
12 | WPL 10 ACS WWW.STIEBEL-ELTRON.COM
INSTALLATION
MOUNTING
10.5 Filling the heating system
10.5.1 Water quality
Before the system is filled, a fill water analysis must be made
available. This may, for example, be requested from the relevant
water supply utility.
To avoid damage as a result of scaling, it may be necessary to
soften or desalinate the fill water. The fill water limits specified
in chapter “Specification / Data table” must always be observed.
Recheck these limits 8-12 weeks after commissioning and as
part of annual system maintenance.
Note
With conductivity of >1000μS/cm, desalination treatment
is recommended in order to avoid corrosion.
Note
If you treat the fill water with inhibitors or additives, the
same limits as for desalination apply.
Note
Suitable appliances for water softening, as well as for
filling and flushing heating systems, can be obtained via
trade suppliers.
10.5.2 Venting the heating system
Vent the pipework carefully. For this, also activate the air
vent valve integrated into the heating flow inside the heat
pump.
10.6 Minimum flow rate
When operating without a buffer cylinder, safeguard the minimum
flow rate specified in the following table as well as the defrost
energy.
Heat pump Minimum flow rate
WPL 10 AC / WPL 10 ACS 0.7 m³/h
Make the correct adjustments to the overflow valve.
Pump head
Pump head to be adjusted at the over-
flow valve*
6 m 4.1 m
7 m 5.1 m
8 m 6.1 m
*Relative to commercially available Wilo and Grundfos pumps.
Note
When installing a heat meter, note that most heat meters
cause a substantial pressure drop. Consequently, size the
circulation pump correspondingly larger.
10.7 Setting the flow rate on the heating side
!
Material damage
For operation without a buffer cylinder, it is essential
that the electric emergency/booster heater (DHC) is con-
nected.
The appliance is designed in such a way that no buffer cylinder
is required to provide hydraulic separation of the flow in the heat
pump circuit and the heating circuit in conjunction with area heat-
ing systems.
For installations with several heating circuits, we recommend the
use of a low loss header.
The setting is made in heat pump mode. For this, make the fol-
lowing settings first:
Operate the appliance in heating mode.
To do so, switch on the appliance using the parameter SET FIXED
TEMPERATURE in the COMMISSIONING menu.
10.7.1 Minimum flow rate with individual room control via
FEK/FE7 for systems without a buffer cylinder and
without a low loss header
For operation without buffer cylinder, make the following set-
ting at the WPM: In the menu SETTINGS / HEATING / STANDARD
SETTING, set parameter BUFFER OPERATION to OFF.
In such cases, one or more heating circuits in the heating system
must remain open. The open heating circuit(s) should be installed
in the lead room (room in which the external programming unit
is installed, e.g. the living room). Individual rooms can then be
controlled with the external programming unit or indirectly by
adjusting the heating curve or by activating room influence.
Fully open the heating circuit(s) in the lead room.
Close all other heating circuits.
If an overflow valve is installed in the heating system, close
this fully before determining the minimum flow rate.
Make the settings for the heating circuit pump so that the
minimum flow rate required for system operation is ensured
(see chapter „Specification/ Data table“).
The current flow rate can be called up in the menu INFO/ HEAT
PUMP/ PROCESS DATA, under WP WATER FLOW RATE.
10.7.2 Minimum flow rate for systems with buffer cylinder or
low loss header
For operation with buffer cylinder, make the following setting at
the WPM: In the menu SETTINGS / HEATING / STANDARD SET-
TING, set parameter BUFFER OPERATION to ON.
Make the settings for the heating circuit pump so that the
nominal flow rate required for system operation is ensured
(see chapter „Specification/ Data table“).
The current flow rate can be called up in the menu INFO/ HEAT
PUMP/ PROCESS DATA, under WP WATER FLOW RATE.
For operation without a buffer cylinder and with a low loss
header, ensure that the electric emergency/booster heater is
connected.