
GB.COOLDX.SI.G.190603
We reserve the right to alter specifications.
4 www.swegon.com
Function
There are two refrigerant circuits in the chiller. The circuits
are separated from one another.
Each circuit is equipped with its own finned condenser,
finned evaporator and compressor.
The two compressors are of different capacity, which
makes it possible to regulate the capacity in 3 steps.
COND
VSH2
M1 M2
EVAP
VET1VET2
IPL1IPL2
FD1FD2
COND Condenser
VSH1 Overpressure protection
VSH2 Overpressure protection
B1-1 High pressure sensor
B2-1 Low pressure switch
B1-2 High pressure sensor
B2-2 Low pressure switch
BP1-2 High pressure switch, alarming
BP2-2 High pressure switch, alarming
M1 Compressor
M2 Compressor
M3 Compressor (size 80, cap. var. 3)
EVAP Evaporator
VET1 Expansion valve with thermostat
VET2 Expansion valve with thermostat
IPL1 Sight glass, cooling medium circuit 1
IPL2 Sight glass, cooling medium circuit 2
FD1 Filter dryer
FD2 Filter dryer
B2-2
HP
The gaseous refrigerant is compressed by cooling com-
pressors M1 and M2 and from there flows to condenser
COND, where it is cooled by the extract air and is con-
densed to liquid form.
The gaseous refrigerant flows through expansion valve
VET1 and VET2, where the pressure and the temperature
decrease.
From the expansion valves, the refrigerant advances to
evaporator EVAP, where the refrigerant evaporates and
cools down the outdoor air.
The evaporated refrigerant flows from evaporator EVAP
further to the suction side by the compressors to once
again be compressed.
Regulation
The cooling capacity is regulated in three binary steps by
having one or two compressors in operation.
COOL DX is controlled via a signal, 0 – 10 V.
Step 1: When cooling is needed, Compressor M1 is start-
ed.
Step 2: If more cooling is needed, Compressor M2 starts
and at the same time Compressor M1 stops. An adjust-
able time delay (a step duration of 250 seconds) ensures
that Compressor M2 will not start until Compressor M1 is
operating at full capacity.
Step 3: If even more cooling is needed, Compressor M1 is
restarted and is run at the same time as Compressor M2.
This third cooling step is also delayed by a preset time de-
lay setting. In addition, the restarting time (300 seconds)
for Compressor M1 shall have expired.
If less cooling is needed and the compressors are subse-
quently switched out step-by-step, there will be no delay
between compressors. The restarting time (300 seconds)
for Compressor M1 shall have expired to enable it to start
again in Step 1 after it has been operated in Step 3.
If any compressor is stopped, the restarting time must
expire before a restart can take place. The restart time is
calculated from one start to the next start.
If the pressure in the cooling circuit becomes too low, or
if the pressure in the condenser circuit becomes too high,
the compressor is stopped.
When the restart time has expired, the compressors will try
to restart.
If the pressure increases more, high pressure switches BP1-
2 and BP2-2 will trip and stop the chiller.
Alarms are shown on the hand-held terminal, see separate
instructions for IC208CX control.
Pressure switches BP1-2 and BP2-2 can be manually reset
by pressing a button under each protective sock on the
upper side of the pressure switch. This can be done with-
out removing the protective sock.
1.2 Basic function diagram
B1-2
LP
HP
B2-1
HP
B1-1
LP
HP
BP2-2BP1-2
VSH1
M3