Super Systems AC50 User manual

1unit of measurement
2 state of outputs OUT1 OUT2 OUT3 OUT4
3
controller function states:
* man = manual/automatic (off=automatic control, on = manual control);
* rem = remote setpoint enabled
4
selects auto or manual control from the home screen.
pressing the key returns you to the previous menu item or to the higher menu level, as appropriate.
hold for 2 seconds to return to the main menu
5 navigate through user menu
6 probe test and burnoff key
7 up / down key
8
hold for more than 2 seconds to enter the conguration menus.
navigates among controller menus and parameters, conrms parameter value,
and selects next parameter
9 key pressed signals
10 displays percentage of power output
11 display of percentage of process variable and of setpoint
12 parameters, diagnostics and alarm messages.
13 sv display: parameter values. congurable with parameter ds.sp
(default = setpoint).
14 pv display = process variable
AC50 Quick Start Guide
Display DiagramDisplay Functions
1
2

A/M
Selects Auto or Manual control from the home screen. Pressing the key returns you to the
previous menu item or the higher menu level, as appropriate. Hold for 2 seconds to return to
the Main menu.
FUN Navigate through user menu
TST TST+A/M = start burnoff
TST + FUN = start probe test
Press to raise the value of the displayed parameter.
Hold to progressively increase the speed of raising the displayed parameter.
Press to enter a submenu or to reduce the value of the displayed parameter,
as appropriate.
Hold to progressively increase the speed of reduction of the displayed parameter.
MEN Hold for 2 seconds to enter the conguration menus. Navigates among controller menus and
parameters, conrms parameter value and selects next parameter.
TO CHANGE PROCESS SETPOINT
when device is in auto control, press or until desired setpoint is reached.
in manual mode, change the power output using the up or down arrow
TO CHANGE CO FACTOR:
Press FUN key to cycle user menu until the COF parameter is displayed
Adjust the parameter with or
Press FUN key to conrm selection
Hold A/M key to return to home screen or let device return home after 15 seconds
TO CHANGE H2 FACTOR:
Press FUN key to cycle user menu until the H2F parameter is displayed
Adjust the parameter with or
Press FUN key to conrm selection
Hold A/M key to return to home screen or let device return home after 15 seconds
TO CHANGE BURNOFF TIMER AND FREQUENCY:
Hold MEN button until display shows PASSQ
Enter quickmenu password if set (SSi default password = 5)
Press MEN button to cycle parameters until B.TIME is reached
Use arrow keys to adjust time (units are in seconds)
Press MEN key to conrm selection and advance to B.FREQ parameter
Use arrow keys to adjust time (units are in seconds)
Press MEN key to conrm selection
Hold A/M to return home
TO PERFORM A PROBE BURNOFF
From the home screen, press FUN button once to reach carbon state menu
Simultaniously press the TST and A/M buttons, burnoff will be initiated if there are no
inhibiting factors. Probe burnoff can be cancled by holding up and down keys simultaniously
TO PERFORM A PROBE DIAGNOSTIC
from the home screen, press FUN button once to reach carbon state menu
simultaniously press the TST and FUN buttons, probe test will be inititiated if there are no
inhibiting factors
AC50 Quick Start Guide
Keyboard Description
3
Basic Functionality
4

PARAMETER DESCRIPTION
TYPE_1 shows and sets thermocouple type for main input
F.OUT_1 shows and sets the function of output 1
F.OUT_2 shows and sets the function of output 2
F.OUT_3 shows and sets the function of output 3
F.OUT_4 shows and sets the function of output 4
TYPE_1 shows and sets the function of analog output 1
FUNC_1 shows and sets the function assigned (retransmission of values) to analog output 1
TYPE_2 shows and sets the function of analog output 2
FUNC_2 shows and sets the function assigned (retransmission of values) to analog output 2
H.PB_1 shows and sets the proportional heating band
H.IT_1 shows and sets the integral heating time
H.DT_1 shows and sets the derivative heating time
C.PB_1 shows and sets the proportional cooling band
C.IT_1 shows and sets the integral cooling time
C.DT_1 shows and sets the derivative cooling time
B.TIME shows and sets the duration in seconds of the air blowing phase during a burnoff
B.FREQ shows and sets the automatic burnoff repetition frequency in minutes
D.FREQ shows and sets the frequency of automatic diagnostics repetition, in minutes
STAT_3 shows and sets the state of the digital input
CODE shows and sets the identifying code of the controller in a modbus serial network
KBAU shows and sets the communication speed for the serial port.
PAR shows and sets the parity used in serial communication.
IP.AD1 shows the ip 1 address identifying the controller in an ethernet network.
the parameter is the rst eld in the complete ip address (xxx.xxx.xxx.xxx)
IP.AD2 shows the ip 2 address identifying the controller in an ethernet network.
the parameter is the second eld in the complete ip address (xxx.xxx.xxx.xxx).
IP.AD3 shows the ip 3 address identifying the controller in an ethernet network.
the parameter is the third eld in the complete ip address (xxx.xxx.xxx.xxx).
IP.AD4 shows the ip 4 address identifying the controller in an ethernet network.
the parameter is the fourth eld in the complete ip address (xxx.xxx.xxx.xxx).
SUB.M1 shows the subnet mask 1 identifying the controller in an ethernet network.
the parameter is the rst eld in the complete subnet mask (xxx.xxx.xxx.xxx).
SUB.M2 shows the subnet mask 2 identifying the controller in an ethernet network.
the parameter is the second eld in the complete subnet mask (xxx.xxx.xxx.xxx).
SUB.M3 shows the subnet mask 3 identifying the controller in an ethernet network.
the parameter is the third eld in the complete subnet mask (xxx.xxx.xxx.xxx).
SUB.M4 shows the subnet mask 4 identifying the controller in an ethernet network.
the parameter is the fourth eld in the complete subnet mask (xxx.xxx.xxx.xxx).
AC50 Quick Start Guide
TO ENTER QUICK SETUP MENU:
Hold MEN button until display shows PASSQ
Use or to enter password if set (SSi default password = 5)
Press MEN button again to enter menus.
Continue pressing MEN to cycle through menu options.
To exit menu, hold A/M until home screen appears,
or press MEN to cycle through menu options to return to the home screen.
Quick Setup Menu
5

MENUS UNDER PASS1
INFO
INFO ETHERNET
INFO CARBON POTENTIAL
CP SET
BURNOFF SET
PROBE DIAGNOSTIC SET
ANALOG INPUTS
ALARM
PID
AC50 Quick Start Guide
PASS1 and PASS2 Menus
6
After the nal PASS1 menu option, you will
be prompted to enter the password to
access PASS2 options.
Use or as above.
(SSi default password = 5) MENUS UNDER PASS2
DIGITAL INPUTS
OUTPUT
ANALOG OUTPUT
SERIAL
ETHERNET
PASC0
PASC1
PASC2
Hold MEN button until display shows the
desired menu (PASS1 or PASS2)
Use or to enter password if set
(SSi default password = 5)
Press MEN button again to enter menus.
Continue pressing MEN
to cycle through menu options.
Continue pressing MEN
to cycle through menu options.
To exit menu, hold A/M
until home screen appears,
or press MEN
to cycle through menu options
to return to the home screen.
This manual suits for next models
2
Popular Controllers manuals by other brands

BN Thermic
BN Thermic WD16 instructions

ELREHA
ELREHA MSR 100 Series Technical manual

SOMFY
SOMFY animeo installation guide

ABB
ABB COM600 series User's & technical manual

Mitsubishi
Mitsubishi MELSEC-L Series Programming manual

Rockwell Automation
Rockwell Automation Allen-Bradley PowerFlex 7000 installation instructions