Solidyne sLON-5 Instruction Manual

Solidyne Corporation - www.solidyne.com sLON-5, sLON-6 rev1 03/2005
Application
The sLON-5 and sLON-6 Controllers are interoperable
controllers designed in accordance with LONMARK®
guidelines. When programmed using WPT Software
Tool, these controllers provide control for fan coil and
unit ventilator applications. These controllers feature:
screw terminal blocks; three universal inputs,
software-configured to respond to one of five input
types; one (sLON-5) or three (sLON-6) high-voltage
relay output(s); four 24 Vac Triac (digital) outputs; and
an S-Link interface for connection to an optional
sLON-WTSx digital sensor.
The sLON-5 and sLON-6 controllers conform to the
LONMARK Fan Coil Unit functional profile (8020)
providing open communication and interoperability with
third party LONMARK devices and greater freedom in
system design. These controllers can function in
standalone mode or as part of a LONWORKS®TP/FT-10
Free Topology network.
Model Chart
INSTALLATION
Inspection Inspect carton for damage. If
damaged, notify carrier
immediately. Inspect
controllers for damage upon
receipt.
Model Description Inputs / Outputs
sLON-5 Fan Coil Controller
with One High
Voltage Relay
• 3 Universal Inputs
(software-configured)
• 4 DO Triacs, capable of
switching a total load of
0.5 A @ 24 Vac.
• 1 DO Relay Output,
250 Vac, 3 A.
• S-Link Support.
sLON-6 Fan Coil Controller
with Three High
Voltage Relays
• 3 Universal Inputs
(software-configured)
• 4 DO Triacs, capable of
switching a total load of
0.5 A @ 24 Vac.
• 3 DO Relay Outputs,
250 Vac, 3 A.
• S-Link Support.
DO1
24VAC
DO2
DO3
24VAC
DO4
Power: 24VAC, 50/60Hz, Class 2,
8.5VA + DO1-DO4 loads.
Ambient Temp:-40°C to +60°C
UI: 5VDC Max, Class 2.
S-LK: 16VDC Max, Class 2.
DO1-DO4: 24VAC, 0.4A Max TotalLoad.
DO5: 250VAC, 3A Max, COS
f
= 0.4.
DO5
C5
GND
0V
24VAC
UI3
COM 0V
UI2
COM 0V
UI1
S-LK
S-LK
LON
LON
S
R
V
C
R
E
C
V
X
M
I
T
J1
934G
E9429
N2223
SRVC
CAUTION
RISK OF ELECTRICAL SHOCK OR FIRE. DO NOT
INTERCONNECT SEPARATE CLASS 2 CIRCUITS.
DISCONNECT POWER BEFORE SERVICING.
DECONNECTER AVANT ENTRETEN.
This device conforms with Part 15 of the FCC Rules. Operationis subject to the following two conditions: (1) This
device may not cause harmful interference, and(2) This device must accept any interference received, including
interference that may cause undesired operation.
This Class B digital apparatus meets all requirements oftheCanadian Interference-Causing Equipment Regulations.
Cet appareil numerique de la classe B respectetoutesles exigences du Reglement sur le material brouilleur du Canada
Temperature indicating and
Regulating Equipment
3.3
sLON-5
DO1
24VAC
DO2
DO3
24VAC
DO4
Power: 24VAC, 50/60Hz, Class 2,
9.5VA + DO1-DO4 loads.
Ambient Temp: -40°C to +55°C
UI: 5VDC Max, Class 2
S-LK: 16VDC Max, Class 2
DO1-DO4: 24VAC, 0.4A Max Total Load.
DO5-DO7: 250VAC, 3A Max,
COS
Φ
= 0.4
DO5
C5
DO6
C6
DO7
C7
GND
0V
24VAC
UI3
COM 0V
UI2
COM 0V
UI1
S-LK
S-LK
LON
LON
S
R
V
C
R
E
C
V
X
M
I
T
J1
934G
E9429
N2223
SRVC
CAUTION
RISK OF ELECTRICAL SHOCK OR FIRE. DO NOT
INTERCONNECT SEPARATE CLASS 2 CIRCUITS.
DISCONNECT POWER BEFORE SERVICING.
DECONNECTER AVANT ENTRETEN.
This device conforms with Part 15 of the FCC Rules. Operation is subject to the
following two conditions: (1) This device may not cause harmful interference, and
(2) This device must accept any interference received, including interference that
may cause undesired operation.
This Class B digital apparatus meets all requirements of the Canadian Interference-
Causing Equipment Regulations.
Cet appareil numerique de la classe B respecte toutes les exigences du Reglement
Temperature indicating and
Regulating Equipment
3.3
sLON-6
TECH/DATA SHEET
sLON-5
sLON-6
sLON VAV Controller
firealarmresources.com

2sLON-5, sLON-6 rev1 03/2005
Requirements •Installer must be an experienced technician.
•Tools:
– Drill and bits
– Digital Volt-ohm meter (DVM)
– Static protection wrist strap
•Class 2 power transformer supplying a nominal 24 Vac (20.4 to 30 Vac), 50/60 Hz. For
transformer specifications, see the “Power Supply Wiring” section, on page 14.
•Suitable grounded metal enclosure (to prevent the possibility of accidental contact with
the high-voltage terminals)
•Four #6 self-starting screws or 35 mm DIN rail for mounting
•Terminators (if a LONWORKS network is used):
– One sLON-T1 terminator required for each free topology segment
– Two sLON-T2 terminators required for each bus topology segment
•Accessories (as required):
– sLON-WTSx (S-Link) Sensors
– 470k ohm 1/4 watt resistor (if shielded wire is used for S-Link wiring)
– Approved Category 4 or 5, twisted-pair (two conductors) cable (optional LONWORKS
Network connection)
– 0.205 mm2(#24 AWG) or larger twisted pair, voice grade telephone wire (for UI,
AO, and DI wiring)
– 10K ohm Thermistor Sensor with 11K ohm Shunt Resistor
– Platinum Sensor
– Balco Sensor
– 1K Balco or platinum element resistive sensor
– 0 to 5 Vdc analog voltage transmitter
– 4 to 20 mAdc analog current transmitter
– Digital dry switched contact (switched contact resistance must be less than
300 ohms for closed contact and greater than 1.5K ohms for open contact)
firealarmresources.com

sLON-5, sLON-6 rev1 03/2005 3
Precautions General
Warning: The sLON-5 and sLON-6 controllers are not suitable for exposed mounting
on a wall or panel, or in any other easily accessible place due to the possibility of
personal contact with the high-voltage terminals. They must be mounted inside a
suitable grounded metal enclosure (Figure-2).
Warning: Electrical shock hazard! Disconnect power from the controller and any digital
outputs before installing or removing the cover.
•Follow Static Precautions when installing this equipment.
•Use copper conductors that are suitable for 75 °C (167 °F).
•Make all connections according to electrical wiring diagram, national and local electrical
codes.
Static Precautions
Static charges damage electronic components. The microprocessor and associated circuitry
are extremely sensitive to static discharge. Use the following precautions when installing,
servicing, or operating the system.
•Work in a static-free area.
•Discharge static electricity by touching a known, securely grounded object.
•Use a wrist strap connected to earth ground when handling the controller’s printed
circuit board.
Federal Communications Commission (FCC)
This equipment has been tested and found to comply with the limits for a Class B digital
device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference in residential installations. This
equipment generates, uses, and can radiate radio frequency energy and may cause harmful
interference if not installed and used in accordance with the instructions. Even when
instructions are followed, there is no guarantee that interference will not occur in a particular
installation. If this equipment causes harmful interference to radio or television reception —
which can be determined by turning the equipment off and on — the user is encouraged to
try to correct the interference by one or more of the following measures:
•Reorient or relocate the receiving antenna.
•Increase the separation between the equipment and receiver.
•Connect the equipment to an outlet on a circuit different from that to which the receiver
is connected.
•Consult the dealer or an experienced radio/television technician for help.
Canadian Department of Communications (DOC)
Note: This Class B digital apparatus meets all requirements of the Canadian
Interference-Causing Equipment Regulations.
Cet appareil numerique de la classe B respecte toutes les exigences du Reglement sur le
material broilleur du Canada.
European Community Directives
This equipment meets all requirements of European Community Directives for Low Voltage
(72/23/EEC), General Safety (92/59/EEC), and Electromagnetic Compatibility
(89/336/EEC).
Caution:
•This is a Class A product. In a domestic environment this product may cause radio
interference, in which case the user may be required to take adequate measures.
•The LON and S-LK cables must be installed within grounded metallic conduit or
conductive cable trays to fully comply with the EMC requirements of EN61326.
firealarmresources.com

4sLON-5, sLON-6 rev1 03/2005
Location The sLON-5 and sLON-6 controllers are suitable for indoor use only (IP 20). See Figure-1
for mounting dimensions. When selecting a mounting location, make certain the following
conditions are met:
Warning: The sLON-5 and sLON-6 controllers are not suitable for exposed mounting
on a wall or panel, or in any other easily accessible place due to the possibility of
personal contact with the high-voltage terminals. They must be mounted inside a
suitable grounded metal enclosure (Figure-2).
Caution:
•Do not install where excessive moisture, corrosive fumes, vibration, or explosive vapors
are present.
•Do not install near large contactors, electrical machinery, or welding equipment.
•Allow 150 mm (6 in.) clearance from contactors, switches, and associated cabling.
•Locate where ambient temperatures do not exceed 55 °C (131 °F) or fall below -40 °C
(-40 °F) and relative humidity does not exceed 95%, non-condensing.
Mounting Panel or DIN Rail Mounting
1. Select a mounting location. Allow a minimum of 50 mm (2 in.) clearance around the
controller.
23 mm
(15/16 in.)
50 mm
(2 in.)
107 mm
(4-3/16 in.)
14 mm
(9/16 in.)
6 mm
(1/4 in.)
9 mm
(3/8 in.)
134.5 mm (5-5/16 in.)
95.5 mm
(3-3/4 in.)
155 mm (6 in.)
132.5 mm (5-7/32 in.)
Note: sLON-5 shown. Dimensions are
the same for sLON-6.
Figure-1 Mounting Dimensions.
firealarmresources.com

sLON-5, sLON-6 rev1 03/2005 5
2. Do the following to mount the controller onto a panel (Figure-3):
a. Place the controller on a panel and mark the location of one top mounting hole.
b. Drill the marked hole, using a drill bit sized for a #6 screw.
c. Fasten the controller to the panel with one #6 self-starting screw.
d. Level the controller, then mark the locations of the remaining mounting holes.
e. Drill the marked holes, then fasten the controller, using the three remaining screws.
3. Do the following to mount the controller onto a 35 mm DIN mounting rail (Figure-4):
a. Hook the mounting tabs, on the back of the controller, onto the top edge of the DIN
rail.
b. Gently press the bottom of the controller onto the DIN rail so that it snaps into place.
1
Dedicated Ground
Wire from Enclosure
Metal Enclosure
(Grounded)
Controller
(sLON-5 Shown)
(4) Screws
DIN Rail
Alternate Mounting
Methods
Grounding Point
inside Enclosure
OR
1 This example illustrates the use of a suitable grounded metal
enclosure to mount an sLON-5 or sLON-6 controller.
This controller is not suitable for exposed mounting on a wall
or panel, or in any other easily accessible place due to the
possibility of personal contact with the high-voltage terminals.
DO1
24VAC
DO2
DO3
24VAC
DO4
DO5
C5
GND
0V
24VAC
UI3
COM 0V
UI2
COM 0V
UI1
S-LK
S-LK
LON
LON
S
R
V
C
R
E
C
V
X
M
I
T
J1
934G
E9429
N2223
SRVC
Temperature indicating and
Regulating Equipment
GND
0V
24VAC
UI3
COM 0V
UI2
COM 0V
UI1
3.3
Figure-2 Mounting in Enclosure.
Figure-3 Panel Mounting Method.
(3) Screws
(1) Screw
DO1
24VAC
DO2
DO3
24VAC
DO4
DO5
C5
GND
0V
24VAC
UI3
COM 0V
UI2
COM 0V
UI1
S-LK
S-LK
LON
LON
S
R
V
C
R
E
C
V
X
M
I
T
J1
934G
E9429
N2223
SRVC
Temperature indicating and
Regulating Equipment
DO1
24VAC
DO2
DO3
24VAC
DO4
DO5
C5
GND
0V
24VAC
UI3
COM 0V
UI2
COM 0V
UI1
S-LK
S-LK
LON
LON
S
R
V
C
R
E
C
V
X
M
I
T
J1
934G
E9429
N2223
SRVC
Temperature indicating and
Regulating Equipment
3.3
3.3
Figure-4 DIN Rail Mounting Method.
DO1
24VAC
DO2
DO3
24VAC
DO4
DO5
C5
GND
0V
24VAC
UI3
COM 0V
UI2
COM 0V
UI1
S-LK
S-LK
LON
LON
S
R
V
C
R
E
C
V
X
M
I
T
J1
934G
E9429
N2223
SRVC
Temperature indicating and
Regulating Equipment
DO1
24VAC
DO2
DO3
24VAC
DO4
DO5
C5
GND
0V
24VAC
UI3
COM 0V
UI2
COM 0V
UI1
S-LK
S-LK
LON
LON
S
R
V
C
R
E
C
V
X
M
I
T
J1
934G
E9429
N2223
SRVC
Temperature indicating and
Regulating Equipment
3.3
3.3
firealarmresources.com

6sLON-5, sLON-6 rev1 03/2005
Wiring
The following electrical connections can be made to sLON-5 and sLON-6 controllers:
•Communications wiring, including:
•S-LK wiring between an sLON-5 and sLON-6 controller and an sLON-WTSx
Sensor.
•LONWORKS network (LON) connection, including connections to other sLON-type
controllers.
•I/O connections, including:
•Three Universal Inputs (UIs)
•One (sLON-5) or three (sLON-6) high-voltage relay output(s)
•Four Triac digital outputs
•LONWORKS Network Jack
•24 Vac nominal class 2 (EN 60742) power source and earth ground power connection
GND
24VAC
0V
UI3
COM 0V
UI2
COM 0V
UI1
S-LK
S-LK
LON
LON
DO1
24VAC
DO2
DO3
24VAC
DO4
C5
DO5
LONWORKS Network
(LON) Jack
High-Voltage
Relay
Digital (Triac)
Outputs
Ground
sLON-WTSx
Sensor Inputs
Universal
Inputs
LONWORKS
Network Connection
24Vac Power
(Transformer)
DO1
24VAC
DO2
DO3
24VAC
DO4
Power: 24VAC, 50/60Hz, Class 2,
8.5VA + DO1-DO4 loads.
Ambient Temp: -40°C to +60°C
UI: 5VDC Max, Class 2.
S-LK: 16VDC Max, Class 2.
DO1-DO4: 24VAC, 0.4A Max Total Load.
DO5: 250VAC, 3A Max, COS f= 0.4.
DO5
C5
GND
0V
24VAC
UI3
COM 0V
UI2
COM 0V
UI1
S-LK
S-LK
LON
LON
S
R
V
C
R
E
C
V
X
M
I
T
J1
934G
E9429
N2223
SRVC
CAUTION
RISK OF ELECTRICAL SHOCK OR FIRE. DO NOT
INTERCONNECT SEPARATE CLASS 2 CIRCUITS.
DISCONNECT POWER BEFORE SERVICING.
DECONNECTER AVANT ENTRETEN.
This device conforms with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This
device may not cause harmful interference, and (2) This device must accept any interference received, including
interference that may cause undesired operation.
This Class B digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numerique de la classe B respecte toutes les exigences du Reglement sur le material brouilleur du Canada
Temperature indicating and
Regulating Equipment
Service Pin
LEDs
3.3
Figure-5 sLON-5 Terminal Connections.
GND
24VAC
0V
UI3
COM 0V
UI2
COM 0V
UI1
S-LK
S-LK
LON
LON
DO1
24VAC
DO2
DO3
24VAC
DO4
LONWORKS Network
(LON) Jack
Digital (Triac)
Outputs
Ground
sLON-WTSx
Sensor Inputs
Universal
Inputs
LONWORKS
Network Connection
24Vac Power
(Transformer)
Service Pin
LEDs
C7
DO7
C6
DO6
C5
DO5
High-Voltage
Relays
DO1
24VAC
DO2
DO3
24VAC
DO4
Power: 24VAC, 50/60Hz, Class 2,
9.5VA + DO1-DO4 loads.
Ambient Temp: -40°C to +55°C
UI: 5VDC Max, Class 2
S-LK: 16VDC Max, Class 2
DO1-DO4: 24VAC, 0.4A Max Total Load.
DO5-DO7: 250VAC, 3A Max,
COS
Φ= 0.4
DO5
C5
DO6
C6
DO7
C7
GND
0V
24VAC
UI3
COM 0V
UI2
COM 0V
UI1
S-LK
S-LK
LON
LON
S
R
V
C
R
E
C
V
X
M
I
T
J1
934G
E9429
N2223
SRVC
CAUTION
RISK OF ELECTRICAL SHOCK OR FIRE. DO NOT
INTERCONNECT SEPARATE CLASS 2 CIRCUITS.
DISCONNECT POWER BEFORE SERVICING.
DECONNECTER AVANT ENTRETEN.
This device conforms with Part 15 of the FCC Rules. Operation is subject to the
following two conditions: (1) This device may not cause harmful interference, and
(2) This device must accept any interference received, including interference that
may cause undesired operation.
This Class B digital apparatus meets all requirements of the Canadian Interference-
Causing Equipment Regulations.
Cet appareil numerique de la classe B respecte toutes les exigences du Reglement
Temperature indicating and
Regulating Equipment
3.3
Figure-6 sLON-6 Terminal Connections.
firealarmresources.com

sLON-5, sLON-6 rev1 03/2005 7
Communications
Wiring Communications wiring includes wiring between the sLON-5 or sLON-6 controller and one
sLON-WTSx Sensor, as well as wiring between the sLON-5 or sLON-6 controller and a
LONWORKS Network (LON).
S-Link and LON Wiring Precautions
Caution:
•Communication wire pairs must be dedicated to S-Link and LON communications. They
cannot be part of an active, bundled telephone trunk.
•The LON and S-LK cables must be installed within grounded metallic conduit or
conductive cable trays to fully comply with the EMC requirements of EN61326.
•Shielded cable is not required for S-Link or LON communications wiring. If shielded wire
is used, the shield must be connected to earth ground at only one end, using a 470k
ohm 1/4 watt resistor, and the shield must be continuous from one end of the trunk to
the other.
•Conduit between a Sensor and a controller can be shared by S-LK wiring and LON
wiring, provided that this conduit does not also contain wiring for power, UI, AO, DI, or
DO. However, the S-Link and LON wiring must be separate cables.
Sensor Link (S-Link) Wiring
Using S-LK wiring, an sLON-5 or sLON-6 controller may be connected to one sLON-WTSx
sensor. S-Link wiring powers and enables the sensor. The S-Link requires at least
0.205 mm2(#24 AWG), twisted pair, voice-grade telephone wire. The capacitance between
conductors cannot be more than 32 pF per 0.3 m (1 ft). If shielded cable is used, the
capacitance between any one conductor and the others, connected to the shield, cannot be
more than 60 pF per 0.3 m (1 ft). The maximum wire length is 61 m (200 ft).
Note:
•The sLON-5 or sLON-6 controller can support one sLON-WTSx Sensor.
•S-Link wiring is not polarity-sensitive.
Connect the one sLON-5 or sLON-6 controller to an sLON-WTSx Sensor as follows:
1. Strip 6 mm (1/4 in.) of insulation from one end of the S-LK wires.
2. Connect the stripped wires to the S-LK terminals of the controller (Figure-5 or Figure-6).
The S-LK connection is not polarity-sensitive.
3. Strip 6 mm (1/4 in.) of insulation from the other end of the S-LK wires.
4. Connect the other end of the S-LK wires to the sensor.
1 The S-Link connection is
not polarity sensitive.
1 1
S-LK
S-LK
sLON-5
sLON-6
1
2
sLON-WTSx
Sensor
S-Link
Terminals
Figure-7 sLON-5 and sLON-6 S-Link Terminal Connections.
firealarmresources.com

8sLON-5, sLON-6 rev1 03/2005
LONWORKS Network (LON) Wiring
Approved Category 4 or 5, twisted-pair (two conductors) cable may be used for the
LONWORKS Network connection between the sLON-5 or sLON-6 controller and a LONWORKS
Network, or for the optional LONWORKS Network connection between the controller and an
sLON-WTSx Sensor.
Caution:
•See the section, “S-Link and LON Wiring Precautions,” on page 7.
•Do not mix LON network wiring with power, UI, AO, DI, or DO types of wiring.
•Conduit between an sLON-WTSx Sensor and a controller can be shared by LON
wiring and S-LK wiring, provided that this conduit does not also contain wiring for
power, UI, AO, DI, or DO. However, the S-Link and LON wiring must be separate
cables.
Connect the sLON-5 or sLON-6 controller to a LONWORKS Network or an sLON-WTSx
Sensor as follows:
1. Strip 6 mm (1/4 in.) of insulation from one end of the LON wires.
2. Connect the stripped wires to the LON terminals of the controller (Figure-8). The LON
connection is not polarity-sensitive.
3. Strip 6 mm (1/4 in.) of insulation from the other end of the LON wires.
4. If the sLON-5 or sLON-6 controller is to be connected to a LONWORKS network,
determine the topology chosen for the TP/FT-10 segment, then connect to additonal
controllers. To allow the sLON-5 or sLON-6 to share data with other LONWORKS
devices, the controller must be addressed and the desired network bindings must be
made. Refer to the section, “Installation on a LONWORKS Network,” to accomplish this.
Note:
•The sLON-5 and sLON-6 controllers use the LONWORKS Free Topology Transceiver
(FT 3150®). It may be connected to other controllers freely, using multiple wiring
tees and stars (Free Topology) or using a daisy-chain topology. If a daisy-chain
topology is chosen, the controllers must be connected only in a device-to-device
fashion (Bus Topology). A maximum of 62 nodes can be connected per wiring
segment.
Note:
•Use of the LON terminals to connect to the sLON-WTSx sensor permits use of the
sensor’s built-in LONWORKS Network Jack.
•To preserve the integrity of the network, the LONWORKS Network wiring connecting
an sLON controller to an sLON-WTSx sensor must be run to the sensor and back,
in daisy-chain fashion. A wire “spur” must not be used to connect the sensor to the
controller.
•While the sLON-WTSx sensor is not counted as a “node” in the LONWORKS
Network (LON), all LONWORKS Network wiring to the sensor must be counted when
determining the length of the TP/FT-10 wiring segment.
5. Install terminators as required.
L
ON
W
ORKS
Network
1 The L
ON
W
ORKS
connection is not polarity sensitive.
1
LON
LON
sLON-5
sLON-6
Figure-8 sLON-5 and sLON-6 LONWORKS Network Terminal Connections.
firealarmresources.com

sLON-5, sLON-6 rev1 03/2005 9
I/O Wiring I/O connections include three software-configured universal inputs (UIs), one (sLON-5) or
three (sLON-6) high-voltage relay output(s) (DOs), and four Triac outputs. The Triac outputs
are for switching 24 Vac pilot-duty loads. See Figure-5 and Figure-6 for wire terminal
information.
Warning: Electrical shock hazard. Remove all power from both the controller and digital
outputs before making terminations.
UI, AO, and DI wiring require at least 0.205 mm2(#24 AWG), twisted pair, voice grade
telephone wire. The capacitance between conductors cannot be more than 32 pF per 0.3 m
(1 ft). If shielded cable is used, the capacitance between any one conductor and the others,
connected to the shield, cannot be more than 60 pF per 0.3 m (1 ft). Refer to Table-1 for
wiring specifications.
Universal Inputs (UI)
The Universal Inputs’ characteristics are software-configured to respond to one of the
following input types:
1. 10K ohm Thermistor with 11K ohm Shunt Resistor (refer to Figure-9).
2. 10K ohm Resistive.
3. 1K ohm Balco (refer to Figure-10).
4. 1K ohm Platinum (refer to Figure-10).
5. 1K ohm Resistive.
6. Analog Voltage (refer to Figure-11).
7. Analog Current (refer to Figure-12).
8. Digital Dry Switched Contact (refer to Figure-13).
Caution:
•If shielded cable is used for universal inputs (UI), connect only one end of the shield
to a single COM 0V terminal (not to GND).
•If shielded cable is used for other I/O, connect only one end of the shield to a single
earth ground point, at the controller’s ground (GND) terminal.
•Input and output devices cannot share common wiring. Each connected device
requires a separate signal and return conductor.
•UI, S-Link, and LON wiring cannot share a conduit with either power wiring or
high-voltage relay wiring.
Note: UI and S-Link wiring can share a single conduit.
10K Thermistor with 11K Shunt Resistor
Any of the sLON-5 or sLON-6 controller’s UI inputs can be configured for Thermistor input.
When configured in this way, a 10K ohm Thermistor with 11K ohm shunt resistor may be
connected to the sLON-5 or sLON-6 controller to sense the space temperature. See Table-2
for temperature versus resistance data for this thermistor.
Table-1 UI, AO, and DI Wiring Specifications.
Connection Gage
mm2(AWG) Maximum Distance
m (ft)
UI, AO, and DI
0.823 (18) 91 (300)
0.518 (20) 61 (200)
0.326 (22) 38 (125)
0.205 (24) 23 (75)
Table-2 Temperature Versus Resistance.
Temperature
°C (°F) Resistance
ohms Temperature
°C (°F) Resistance
ohms
4 (40) 7596 30 (86) 4696
firealarmresources.com

10 sLON-5, sLON-6 rev1 03/2005
Make the Thermistor connections according to the diagram in Figure-9.
Resistive — 1K Balco or 1K Platinum Input
Any of the sLON-5 or sLON-6 controller’s UI inputs can be configured for the 1K Balco or
Platinum Element Resistive Sensor. Make the connections according to the diagram in
Figure-10.
10 (50) 6938 40 (104) 3707
20 (68) 5798 50 (122) 2875
25 (77) 5238 60 (140) 2206
Table-2 Temperature Versus Resistance.
Temperature
°C (°F) Resistance
ohms Temperature
°C (°F) Resistance
ohms
UI1
COM 0V
sLON-5
sLON-6
2
10K ohm Thermistor
1
10K ohm
Thermistor
11K ohm
± 0.1%
Shunt
Resistor
12
1 Any one of the three Universal Inputs (UI1, UI2,
or UI3) may be programmed for Thermistor
input. Connection to UI1 is illustrated here as an
example only.
2 Applications that use a 10K thermistor sensor
require an 11K ohm Shunt Resistor Kit,
AD-8969-206. Install this resistor across the
Universal Input and the Common.
Figure-9 Typical Wiring for 10K Thermistor with 11K Shunt Resistor.
UI1
COM 0V
sLON-5
sLON-6
1K Resistive Sensor
Balco or Platinum
Element
1
1 Any one of the three Universal Inputs (UI1, UI2,
or UI3) may be programmed for Balco or
Platinum Sensor input. Connection to UI1 is
illustrated here as an example only.
Figure-10 Typical Wiring for 1K Balco or 1K Platinum Sensor Input.
firealarmresources.com

sLON-5, sLON-6 rev1 03/2005 11
Analog Voltage Input
Any of the sLON-5 or sLON-6 controller’s UI inputs can be configured for the 0 to 5 Vdc
Analog Voltage Transmitter input. Make the connections according to the diagram in
Figure-11.
Analog Current Input
Any of the sLON-5 or sLON-6 controller’s UI inputs can be configured for the 4 to 20 mAdc
Analog Current Transmitter input. Make the connections according to the diagram in
Figure-12.
Digital Dry Switched Contact Input
Any of the sLON-5 or sLON-6 controller’s UI inputs can be configured for the Digital Dry
Switched Contact input. Make the connections according to the diagram in Figure-13.
Note: If the maximum closed switch voltage is not more than 1.0 V and the minimum open
switch voltage is at least 4.5 V, then solid state switches may be used for a UI when
configured as a DI.
UI1
COM 0V
sLON-5
sLON-6
0 to 5 Vdc
Transmitter
1
1 Any one of the three Universal Inputs (UI1, UI2, or UI3) may be
programmed for 0 to 5 Vdc Analog Voltage input. Connection to
UI1 is illustrated here as an example only.
2 Input signals of 1 to 11 Vdc must be converted to 0.45 to 5 Vdc
with a Voltage Divider, AD-8961-220.
+
_
Power
Source
Figure-11 Typical Wiring for 0 to 5 Vdc Analog Voltage Input.
sLON-5
sLON-6
4 to 20 mA
Transmitter
1
2
1 Any one of the three Universal Inputs (UI1, UI2, or UI3) may be
programmed for 4 to 20 mAdc Analog Current input. Connection
to UI1 is illustrated here as an example only.
2 Input signals of 4 to 20 mAdc must be converted to 1 to 5 Vdc
with a 250 ohm Shunt Resistor Kit, AD-8969-202. Install the
resistor across the Universal Input and Common terminals.
+
_
Power
Source
UI1
COM 0V
250 ohm
Figure-12 Typical Wiring for 4 to 20 mA Analog Current Input.
sLON-5
sLON-6
Digital Dry
Switched
Contact
1
2
1 Any one of the three Universal Inputs (UI1, UI2, or UI3) may be
programmed for Digital Dry Switched Contact input. Connection
to UI1 is illustrated here as an example only.
2 Switched contact resistance must be less than 300 ohms for
closed contact and greater than 1.5K ohms for open contact.
UI1
COM 0V
Figure-13 Typical Wiring for Digital Dry Switched Contact Input.
firealarmresources.com

12 sLON-5, sLON-6 rev1 03/2005
Digital Triac Outputs (DOs)
The sLON-5 and sLON-6 controllers contain four 24 Vac (digital) Triac outputs. Before
wiring these outputs, refer to Table-3 for their electrical specifications.
Caution:
•Do not mix DO wiring with power, high-voltage relay, DI, UI, S-Link, LON, or AO wiring.
•The total output load for DO1 through DO4 is 12 VA. This limit applies whether one, two,
three, or all four DOs are ON at the same time. Exceeding this limit may result in the
loss of controller power until the external fault is removed and the internal PTC (Positive
Temperature Coefficient) device cools sufficiently. The PTC is a current-limiting thermal
safety device.
•Triac output terminals accept one 0.823 mm2(#18 AWG) or smaller wire. The selected
wire gage must be consistent with the load current rating.
Note:
•DO1 through DO4 are Triac outputs for switching 24 Vac loads only, such as pilot-duty
relays and floating control actuators.
•Triac outputs switch the load circuit to ground and are supplied through the 24VAC
terminals.
Connect the sLON-5 or sLON-6 controller’s Triac output terminals (DO1, DO2, DO3, and
DO4) as follows:
1. Connect one side of a 24 Vac load to one of the 24VAC terminals.
Caution: Whenever the sLON-5 or sLON-6 is connected to share I/O with other
controllers, care must be exercised to connect the power for the inputs in a consistent
manner. Refer to the wiring diagram on the cover.
2. Connect the other side of the load to a Triac output terminal (DO1, DO2, DO3, or DO4).
See Figure-14.
Table-3 Triac Output Electrical Specifications.
Characteristic Specification
Maximum Triac Switched Output Voltage 24 Vac terminal voltage a
aSwitched output voltage is equivalent to the value of the input voltage.
Minimum Triac Switched Output Voltage 24 Vac terminal voltage a- 2.0 Vac
Rating 12 VA (0.5 A) @ 24 Vac at each output.
Total of 12 VA @ 24 Vac for all outputs that are ON at any
one time.
Motor Requirements NA
Default Output State OFF (inactive)
Output Short Circuit Protection Internal current limiting
Maximum Off-State Leakage Current 2.0 mA
Minimum Permissible Load 50 mA
0V
24Vac
24Vac
24Vac
DO1
DO2
DO3
DO4
sLON-5
sLON-6
24 Vac Load
(Cooling)
Open
Close
COM
24 Vac Load
(Heating)
Open
Close
COM
1 The example shown here is for controlling two 24 Vac floating valve actuators.
1
1
B3
R1
W2
B3
R1
W2
Figure-14 24 Vac Loads Switched by Triac Outputs.
firealarmresources.com

sLON-5, sLON-6 rev1 03/2005 13
High-Voltage Relay Output
The sLON-5 controller contains one high-voltage relay output and the sLON-6 controller
contains three such outputs. Before wiring a high-voltage output, refer to Table-4 for its
electrical specifications.
Caution:
•Do not mix high-voltage relay wiring with any other controller wiring.
•High-voltage relay terminals accept one 2.08 mm2(#14 AWG) or smaller wire. The
selected wire gage must be consistent with the load current rating.
Connect the sLON-5 or sLON-6 controller’s high-voltage relay terminal(s) (DO5 and C5 for
the sLON-5; DO5, C5, DO6, C6, DO7, and C7 for sLON-6) to 230 Vac power and the
switched 230 Vac motor(s) as shown in Figure-15 and Figure-16.
Table-4 High-Voltage Relay Output Load Specifications.
Specification Value
Maximum Relay Contact Switched Output Voltage 250 Vac
Maximum Output Load (cos φ= 0.4)3.0A
Minimum Controllable Load @ 5 Vdc 10.0 mA
Maximum Off-State Leakage Current 100 µA
Minimum Cycles at Rated Load @ 0.4 Power Factor 100,000 cycles
C5
DO5
sLON-5
230 Vac
3A Motor
230 Vac
Power
Figure-15 sLON-5 Connection to 230 Vac High-Voltage Relay.
sLON-6
230 Vac
3A Motor
#3
230 Vac
Power
230 Vac
3A Motor
#2
230 Vac
Power
230 Vac
3A Motor
#1
230 Vac
Power
C7
DO7
C6
DO6
C5
DO5
Figure-16 sLON-6 Connections to 230 Vac High-Voltage Relays.
firealarmresources.com

14 sLON-5, sLON-6 rev1 03/2005
Power Supply Wiring Power Supply Wiring Precautions
Caution:
•The sLON-5 and sLON-6 controllers contain a non-isolated half-wave rectifier power
supply and must not be powered by transformers used to power other devices
containing non-isolated full-wave rectifier power supplies.
•Do not mix power wiring or high-voltage relay wiring with any other controller wiring.
•Use a Class 2 power transformer supplying a nominal 24 Vac (20.4 to 30 Vac),
50/60 Hz. It must have a minimum rating of 9.5 VA plus the DO1 through DO4 total
output load of 12 VA maximum, up to a total of 21.5 VA per controller. In the European
Community, a safety-isolating SELV (Safety Extra Low-Voltage), limited energy source
(<100 VA) transformer that conforms to EN 60742 must be used.
•The transformer frame must be grounded, and the supply to the transformer must have
a circuit breaker or disconnect.
Note:
•24 Vac power wiring can be intermixed with DO wiring.
•Twisted or untwisted cable can be used for power wiring.
•To preserve the integrity of the network, the LONWORKS Network wiring connecting an
sLON controller to an sLON-WTSx sensor must be run to the sensor and back, in
daisy-chain fashion. A wire “spur” must not be used to connect the sensor to the
controller.
Power Wiring
Refer to Figure-17 and Figure-18 for acceptable wiring configurations.
1. Connect the power ground wire to the Ground terminal (GND).
2. Connect the 24 Vac power wiring to the power terminals (24 VAC and 0V).
Primary 24 Vac
Secondary
Class 2
S-Link
LON 1
2To rest of the LONWORKS
network
sLON-WTSx
Sensor
1 Optional connection provides local
access to the LONWORKS network.
2 Ground the frame of the transformer
to a known ground.
0V
24VAC
S-LK
S-LK
LON
LON
sLON-5
sLON-6
GND
Figure-17 Power Supply Connection — Single Controller Powered from a Separate Class 2 Power Source.
firealarmresources.com

sLON-5, sLON-6 rev1 03/2005 15
Primary 24 Vac
Secondary
Class 2
S-Link
LON 1
2
3
To rest of the
LONWORKS network
sLON-WTSx
Sensor
S-Link
LON 1
sLON-WTSx
Sensor
S-Link
LON 1
sLON-WTSx
Sensor
S-Link
LON 1
sLON-WTSx
Sensor
1 Optional connection provides local
access to the LONWORKS network.
2 Ground the frame of the transformer
to a known ground.
3 Class 2 wiring.
To other LONMARK
and LONWORKS Controllers
0V
24VAC
S-LK
S-LK
LON
LON
sLON-5
sLON-6
GND
0V
24VAC
S-LK
S-LK
LON
LON
sLON-5
sLON-6
GND
0V
24VAC
S-LK
S-LK
LON
LON
sLON-5
sLON-6
GND
0V
24VAC
S-LK
S-LK
LON
LON
sLON-5
sLON-6
GND
To rest of the
LONWORKS network
Figure-18 Power Supply Connection — Multiple Controllers Powered from a Separate Class 2 Power Source
and Sharing Communications in a Free Topology Segment.
firealarmresources.com

16 sLON-5, sLON-6 rev1 03/2005
Installation on a
LONWORKS Network In addition to functioning in standalone mode, the sLON-5 or sLON-6 controller may be
connected to a LONWORKS network for data sharing with other LONWORKS devices. This is
made possible by addressing the controller on the network and performing the desired
network bindings.
LONWORKS Network Addressing
Address the controller on the LONWORKS network, as follows:
1. Verify that the controller is powered and connected to the network.
2. Perform the necessary steps to configure the controller, using the WPT Software Tool.
This involves the creation and downloading of control logic to the controller.
Note: The WPT Software Tool must be Version 4.0 or greater when it is used to
configure the sLON-5 and sLON-6 controllers on a LONWORKS network.
3. Using an appropriate network management tool, proceed to address the controller on
the LONWORKS network, up to the point at which the tool asks for the controller’s unique
Neuron®ID. This address will consist of a domain, subnet, and node.
4. Obtain the controller’s Neuron ID, using either of the following methods:
Service Pin Button
a. Make the network tool “listen” for the service pin message.
b. Press and release the controller’s service pin button. This sends a broadcast
message containing the controller’s Neuron ID (the controller’s LONWORKS serial
number). Service pin messages can be sent from a controller, whether addressed
or not, as many times as necessary.
Caution: Do not hold the service pin button in the pressed position. Holding the
service pin button for 6 seconds or longer will completely unconfigure the
controller.
Note: If an sLON-WTS2, sLON-WTS3, sLON-WTS4, or sLON-WTS5 sensor is
connected to the controller, the sensor’s override button can also be used to
generate a service pin message from the controller by holding the button for 5
seconds.
Manual Method
a. Indicate to the network tool that you will enter the Neuron ID manually.
b. Locate the controller’s Neuron ID. The sLON-5 or sLON-6 controller’s Neuron ID is
printed on a pair of barcode labels attached to the controller at the factory. One of
the labels remains on the controller permanently, while the other label can be
detached and placed on a job site’s node list plan.
c. Manually enter the Neuron ID into the tool, or scan the barcode.
5. Proceed to finish commissioning the controller on the LONWORKS network.
Network Bindings
Using an appropriate network management tool, perform the desired network bindings to
enable the sharing of data over the LONWORKS network.
firealarmresources.com

sLON-5, sLON-6 rev1 03/2005 17
Checkout Mechanical Hardware Checkout
1. If an sLON-WTSx Sensor is connected to the controller, verify that the wiring between
the sensor and the controller is installed according to the job wiring diagram and
national and local wiring codes.
Note: Wiring of the S-Link and LONWORKS network between the sensor and the controller
is not polarity sensitive.
2.If the controller is part of a LONWORKS network, verify that the TP/FT-10 LONWORKS
network wiring between the controller and other devices is installed according to the job
wiring diagram and the national and local electrical codes.
3.Verify that 24 Vac power is provided from a Class 2 power transformer, and that wiring is
installed according to the job wiring diagrams and the national and local electrical
codes.
4.If multiple devices are powered from the same transformer (Figure-18), verify that wiring
polarity has been maintained between all connected devices, and that all other issues
associated with powering multiple devices from a common transformer have been
addressed.
5.Verify that the digital outputs and the high-voltage relay(s) are wired according to the job
wiring diagram and the national and local electrical codes.
6.Make certain that the current requirements of the controlled device do not exceed the
rating of the controller’s digital outputs.
Communications Hardware Checkout
In addition to functioning in standalone mode, the sLON-5 or sLON-6 controller may be
connected to a LONWORKS network for data sharing with other LONWORKS devices. If so,
check the status of its network communications according to the following procedure:
1. Verify that all controlled equipment is in a manually controlled, safe state.
2.Place the controller’s power circuit breaker in the ON position. See the job wiring
diagrams for the location of this breaker.
3.Observe the green Data Transmission LED (Figure-19) and do the following:
a. If the green Data Transmission LED is steady ON or blinking, go to step 4.
b. If the green Data Transmission LED is OFF, check the power to the controller.
4.Observe the red Service LED (Figure-19) and do the following:
a. If the red Service LED is off or flashing, proceed with downloading an application
using WPT Software Tool and configuring the controller with a third party network
management tool.
b. If the red Service LED is steady ON, turn OFF the power to the controller, wait five
seconds, then turn the power ON. If the red Service LED is still steady ON, turn the
power OFF and replace the controller.
5. If necessary, perform additional checks and take the appropriate corrective action,
according to Table-5.
firealarmresources.com

18 sLON-5, sLON-6 rev1 03/2005
Data Reception LED
(Amber)
Power and Data
Transmission LED
(Green)
Service LED
(Red)
Service Pin
LONWORKS
Network Jack
Figure-19 Location of Controller LEDs.
firealarmresources.com

sLON-5, sLON-6 rev1 03/2005 19
Table-5 LED Indication.
Indicator Context Status Corrective Action
Data Reception LED – amber Anytime
Blinks when the controller receives data from the
LONWORKS Network. None required.
On indicates a possible network connection problem, or
a large amount of network traffic is present.
Remove the LONWORKS Network
connections from the controller and
determine if the LED goes off. If the
LED does not go off, replace the
controller. If the LED does go off,
check the network topology (con-
nections to each node, routers, ter-
minators, etc.) and the amount of
traffic on the network.
Off indicates that data reception is not taking place.
None Required
Data Transmission LED –
Green Anytime
Blinks when the controller transmits data to the
LONWORKS Network.
On indicates that the controller is not transmitting data.
On also indicates that power is being applied to the
controller.
Off indicates no power to controller. Check power
Service LED – Red
Power-up The LED blinks once to indicate successful power-up.
None Required
Wink mode
Blinks (3 seconds on, 1 second off) three times to
indicate physical location of the controller. If a sensor
(sLON-WTSx) is connected, its red occupancy LED will
flash (1/sec) during the wink period.
Anytime On indicates that the neuron application is not running.
Neuron applications are not field replaceable. Replace the controller.
Anytime
Blinks (1/sec) to indicate that the neuron application is
loaded, but the neuron’s communication parameters
are not loaded, are being reloaded, or have been
corrupted. Neuron is considered unconfigured.
Communication parameters cannot be configured by
field personnel.
Use a third party network manage-
ment tool to commission the control-
ler, or use the change state tool in
WPT Software Tool (version 4.0 or
greater) to set the Neuron®to the
configured/on-line state.
While the controller is unconfigured,
WPT Software Tool can be used to
download an application, but at the
completion of the download, WPT
Software Tool versions 4.0 and
higher will restore the Neuron to the
unconfigured state.
Anytime
Off may indicate that the neuron application is loaded
but the device is off-line. In this state, a pre-loaded
HVAC application will not run.
Use a third party network manage-
ment tool to commission the control-
ler, or use the change state tool in
WPT Software Tool (version 4.0 or
greater) to set the Neuron to the
configured/on-line state.
While the controller is off-line, WPT
Software Tool can be used to
download an application, but at the
completion of the download, WPT
Software Tool versions 4.0 and
higher will restore the Neuron to the
off-line state.
Anytime
Off usually indicates a normal state. In this state, the
controller operates normally, and you can download
and/or run HVAC applications.
If the controller is able to accept
and/or run a downloaded HVAC
application, no action is required.
firealarmresources.com

sLON-5, sLON-6 rev1 03/2005 Solidyne Corporation - www.solidyne.com
© Copyright 2005 Solidyne Corp. All rights reserved.
No part of this document may be photocopied or reproduced by any means,
or translated to another language without prior written consent of Solidyne
Corporation.
All specifications are nominal and may change as design improvements are
introduced. Solidyne shall not be liable for damages resulting from
misapplication or misuse of its products.
Echelon, LON, Neuron, 3150, LONMARK and LONWORKS are trademarks of Echelon
Corporation registered in the United States and other countries.
Service
Components within the sLON-5 and sLON-6 controllers cannot be field repaired. If there is
a problem with the controller, follow the steps outlined in the “Checkout“ section. If the
problem persists, record the following hardware setup information before contacting
Solidyne Technical Support:
•Version number of the application software.
•The controller’s firmware version number.
•Information regarding the network management tool being used.
•A complete description of the difficulties encountered.
firealarmresources.com
This manual suits for next models
1
Table of contents
Popular Controllers manuals by other brands

halstrup-walcher
halstrup-walcher PSD4 Series instruction manual

Dometic
Dometic GP-MPPT-60/10 user manual

V2
V2 BLITZ-24V instructions

Becker
Becker Centronic UnitControl UC52 Assembly and operating instructions

ARAG
ARAG Bravo 3 Series ADDITION TO INSTRUCTION BOOKLET

IAI
IAI ROBO Cylinder RCP2 Series operating manual