S ANDARDS AND PROVISIONS: Standards, recommendations, regulations
and provisions of the country in which the devices will operate, must
be considered while planning and setting up electrical devices. Work
on 100 .. 240 V AC network is allowed for authorized personnel only.
DANGER WARNINGS: Devices or modules must be protected from
moisture, dirt and damage during transport, storing and operation.
WARRAN Y CONDI IONS: For all modules LONGO LPC-2 – if no
modifications are performed upon and are correctly connected by
authorized personnel – in consideration of maximum allowed
connecting power, warranty of 24 months is valid from the date of sale
to the end buyer, but not more than 36 months after delivery from
Smarteh. In case of claims within warranty time, which are based on
material malfunctions the producer offers free replacement. he
method of return of malfunctioned module, together with description,
can be arranged with our authorized representative. Warranty does
not include damage due to transport or because of unconsidered
corresponding regulations of the country, where the module is
installed.
his device must be connected properly by the provided connection
scheme in this manual. Misconnections may result in device damage,
fire or personal injury.
Hazardous voltage in the device can cause electric shock and may
result in personal injury or death.
NEVER SERVICE HIS PRODUC YOURSELF!
his device must not be installed in the systems critical for life (e.g.
medical devices, aircrafts, etc.).
If the device is used in a manner not specified by the manufacturer,
the degree of protection provided by the equipment may be impaired.
Waste electrical and electronic equipment (WEEE) must be collected
separately!
LONGO LPC-2 complies to the following standards:
•EMC: EN 61000-6-3:2007 + A1:2011, EN 61000-6-1:2007, EN 61000-
3-2:2006 + A1:2009 + A2: 2009, EN 61000-3-3:2013
•LVD: IEC 61010-1:2010 (3rd Ed.), IEC 61010-2-201:2013 (1st Ed.)
Smarteh d.o.o. operates a policy of continuous development.
herefore we reserve the right to make changes and improvements to
any of the products described in this manual without any prior notice.
MANUFAC URER:
SMAR EH d.o.o.
Poljubinj 114
5220 olmin
Slovenia
ii

Longo programmable controller LPC-2.DI6
Longo programmable controller LPC-2.D 6
1 DESCRIP ION...................................................................................1
2 FEA URES.......................................................................................2
3 INS ALLA ION..................................................................................3
3.1 Connection scheme....................................................................3
3.2 Mounting instructions.................................................................5
3.3 Module labeling........................................................................6
4 ECHNICAL SPECIFICA IONS..................................................................7
5 CHANGES .......................................................................................8
6 NO ES...........................................................................................9
iii

Longo programmable controller LPC-2.DI6
1 DESCR PT ON
LPC-2.DI6 is used as standard digital input module for eight connections to 24 V DC external sources.
Module is galvanic isolated from the rest of the LPC-2 system. It can be used in a wide range of
operation where sensors and devices connected to the LPC-2.DI6 module provide 24 V DC signals
required for inputs' activation.
LEDs indicate active signal present on each module input (refer to the able 6).
Module is powered from internal BUS.
NO E: For proper system configuration and data allocation please refer to LPC Composer software
help menu.
1

Longo programmable controller LPC-2.DI6
2 FEATURES
Figure 1: LPC-2.DI6 module.
Table 1: Technical data
Eight external 24 V DC digital inputs, galvanic isolated
Flexible input for wide use of operation
Standard DIN EN50022-35 rail mounting
2

Longo programmable controller LPC-2.DI6
3 NSTALLAT ON
3.1 Connection scheme
Figure 2: Connection scheme
Table 2: N1
IN1.1 (I+) Digital input in reference to IN1.2, 0..24 V DC 24 V DC digital input
IN1.2 (I-) Reference Reference to 24 V DC
IN2.3 (I+) Digital input in reference to IN2.4, 0..24 V DC 24 V DC digital input
IN2.4 (I-) Reference Reference to 24 V DC
IN3.5 (I+) Digital input in reference to IN3.6, 0..24 V DC 24 V DC digital input
IN3.6 (I-) Reference Reference to 24 V DC
IN4.7 (I+) Digital input in reference to IN4.8, 0..24 V DC 24 V DC digital input
IN4.8 (I-) Reference Reference to 24 V DC
1 Wires connected to the module must have cross sectional area at least 0.75 mm2. Minimum temperature rating of wire
insulation must be 85 °C.
3
K2
K1
LED1 - LED4
LED5 - LED8
24 V
+

Longo programmable controller LPC-2.DI6
Table 2: N
IN5.9 (I+) Digital input in reference to IN5.10, 0..24 V DC 24 V DC digital input
IN5.10 (I-) Reference Reference to 24 V DC
IN6.11 (I+) Digital input in reference to IN6.12, 0..24 V DC 24 V DC digital input
IN6.12 (I-) Reference Reference to 24 V DC
IN7.13 (I+) Digital input in reference to IN7.14, 0..24 V DC 24 V DC digital input
IN7.14 (I-) Reference Reference to 24 V DC
IN8.15 (I+) Digital input in reference to IN8.16, 0..24 V DC 24 V DC digital input
IN8.16 (I-) Reference Reference to 24 V DC
Table 3: Digital input specification
IN1.1 .. IN8.15
Digital input reference to IN1.2 up to IN8.16,
0 .. 24 V DC
Rin = 3.6 kΩ
Off (Uin < 2 V DC)
On (Uin > 15 V DC)
Max. input voltage = 35 V DC
Max. input frequency = 5 Hz
24 V DC
Table 4: K1
Internal BUS Data & DC power supply Connection to I/O module
Table 5: K2
Internal BUS Data & DC power supply Connection to I/O module
Table 6: LED1 – LED8
Status Digital input state
On: Input voltage present between IN1.1 and IN1.2 up
to IN8.15 and IN8.16
Off: Input voltage not present between IN1.1 and
IN1.2 up to IN8.15 and IN8.16
4

Longo programmable controller LPC-2.DI6
3.2 Mounting instructions
Figure 3: Housing dimensions
Dimensions in millimeters.
All connections, module attachments and assembling must be done
while module is not connected to the main power supply.
Mounting instructions:
1. Switch OFF main power supply.
2. Mount LPC-2.DI6 module to the provided place inside an electrical panel (DIN EN50022-35
rail mounting).
3. Mount other LPC-2 modules (if required). Mount each module to the DIN rail first, then
attach modules together through K1 and K2 connectors.
4. Connect digital inputs' wires according to the connection scheme in Figure 2.
5. Switch ON main power supply.
Dismount in reverse order. For mounting/dismounting modules to/from DIN rail a free space of at
least one module must be left on the DIN rail.
NO E: LPC-2 main module should be powered separately from other electrical appliance connected
to LPC-2 system. Signal wires must be installed separately from power and high voltage wires in
accordance with general industry electrical installation standard.
5
53
90
95
36
60

Longo programmable controller LPC-2.DI6
3.3 Module labeling
Figure 5: Labels on housing
Label 1 (MC3 sample): Label 2 (MC3 sample):
Label 1 description:
1. LPC-2.MC3 is the full product name.
2. P/N:225MC3040001001 is the part number.
•225 – general code for product family,
•MC3 – short product name,
•04001 – sequence code,
•04 – year of code opening,
•001 – derivation code,
•001 – version code (reserved for future HW and/or SW firmware upgrades).
3. D/C:16/05 is the date code.
•16 – week and
•05 – year of production.
Label 2 description:
1. S/N:MC3-S9-0500000190 is the serial number.
•MC3 – short product name,
•S9 – user code (test procedure, e.g. Smarteh person xxx),
•0500000190 – year and current stack code,
•05 – year (last two cyphers),
•00000190 – current stack number; previous module would have the stack number
00000189 and the next one 00000191.
6

Longo programmable controller LPC-2.DI6
4 TECHN CAL SPEC F CAT ONS
Table 6: Technical specifications
Power supply from internal BUS
Power consumption 0.25 W
Nominal input voltage 24 V DC
Max. input voltage 35 V DC
Number of digital inputs 8
Off / “0” input signal voltage Uin < 2 V DC
On / “1” input signal voltage Uin > 15 V DC
Connection type screw type connector for stranded wire 0.75 to
2.5 mm2
Dimensions (L x W x H) 90 x 53 x 60 mm
Weight 100 g
Ambient temperature 0 to 50 °C
Ambient humidity max. 95 %, no condensation
ransport and storage temperature -20 to 60 °C
Pollution degree 2
Protection class IP 30
7

Longo programmable controller LPC-2.DI6
5 CHANGES
he following table describes all the changes to the document.
Date V. Description
1.7.2012 005 CGP General update .
11.5.2010 004 Updated warranty permanence.
30.6.2005 003 he initial version, issued as LPC-2.DI6 module UserManual.
8

Longo programmable controller LPC-2.DI6
6 NOTES
9
Table of contents