
Aqua-Gen 2 INSTRUCTIONS
DESCRIPTION:
The Aqua-Gen 2 is an entry range automatic solar controller with temperature adjustment, manual
mode and winter mode features. Mode of operation and the temperature limit setting are retained after
a power outage.
CONTROLLER INSTALLATION:
Find a suitable location to mount the control box. The controller must be installed out of direct weather
and no closer than 3m from the waters edge. Lift up the two mounting tabs and use two appropriate
screws to mount the control box to the wall, keeping in mind that the power cable is 1.8m long and
should be plugged directly into a general power outlet, not into an extension lead.
The solar pump plugs into the 240Vac socket marked as PUMP.
The pool sensor must be fitted into the suction line of the pump, as close to the pool as practical,
preferably in a position out of direct sunlight. It is recommended that a 14.5mm hole be drilled in the
PVC pipe, this can be carried out using a Dontek PD01 grinding drill or a small pilot hole can be drilled
and a 14.0mm drill-bit used spinning in a counter clockwise direction to minimise the chance of
shattering pipe. Insert the grommet into the pipe and gently push in the black sensor barb. The green
sensor plug is to be fitted to the plug socket marked POOL.
DO NOT cable-tie or tape sensor wires to mains power. In some cases there is some benefit to cable
tie 30cm of wire from the sensor to the pipe and insulate this section (some ambient differences can
travel up the copper wire and affect the sensor reading).
Roof sensors must be fitted into a small piece of solar collector or equivalent and attached to the roof.
The best location is within arms length of the gutters edge of the house or shed as long as the sensor
end is not shaded and is on a roof of similar aspect of the main collector. It must not be fitted on top
of the solar collector or fitted to high points on the roof like Ridge Capping as false readings will be
detected.
Keep in mind that it is of the utmost importance to keep the roof sensor as short as possible as this will
assist in the longevity of the sensor and controller in the event of electrical storm activity and power
surges. Sensor cables must not be run parallel to power cables and run lengths should be less
than 50m. Cable ties should be used to fasten the sensor cable to the cold water inlet pipe making
sure that the ties are approximately 10mm from PVC fittings. Cable ties should be tightened only firm,
over tightening can cause breaks in the outer PVC if not careful. If the cable is to be run under ground
a conduit must be used to protect the wire and there is to be no cable joins within, conduit ends must
be sealed to prevent water ingress. Any excess cable should be removed and re-fitted ensuring
that the wire ends are tinned with solder. The sensor plug is to be fitted to the right hand socket
marked ROOF.
NOTES:
1. If a sensor fault is detected the controller will display which sensor failed (POOL and/or ROOF)
and the type of failure.
2. Should power be interrupted for any reason, the controller will resume normal operation when
power is restored, all information will have been kept.