
INS_ASB/ASB-M-U 0611
MODELS “ASB-M”OPERATION
The ASB-M series duct heater modulates the electric element’s output according to the set point temperature in the duct. This model was specially developed to augment the heat
from a heat pump. However, It is possible to use this unit only, without any other heat source. In any case, the ultimate goal is to obtain a constant air temperature in the duct.
In order to achieve this, the control board reads the duct temperature and compares it to the set point chosen by the installer. The set point is adjusted via a rotating knob
accessible on the front of the unit. If the temperature read is below the set point, the electronic control activates the elements until the set point is achieved. If the duct air
temperature should pass the set point, the electronic control will deactivate the elements until the set point is achieved.
Three types of operating modes are possible: “ELECTRIC / ELECTRIC + HEAT PUMP”, “FOSSIL FUEL ONLY” and “ELECTRIC + EMERGENCY FOSSIL FUEL”. The button
on the control panel selects the heating mode. The modes, “ELECTRIC / ELECTRIC + HEAT PUMP” and “FOSSIL FUEL ONLY” are indicated by a light illuminated next to the
text. When both lights are illuminated, the unit is in “ELECTRIC + EMERGENCY FOSSIL FUEL” mode.
OPERATING OPTIONS
Electric / Electric + Heat Pump
When “Electric/ Electric + Heat pump mode” is selected, the duct heater only controls its own
heating elements. The duct heater, while the thermostat calls for a heat demand, modulates its
heat output to attain the required (duct) temperature. Electric + heat pump: If the heating system
incorporates a heat pump, both the heat pump and duct heater are controlled by the thermostat
heat demand. The duct heater modulated output complements the heat-pump output to achieve
the required (duct) temperature. (When electric/ electric + heat pump mode is selected, the “W”
terminal on the duct heater terminal block labelled “heat pump” should be free of any connection).
Fossil Fuel Only
When “Fossil Fuel Only mode” is selected, the duct heater only controls the fossil fuel furnace
heat output. To enable the fossil fuel only mode the W14 (stage) jumper must be set on 2.
Emergency Fossil Fuel
The “Emergency fossil fuel control mode” requires a one stage thermostat (W or Y signal) + emer-
gency mode (E signal). This control mode allows the thermostat to use the fossil fuel furnace as
a supplemental heat source. To enable the fossil fuel only mode the W14 (stage) jumper must be
set on 2. As with the electric/ electric + heat pump mode, the thermostat heat demands are con-
veyed to the duct heater (and heat pump if so equipped). However, if the duct heater/ heat pump
combined heat output is still insufficient the thermostat will redirect the heat demand to the fossil
fuel furnace. The emergency fossil fuel mode requires a double stage thermostat for the fossil
fuel furnace heat output is to be controlled by means of the thermostat second heating stage.
TROUBLESHOOTING ASB-M MODEL
PROBLEM DEFECTIVE PART OR PART TO CHECK
The unit does not work - Defective thermostat, wrong thermostat setting, positioning or wiring
- Open circuit breaker or fuse
- Faulty power supply connections
- Defective transformer
The unit has power but the elements do not work - Defective relay
- Tripped manual reset thermal cut-out
The unit runs continuously - Defective thermostat, wrong thermostat setting, positioning or wiring
- Heat losses greater than the heating capacity of the unit
Element operating and/or cycling continuously - Defective 24V relay (contact probably welded)
All the element operating and/or cycling when there is a heating demand - Defective furnace fan
- Obstructed Return and/or supply air
Unit is overheating - Defective furnace fan
- Obstructed Return and/or supply air
The breaker trips when the heater is turned on - Faulty power supply connections
- Voltage higher than that indicated on the nameplate
Unable to attain desired room temperature - One or more defective elements
- Defective thermostat, wrong thermostat setting, positioning or wiring
- Voltage lower than that indicated on the nameplate
- Heat losses greater than the heating capacity of the unit
- Defective 24V relay
- Tripped manual reset thermal cut-out
The Red “DIAGNOSTIC” pilot light is always on - The plenum’s temperature-sensor is defective or wrongly connected
The Red “DIAGNOSTIC” pilot light blinks every second n/a when “ELECTRIC”
option is selected)
- The control board has detected a malfunction in the “fossil fuel” mode. Verify the
burner and level of fuel.
The Red “DIAGNOSTIC” pilot light blinks four times every two seconds and
pause for two seconds
- The plenum’s air temperature is above 68°C (154.4°F)
- Dirty air filter or worn fan belt
The red “DIAGNOSTIC” pilot light blinks six times in 3 seconds and a pause for
3 seconds
- The “Y” signal is present along with the “W” signal
- Verify the thermostat programing
The red “DIAGNOSTIC” pilot light blinks 8 times in 4 seconds and a pause for
4 seconds
- The relay is cycling between proportional mode and stage mode for 12 hours. The
W4 jumper should be set to “T” and not to “R”
The red “DIAGNOSTIC” pilot light blinks 10 times in 5 seconds and a pause for
5 seconds
- The W1 jumper is set to “B” instead of “M”
- There is a signal on the “W” screw thermostat control board terminal
The red “DIAGNOSTIC” pilot light blinks 12 times in 6 seconds and a pause for
6 seconds
- The W14 jumper is set to “1” instead of “2”
- There is a signal from the second stage on the “W” screw pump control board termi-
nal
N.B. If you do not solve the problem after checking these points, cut off the power supply at the main electrical panel and contact our
customer service (see the “Limited warranty” section to obtain the phone numbers).
ASB-M SERIES USER INTERFACE