2.4 Switching on and off
n All SolarMax inverters operate fully automatically and maintenance-free. The
isolating switches between the solar generator, the inverter and the 230 V mains
supply remain on at all times. SolarMax will start and transfer power to the
230 V grid when the irradiance is high enough. Otherwise the device remains in
standby mode and is thus available for grid feeding at all times. Overnight the
electronic system is disconnected from the mains.
Voltage may only be applied on the DC and AC side of the SolarMax with
the device closed.
Switching on:
n Switch on DC insulation switch.
The graphics display powers up.
During the night or at times of insufficient irradiance the graphics display turns
itself off (no energy consumption).
n Switch on the AC isolating switch (may be fused).
Switching off:
n Switch off the AC insulation switch.
Large arcs may be generated if connectors are disconnected on the DC
side during operation.
n Switch off the DC insulation switch.
Graphics display switched off.
2.5 Removal
n The device does not have to be opened for demounting.
n The inverter must be de-energised. First disconnect the device from the mains
on the AC side via the AC line protection breaker or the fuse. Then open the
DC insulation switch in order to disconnect the inverter from the solar generator
field. Now remove the connectors.
n Before releasing the screws ensure that the bottom of the device (heat sink) has
cooled sufficiently to allow the device to be safely handled.
n Release the two locking screws on the left and right and remove the inverter
from the mounting.
2.6 Configurable limit values and operational settings
In the SolarMax S series the following parameters can be set manually via the inter-
face with the MaxTalk software. The settings are password-protected. A password
application form can be ordered via the SolarMax hotline. The password is only
made available to installers who sign the form. The password is not made available
to private individuals or system operators.
Parameter Unit Regional settings Password-
protected
setting
DE/CH IT ES FR Other
Vac max V 264 274 253 264 300 184…300
Vac min V 184 186 196 196 184
f max Hz 50.2 50.3 51 50.5 55 45…55
f min Hz 47.5 49.7 48 49.5 45
df/dt max Hz/s NA 0 (Inactive) NA NA NA 0.1…1
Vac 10min max V 253 0 (Inactive) 264 264 243…264
Ierr max mA 300 300 300 300 300 50…300
Iac mean max A 1 0.5% of
Iac rated* 1 1 1 0.05...1
Restart delay s 0 0 180 0 0 0…600
Pac max
SM2000S W 1980 1980 1980 1980 1980 990…1980
Pac max
SM3000S W 2750 2750 2750 2750 2750 1375…2750
Pac max
SM4200S W 4180 4180 4180 4180 4180 2090…4180
Pac max
SM6000S W 5060 5060 5060 5060 5060 2530…5060
Iac max
SM2000S A 12 12 12 12 12 6…12
Iac max
SM3000S A 12 12 12 12 12 6…12
Iac max
SM4200S A 19 19 19 19 19 9…19
Iac max
SM6000S A 22 22 22 22 22 11…22
NA: not available * Iac max = 1.1 x Iac rated
The set values can be queried via the display in the main menu (see section 4.4).