09
Installation and Connection
Installation Safety Notes
The manufacturer supplies the heat pump only. All other components, including a bypass,
must be provided by the installer or user.
ATTENTION
The following instructions must be followed when installing the heat pump.
1. Sanitation and automatic dosing systems must be plumbed after the heat pump. A check
valve must be installed between the sanitation/automatic dosing system and the heat pump
to prevent chemicals returning to the heat pump.
2. A bypass must be installed for the use of heat pumps.
3. Always place the heat pump on a solid foundation and use the included rubber mounts to
avoid vibration and noise.
4. Always hold the heat pump upright. If the unit has been held at an angle, wait at least 24
hours before starting the heat pump.
5. For optimum performance the ow rate must match specications provided by the manufacturer.
6. For indoor installation, please consult your installer.
7. In areas subject to sub zero temperatures, the heat pump must be de-commissioned during
the winter months. To do this, the drainage plug must be removed from the heat pump to
allow water to drain from the heat exchanger. Once the water has been drained from the unit,
the drainage plug can be re-installed for use of the heat pump.
Heat Pump Location
For optimum performance ensure good ventilation, stable and reliable power supply and ensure
swimming pool lters are present.
The unit may be installed in virtually any outdoor location as long as the specied minimum
clearances to other objects are maintained (as per the following diagram).
ATTENTION
Never install the unit in a closed room with limited air volume in which the air
expelled from the unit will be re-used, or close to shrubbery that could block
the inlet. Such locations impair the continuous supply of fresh air, resulting in
reduced eciency and possible prevention of sucient heat output, which
will void the compressor warranty.
See drawing on the following page for minimum clearance dimensions.