of Relay4.
2 P
3 NC
Note
Magnetic Contacts (MC+ and MC-) should be short circuited using wire when the door is
not in use for proper functioning of DIS Board.
Door 1, Door 2, Door 3 and Door4 will act as Door 5, Door 6, Door7 and Door 8
respectively when it is used as Slave Board.
4 DIS PCB LED Details
LED’S NUMBER
LABEL
FUNCTION
DESCRIPTION
LD14,LD15,
LD16,LD17
LOCK
Led’s
Door 1, 2, 3, 4
close
Normally off when any other door open
then it turns to green
LD4,LD6,
LD8,LD10
Magnetic
contact
Door 1, 2, 3, 4
Open
Magnetic contact present = Red
LD11 FIRE FIRE Normally OFF, When Fire Activated
then it turns to Red
LD12 12V Power Indication Continuous On
For trouble shouting you can check this LED’s indications on DIS board.

Page 15 of 19
DOOR CONNECTION FOR EML LOCK
-
DOOR CONNECTION FOR STRIKE LOCK
Door Connection for Magnetic Contact:-
DOTL
EG+
OPEN
LOCK
G
12 V
MC-
MC+
Magnetic Contact
DOTL1
EG
OPEN
LOCK
GND
12 V
MC-
MC+
NO
P
NC
EML LOCK
+
NO
P
NC
STRIKE
LOCK
+
-
DOTL1
EG
OPEN
LOCK
GND
12 V
MC-
MC+

Page 16 of 19
DIS-FP1-Alembic Connection Details
Front side of DIS-FP1-Alembic
Back side of DIS-FP1-Alembic
6 Pin Connector Details of DIS-FP1-Alembic
J1 Pin No. Pin Details Wire color
1 12V Green
2 GND Yellow
3 Door LOCK
LED
Orange
4 Door Open
LED
Red
5 Exit switch Brown
6 DOTL Buzzer Black
LOCK
OPEN

Page 17 of 19
DIS-FP1-Alembic connection with 4 Door DIS Board
DIS-FP1-Alembic LED Details
LOCK LED
OPEN LED
DESCRIPTION
OFF GREEN Normal Mode or Door is open
RED RED Door is locked
Facia Relimate Plate Connector To 4 Door DIS Board Door-1 to Door-4
J1 Pin
No.
Pin Details Wire color Facia Pin
No.
Pin Details Wire
color
1 12V Green 1 12V Green
2 GND Yellow 2 GND Yellow
3 Door LOCK
LED
Orange 3 LOCK Orange
4 Door Open
LED
Red 4 Open Red
5 Exit switch Brown 5 EG Brown
6 DOTL Buzzer Black 6 DOTL Black
Door Interlock System is designed for door interlocking requirements. The system
consists of one Master & one slave connected parallel to control total 8 Doors. Each
Master & slave controls 4 doors.
Operation: For normal condition all doors are unlock(i.e. Lock is not energized, but door
is closed indicated by Magnetic contact of door).When we open any one door then
remaining doors are get locked. For Emergency exits then all doors are get open with
emergency alarm.
System Operation

Page 20 of 23
Keypad Function Details for 4 DIS system
Sr.
No.
Function How to go? Note Default Value
1 Normal Mode Key- *0
2 Admin Mode Key- *2
Enter User ID(11111)
Press # key
Enter Password(12345)
Press # Key
To come out from Admin
mode press
Key – *2
Key – #
(Auto logoff after 60sec)
3 Select Mode Key- *3
Press- 1 for Default logic
Press- 2 for User logic
We can select any one of the
logic, depending upon used of
it.
4 Configure Door Key- *4
Press- 1 for not allowing
other door to be used
simultaneously.
Press- 0 for allowing other
door to be used
simultaneously.
Press- # to enter
We can configure 4 or 8 door,
depending upon the units
configuration
Refer
Annexure:1
5 Fire Tamper Key- *5
Press-0 for Disable Fire-
Tamper
Press-1 for Enable Fire
Press-2 for Enable Tamper
Press-3 for Enable Fire-
Tamper
Press -# to enter
1 : Enable fire
6 Help Menu Key – *8
Press – 1 for INC
Press – 3 for DEC
Press – # to enter
We can directly go in to any
menu by pressing “#” key.
7 Initialize System Key – *90
Press – 1 for Yes
Press – 3 for No
Press– # to enter
It initializes the system.
All data will deleted
8
Emergency
Door open time
Key – *94
Enter required door open
time
Key – #
Emergency Door open time
can be set 1 to 900 sec.(15
Minutes) If it is set to 0 then in
emergency all doors remains
open till restart the system or
press emergency button again.
0 secs
9
Door open time Key – *95
Enter door open time
Key – #
Door open time can be set
1 to 98 sec. And DOTL sense
time is equal to Door open
time + 1 sec.
5 secs
10
Switch press
time
Key – *96
Enter egress switch press
time
Key – #
Egress switch press time can
be set 1 to 98 sec. 5 secs
Emergency
Buzzer time
11
Key – *93
Enter required EMRBuzz time
Key – #
0 secs
Emergency buzzer time can
be set 1 to 255 sec.

Page 21of 23
Annexure: 1 (*4 menu)
0 = Door Open by Egress (Indication by OPEN LED) on latch.
1 = Door Locked (Indication by LOCK LED) on latch
*= Door programming
Door1 Door2 Door3 Door4 Door5 Door6 Door7 Door8
1 * 1 0 1 0 1 0 1
2 1 * 1 0 1 0 1 0
3 0 1 * 1 0 1 0 1
4 1 0 1 * 1 0 1 0
5 0 1 0 1 * 1 0 1
6 1 0 1 0 1 * 1 0
7 0 1 0 1 0 1 * 1
8 1 0 1 0 1 0 1 *
Emergency
Door open
Setting
Key – *97
Enter required
emergency door open
configuration
Key – #
Emergency door open Setting
Value = 0 - It will open only that single
particular door upon long press of
egress.
Emergency door open Setting
Value = 1 - It will open all doors
0 secs
12

Page 22 of 23
DIS Integration with Access Controller System
C1: Reader is connected to Access controller (as IN Reader).
C2: Potential free contact o/p of Lock from Access controller is
connected to egress I/P of DIS system.
C3: Lock output from DIS system is connected to Door Lock.
C4: Facia plate is connected to DIS system (as Egress switch for Exit).
C5: For Potential free contact O/P refer respective Access controller
installation Guide.
Connection DIS with Old Access Controller:-
DIS Door Connector
DIS Board Access
Controller
Door Lock
Facia
Plate
Exit
C1
C2
C3
C4
Reader
IN
DOTL
EG+
OPEN
LOCK
G
12 V
MC-
MC+
Door Connector
Access Controller
L-
L+
Potential free O/P
DOTL
EG+
OPEN
LOCK
G
12 V
MC-
MC+
This manual suits for next models
2
Table of contents
Popular Microcontroller manuals by other brands

FDI
FDI uEZGUI-4088-43WQN user manual

Microchip Technology
Microchip Technology DM164120-1 user guide

FDI
FDI ELI121-CRW quick start guide

Analog Devices
Analog Devices Linear Technology ADI Power DC3159A Demo Manual

Microsemi
Microsemi IGLOO2 FPGA DSP FIR Filter user guide

Murata
Murata DNT900DK quick start guide

Freescale Semiconductor
Freescale Semiconductor TWR-K21F120M quick start guide

Toshiba
Toshiba TXZ SERIES Reference manual

Texas Instruments
Texas Instruments MSP432P401R user guide

Logic PD
Logic PD Zoom Torpedo OMAP35 Series user manual

NXP Semiconductors
NXP Semiconductors MPC574xR Series Application note

MCpros
MCpros PIC-P40-28 user manual