2
1 General
These installation instructions are for contrac-
tors. The heat pump installation also requires
the operating instructions of the heat pump
manager WPM.
The heating system heat pumps and the WPM
represent one function unit. Consequently,
their instructions are matched to each other.
Subject to the relevant system, observe the
installation instructions of the components of
which the system comprises.
1.1 Equipment description
~ 5^aUd[[hPdc^\PcXRWTPcX]V^UWTPcX]VfPcTa
to a flow temperature of 60 °C.
~ BdXcPQ[TU^ad]STa^^aWTPcX]VP]SaPSXPc^a
heating systems; preferred are low tempe-
rature heating systems, as these achieve
higher performance factors.
~ 4gcaPRcbT]TaVhUa^\cWTP\QXT]cPXa^dc-
side)
even at outside temperatures as low as –20
°C.
~ 2^\_aXbTbP[[R^\_^]T]cbaT`dXaTSU^aXcb
function and all safety equipment.
~ 2T]caP[R^]ca^[^UcWTWTPcX]VbhbcT\P]S
safety functions through the WPM heat
pump manager (required accessory, part no.
see section 1.6).
~ 2^aa^bX^]_a^cTRcTSTgcTa]P[RPbX]V\PST
from hot-dipped galvanised sheet steel plus
stove enamelled finish.
~ 2^\_PRcSTbXV]cWTaTU^aT\^STbcb_PRT
requirements for interior or exterior instal-
lations.
~ CTbcbh\Q^[^UX]ST_T]ST]ccTbcQ^SXTb
(see type plate).
~ 5X[[TSfXcW]^]R^\QdbcXQ[TbPUTchaTUaXVT-
rant R407C.
1.2 Function
Heat is extracted from outside air with tem-
peratures ranging from + 30 °C to –20 °C by
the heat exchanger on the air side (evapo-
rator). Heating water is heated in the heat
exchanger on the water side (condenser) to
flow temperature levels by this extracted heat
and added heat from the electrical power
used by the compressor. At air temperatures
below approx. +7 °C, the humidity in the air
condenses as hair-frost on the evaporator fins.
This hair-frost is automatically removed. Any
water created from this defrosting is caught
in the defrost basin and drained off via a hose
(Fig. 7 and 8).
The fan is switched OFF and the heat
pump circuit is reversed to enable
the defrost phase. The energy required for
defrosting is drawn from the buffer cylinder.
For that reason, operation without a buffer
cylinder is not permissible, otherwise
unfavourable conditions could lead to the
heating water freezing up.
The heat pump automatically reverts to heat-
ing mode at the end of the defrost phase.
1.3 Correct operation
The heat pump is designed for extracting en-
ergy from the air and for
utilising this energy in water-based
heating systems within the stated operating
temperature range.
1.4 Incorrect operation
The installation location must be prepared by
your contractor in line with section 3.2. Never
operate the heat pump in areas at risk from
explosions or outside the stated operating
temperature range.
1.5 Regulations and standards
Observe the following regulations and stan-
dards during assembly and installation.
On the water side:
DIN EN 12828
Safety equipment for hot water heating systems
DIN 1988: Technical rules for DHW installations
TRD 721: Safety equipment to prevent excess pres-
sure - safety valves
On the electrical side:
DIN VDE 0100: Regulations for the installation of HV
systems with rated voltages up to 1000 V.
VDE 0701: Regulations regarding the repair, modifi-
cation and testing of used electrical equipment.
VDE 0298-4
TAB: Technical connection conditions for connections
to the LV mains.
On the refrigerant side:
EN 378: Safety and environmental requirements
DIN 7003: (draft)
General:
Collation of technical requirements for boiler rooms,
e.g. boiler room guidelines or national/local Build-
ing Regulations, commercial and fire as well as
emission control regulations and requirements.
TA Lärm: Technical instructions to protect against
noise emissions
Installation instructions for contractors
1.6 Standard delivery and accessories
Type WPL 33
Standard delivery – external installation Part no.
–Base unit 18 53 48
–Accessories (comprising the casing). 18 53 69
Standard delivery – internal installation Part no.
–Base unit 18 53 48
–Accessories (comprising the casing) 18 53 68
Special accessories - internal installation Part no.
Air hose with thermal insulation, 3 m 16 80 80
Air hose with thermal insulation, 4 m 16 80 81
Hose connection plate 00 34 78
Condensate pump PK9 18 21 38
Special accessories – external and internal installation (required) Part no.
Heat pump manager with wall mounting enclosure, WPMW II 18 54 50
Heat pump manager as control panel mounted version, WPMS II 18 54 51
Cylinder SBP 200 E 18 54 58
Cylinder SBP 400 E 22 08 24
Cylinder SBP 700 E 18 54 59
Special accessories – external and internal installation Part no.
Mixer module with wall mounting enclosure, MSMW 07 45 19
Mixer module as control panel mounted version, MSMS 07 45 18
Pressure hose G 1¼“ x 1 m (DN32) 07 44 14
Pressure hose G 1¼“ x 2 m (DN32) 18 20 19
Pressure hose G 1¼“ x 5 m (DN32) 18 20 20
Hose fitting for pressure hoses 5 m 07 06 92
Heat pump Compact Installation WPKI 5 22 08 30
UP kit 25 - 60 (for WPKI 5) 07 43 25
UP kit 25 -80 (for WPKI 5) 07 43 16
Remote control for heating system FE 7 18 55 79
Contact sensor AVF 6 16 53 41
Immersion sensor TF 6 16 53 42