11. Basic service and maintenance information
All units are thoroughly checked and tested by the manufacturer before dispatch. The most frequent errors root from
misunderstanding of the unit function or incorrect cabling and connection. For this, observe instructions from the manufacturer
to avoid complex troubleshooting. In no case try to operate the unit when connected in a different way - the unit may operate for
a while as you wish or expect but this irreversible step may result in damage beyond repair and loss. No warranty claims can be
accepted with respect to this damage.
The Li-Combi air units are made of quality materials that require no special maintenance. However, we recommend that
maintenance in required or shorter (depending on your observations due to operation in a specific application) intervals is carried
out for long lifecycle of the unit.
!!! Before any work with the unit, disconnect the electric power supply, mains supply for the unit. Electric shock hazard !!!
Observe generally applicable national provisions, particularly ČSN 12 2002 and other related regulations. Unplug the unit from
mains before any service intervention. Provisions of ČSN 332190, 332000-5-51 ed. 3, and 33 2000-5-54 ed. 3 must be observed
for connecting and earthing of the electric devices. Qualified electrician only may perform any electric service works (qualification
according to Decree of ČBU No. 50/78 Coll., § 6 is required).
Please contact your vendor or distributor for a service agreement. You will get regular service and excellent care of your unit.
Quarterly checks:
Unit hanging and tightening of all bolt connections. Check tightening of bolts of exhaust splines - accessible from
internal side wall of the unit, tighten the central splines by turning the splines (by tightening of the internal thread pin),
Heat exchanger space check and remove dirt or foreign objects (use vacuum cleaner for dedusting, or steam for stuck
dirt). When using steam for removal of dirt, always proceed downstream the air flow. Set as lowest temperature as
possible and as lowest steam pressure as possible for not to damage the heat exchanger,
Check cleanliness of the motor body and inner or outer parts of the unit. Do not wash the motor body with water!
Wipe with lukewarm towel only –motor winding damage hazard; after the motor is cleaned, do not turn the unit on
for at least 60 minutes - let the unit dry. Proceed carefully when wiping of the exhaust splines - fragile splines - danger
of damage!
before winter, check in particular the anti-frost protection function, superior circulating pump (not included in the
supply of the device), setting of electrothermic valve,*
re-test tightness of the unit or of installed fittings on the water side. If a sludge filter is installed before the unit –clean
the filter and check deaeration of the heat exchanger,
check unit safety with respect to electric shock hazard according to applicable ČSN or national standards, including
earthing inspection,
cleaning of the upper suction grid (use vacuum cleaner to remove dust or clean with a damp wipe). Clogged suction
grid may result in insufficient air flow through the heating bars located right under the grid, and consequently to
reduced air output or overheating of the device,
cleaning of the suction grid made from the expanded metal of fine structure (use vacuum cleaner to remove dust or
clean with a damp wipe). Clogged suction grid may result in insufficient air flow through the heat exchanger located
behind under the grid, and consequently to reduced air output of the device.