To start the syste , press the COOL key. Controller starts the BLOWER and COND FAN 1,2 and
3 enter time delay mode. COND FAN1 activates after 60 seconds COND FAN2 after 90 seconds
and COND FAN3 after 120 seconds
After COND FAN 1 activates, COMP 1 energizes ten seconds later to avoid a s rge.
After COND FAN 2 activates, COMP 2 energizes fifteen seconds later to avoid a s rge.
After COND FAN 3 activates, COMP 3 energizes twenty five seconds later to avoid a s rge.
Once set point has been achieved, all devices except blower go off.
For example SP is 23, once this is achieved, all devices will go off. Then at 23(SP) + 1 = 240C, the
time delay starts and cycle contin es in a similar manner
To change the Set Point, press the p / dn key. The 7-segment LED will display the c rrent set
point and flash. Whilst the display is flashing, se the Up/Dn key to achieve the desired Set Point.
Once the req ired Set Point is achieved, the display will confirm that the new Set Point has been
saved into memory by displaying “--“ and will ret rn to normal mode.
If setpoint is not changed, controller will ret rn to normal condition after 15 seconds.
Both the cooling nit (comp. + cond . fan) are switched off at Set Point.
As temperat re + differential are achieved, all the three nits will come on after a set time delay.
At power on, the controller will check for Blower O/L error. If the stat s is OK,. the controller will
activate the Blower.
After activating the blower, if the temperat re is eq al to or above Set Point + Differential, fan time
delays will activate together.
System always checks for COND FAN and COMP O/L and HP/LP fa lts.
On power off , system saves the last mode, so that on power on it will come on in the same mode .
Incase of any fa lt, corresponding cooling nit (compr+ cond fan) will switch off. While other nit
contin es to work normally.
HP/LP fa lt has a man al reset . To reset the fa lt press cool b tton. It will restart that nit with
time delay.
Display will indicate corresponding fa lt.
For eg incase of COND FAN O/L error, display will show “OL” and COND FAN 1 red led will
blink .
Green led indicates active stat s ( blinks while in time delay and lights p for on condition)
Red led indicates inactive stat s (blinks for errors and light p for off condition)
LED Indication :
Red led on- off stat s
Red led blink- fa lt condition
Green led on- on stat s
Green led blink- delay stat s
Yellow led on- CCH on stat s