Swegon COOL DX 008 User manual

GB.COOLDX.SI.G.190603
Chiller COOL DX version G
Installation and Maintenance Instructions
SILVER C, size 008-080
The document was originally written in Swedish.
COOL DX

GB.COOLDX.SI.G.190603
We reserve the right to alter specifications.
2 www.swegon.com
CONTENTS
1. Overview 3
1.1. General 3
1.2 Basic function diagram 4
2 Safety Instructions 5
2.1 Safety Isolating Switch/Main Switch 5
2.2 Risks 5
2.3 Electrical equipment 5
2.4 Authorisation 5
2.5 Decals 5
3 Installation 6
3.1 Unloading/site transport 6
3.1.1 Handling with truck 6
3.1.2 Handling with crane 6
3.2 Arrangement 6
3.3 Basic Installation Diagram COOL DX 7
3.3.1 Height adaptation to SILVER C/water trap 8
3.3.2 Connection to SILVER C air handling unit,
COOL DX, sizes 008-012 9
3.3.3 Connection to SILVER C air handling unit,
COOL DX, sizes 020-040 10
3.3.4 Connection to SILVER C air handling unit,
COOL DX, sizes 060-080 11
3.3.5 Stand-alone COOL DX 11
3.3.6 Supply air filter 11
4 Power connection 12
4.1 Supply connection 12
4.2 Connection of signal, 0 – 10 V 12
5 Commissioning 13
5.1 Preparations 13
5.1.1 Before initial start up 13
5.1.2 Control functions 13
5.1.3 Pressure sensor 13
5.1.4 Phase sequence monitor 14
5.1.5 Measure whether the phase-sequence is wrong 14
6 Alarms 14
7 Maintenance 15
7.1 Cleaning 15
7.2 Handling of refrigerant 15
7.3 Leakage tracing interval/Obligation to report 15
7.4 Service 15
8 Trouble shooting and leakage tracing 16
8.1 Troubleshooting Schedule 16
8.2 Leakage Tracing 16
9 Dimensions 17
10 General technical data 18
11 Internal wiring diagram 19
12 Commissioning Record 23

GB.COOLDX.SI.G.190603
We reserve the right to alter specifications. www.swegon.com 3
Refrigerant
The COOL DX has double refrigerant circuits, which are
separate from each other. Type R410A refrigerant is used.
The refrigerant circuits are charged with refrigerant on
delivery. At present, this refrigerant has no known influ-
ence on the ozone layer and no known future restrictions
are anticipated.
Refrigerant volume
See section 10. General technical data.
Installation check/Obligation to report/
Leakage tracing interval
Must be carried out according to the F-Gas Regulation
EU/517/2014 and associated local legislation.
Quality System to ISO 9001
and Environmental Management System to ISO
14001
Swegon AB works to a certified quality system that con-
forms to ISO 9001 standard and a certified Environmental
Management System that conforms to ISO 14001.
1. OVERVIEW
1.1. General
COOL DX Chiller
Chiller COOL DX is a complete chiller for comfort cooling
in the air handling system. All the components refrigera-
tion engineering-wise and electrically pre-wired and col-
lected inside a common casing. The outer skin is made
of galvanized sheet steel, pre-painted in Swegon’s grey
metallic colour (closest comparable: RAL, 9007). The inner
skin material is aluminium-zinc coated sheet steel. Envi-
ronmental class C4. Panel thickness of 52 mm with inter-
vening insulation consisting of mineral wool.
The cooling coil and condenser are fabricated of copper
tubing and profiled aluminium fins; the casing is made of
galvanized sheet steel.
The chillers are test run prior to delivery.
The COOL DX is available in 19 capacity variants spread
on nine physical sizes, designed for use with the size 008 -
080 SILVER C air handling units.
Compressors
The compressor in the COOL DXchiller is of scroll compres-
sor type and/or rotary compressors.
Completely direct-acting system
The COOL DX has a completely direct-acting system. It has
an evaporation coil for direct-evaporating refrigerant on
the cold side and a condenser coil on the hot side.

GB.COOLDX.SI.G.190603
We reserve the right to alter specifications.
4 www.swegon.com
Function
There are two refrigerant circuits in the chiller. The circuits
are separated from one another.
Each circuit is equipped with its own finned condenser,
finned evaporator and compressor.
The two compressors are of different capacity, which
makes it possible to regulate the capacity in 3 steps.
COND
VSH2
M1 M2
EVAP
VET1VET2
IPL1IPL2
FD1FD2
COND Condenser
VSH1 Overpressure protection
VSH2 Overpressure protection
B1-1 High pressure sensor
B2-1 Low pressure switch
B1-2 High pressure sensor
B2-2 Low pressure switch
BP1-2 High pressure switch, alarming
BP2-2 High pressure switch, alarming
M1 Compressor
M2 Compressor
M3 Compressor (size 80, cap. var. 3)
EVAP Evaporator
VET1 Expansion valve with thermostat
VET2 Expansion valve with thermostat
IPL1 Sight glass, cooling medium circuit 1
IPL2 Sight glass, cooling medium circuit 2
FD1 Filter dryer
FD2 Filter dryer
B2-2
HP
The gaseous refrigerant is compressed by cooling com-
pressors M1 and M2 and from there flows to condenser
COND, where it is cooled by the extract air and is con-
densed to liquid form.
The gaseous refrigerant flows through expansion valve
VET1 and VET2, where the pressure and the temperature
decrease.
From the expansion valves, the refrigerant advances to
evaporator EVAP, where the refrigerant evaporates and
cools down the outdoor air.
The evaporated refrigerant flows from evaporator EVAP
further to the suction side by the compressors to once
again be compressed.
Regulation
The cooling capacity is regulated in three binary steps by
having one or two compressors in operation.
COOL DX is controlled via a signal, 0 – 10 V.
Step 1: When cooling is needed, Compressor M1 is start-
ed.
Step 2: If more cooling is needed, Compressor M2 starts
and at the same time Compressor M1 stops. An adjust-
able time delay (a step duration of 250 seconds) ensures
that Compressor M2 will not start until Compressor M1 is
operating at full capacity.
Step 3: If even more cooling is needed, Compressor M1 is
restarted and is run at the same time as Compressor M2.
This third cooling step is also delayed by a preset time de-
lay setting. In addition, the restarting time (300 seconds)
for Compressor M1 shall have expired.
If less cooling is needed and the compressors are subse-
quently switched out step-by-step, there will be no delay
between compressors. The restarting time (300 seconds)
for Compressor M1 shall have expired to enable it to start
again in Step 1 after it has been operated in Step 3.
If any compressor is stopped, the restarting time must
expire before a restart can take place. The restart time is
calculated from one start to the next start.
If the pressure in the cooling circuit becomes too low, or
if the pressure in the condenser circuit becomes too high,
the compressor is stopped.
When the restart time has expired, the compressors will try
to restart.
If the pressure increases more, high pressure switches BP1-
2 and BP2-2 will trip and stop the chiller.
Alarms are shown on the hand-held terminal, see separate
instructions for IC208CX control.
Pressure switches BP1-2 and BP2-2 can be manually reset
by pressing a button under each protective sock on the
upper side of the pressure switch. This can be done with-
out removing the protective sock.
1.2 Basic function diagram
B1-2
LP
HP
B2-1
HP
B1-1
LP
HP
BP2-2BP1-2
VSH1
M3

GB.COOLDX.SI.G.190603
We reserve the right to alter specifications. www.swegon.com 5
2 SAFETY INSTRUCTIONS
2.1 Safety Isolating Switch/Main Switch
The safety isolating switch is positioned on the inspection
side of the chiller.
The safety switch should not be used for start or stop of
the chiller.
Ensure that COOL DX is shut-off by turning off the chiller
via the display.
When this has been carried out, the current can be iso-
lated with the safety switch. The safety switch must be
switched off in order to make it possible to open the
inspection door.
Important:
Always switch off the safety isolating switch before ser-
vicing the unit if not otherwise specified in the pertinent
instructions.
2.2 Risks
Warning
Before carrying out any work, make sure that the power
supply to the air handling unit has been switched off.
Warning
Under no circumstances may the refrigerant circuit be
opened by unauthorised personnel, since it contains gas
under high pressure.
Risk areas with refrigerant
Risk area for refrigerant is in principal inside the entire
chiller.
For handling when leakage, see section 7.2.
Refrigerant used is R 410A.
Warning
The unit’s inspection door must not be opened when
the SILVER C air handling unit is operational. The door
can open and injure personnel. (The safety switch on the
COOL DX must be switched off in order to make it pos-
sible to open the inspection door of the chiller.)
2.3 Electrical equipment
The machine’s electrical equipment is housed in a separate
cabinet inside one of the inspection doors.
2.4 Authorisation
Only authorized electricians shall be permitted to install
electrical wiring in the unit.
Only an accredited refrigeration company shall be permit-
ted to modify or repair the refrigeration circuit.
Other service work in the unit should only be performed
by service personnel trained by Swegon.
2.5 Decals
The type number mark with type designation, serial num-
ber, refrigerant volume and more is affixed on the chiller’s
door.
Type designation: COOLDX-aa-F-c-d-e-f-g
SILVER C size
Capacity variant

GB.COOLDX.SI.G.190603
We reserve the right to alter specifications.
6 www.swegon.com
3 INSTALLATION
3.1 Unloading/site transport
Important:
All transport should take place with the chiller in hori-
zontal position.
3.1.1 Handling with truck
Warning
High centre of gravity! Lift the chiller carefully.
3.1.2 Handling with crane
Place two line spreaders on top of the chiller and two on
the underside of the pallet or below the chiller and lift in
the pallet (or the chiller if the pallet is not to be included).
See the illustration.
3.2 Arrangement
Place the COOL DX at a suitable location.
Safety isolating switch/main switch must have the requi-
site space to serve according to applicable electrical regu-
lations.
The unit can stand with the back against the wall, but to
facilitate any service of the rear compressor, a distance of
about 1 metre is recommended.

GB.COOLDX.SI.G.190603
We reserve the right to alter specifications. www.swegon.com 7
3.3 Basic Installation Diagram COOL DX
Locate the COOL DX chiller against the outdoor air and
exhaust air side of the SILVER C air handling unit. COOL
DX can also be installed as a stand-alone unit, if you order
a stand-alone COOL DX, select the variant with end con-
nection panels.
The dimensions and capacity of the chiller COOL DX is
matched for connection to the SILVER C air handling unit
in sizes 008-080.
For a list of the capacity sizes of chillers matched to re-
spective unit size, see section 10. General technical data.
COOL DX 008
COOL DX 012-080
Right-hand version Left-hand version
Cooling coil in lower level/SILVER C fan arrangement 1 Cooling coil in upper level/SILVER C fan arrangement 2
Cooling coil in upper level/SILVER C fan arrangement 1 Cooling coil in lower level/SILVER C fan arrangement 2
Right-hand version
Left-hand version
Outdoor air Supply air Extract air Exhaust air

GB.COOLDX.SI.G.190603
We reserve the right to alter specifications.
8 www.swegon.com
3.3.1 Height adjustment to the height of the SIL-
VER C/water trap
COOL DX, size 008
In combination with the SILVER C RX 08
The SILVER C air handling unit can be mounted on base
beams, a stand or some other form of foundation. Base
beams and stands are available as accessories.
Appropriate base beams and stands are also available as
accessories for the COOL DX. The base beams/stands are
matched to one another in terms of height. The stands
also provide space for accommodating a possible water
trap in the lower level (right-hand unit version).
In combination with the SILVER C PX 008
The air handling unit is supplied with base beams. A set of
legs (accesssory) can be mounted in the base beams.
Appropriate base beams and set of legs are also available
as accessories for the COOL DX. The base beams/sets of
legs are matched to one another in terms of height. The
sets of legs also provide space for accommodating a pos-
sible water trap in the lower level (right-hand unit version).
COOL DX, sizes 012-080
The SILVER C air handling unit and the COOL DX cooling
unit are supplied with a 100 mm high base beam.
Applicable to a cooling coil in the lower level:
If a water trap (accessory) is fitted, the SILVER C air han-
dling unit and the cooling unit must be raised at least 50
mm to provide space for the water trap. Adjustable sup-
port feet (accessories) can be appropriately fitted to the
base beams for this purpose.

GB.COOLDX.SI.G.190603
We reserve the right to alter specifications. www.swegon.com 9
3.3.2 Connection to SILVER C air handling unit,
COOL DX, sizes 008-012
The sealing strips are factory-fitted to the unit.
The chiller is connected directly to the air handling unit by
means of the supplied bolts + pre-fitted rivets nut and 2
expansion locking devices, see the figure.
Secure the chiller to the air handling unit from inside the
unit via the inspection door. It may be necessary to remove
the fan assembly or filter cassettes in order to reach the
expansion-type locking device.
Expansion-type locking device
In this case, fastening is done with the bolts and
pre-fitted rivet nuts.
COOL DX Chiller

GB.COOLDX.SI.G.190603
We reserve the right to alter specifications.
10 www.swegon.com
3.3.3 Connection to SILVER C air handling unit,
COOL DX, sizes 020-040
The sealing strips are factory-fitted to the unit.
Dock the chiller directly to the SILVER C air handling unit
by means of the supplied bolts (4 bolts) + pre-fitted rivet
nuts.
In this case, fastening is done with the bolts supplied and pre-fitted rivet nuts in
predrilled holes.
Option 1
If there is sufficient space for working from the rear of the
air handling unit, the simplest way to secure the chiller at
the rear edge of the SILVER C air handling unit is by exter-
nally jointing it, see Illustration 1.
Secure the chiller to the front edge of the SILVER C air
handling unit within the unit via the inspection cover, see
Illustration 3.
Option 2
The chiller is secured to the back edge of the SILVER C
air handling unit within the casing, see Illustration 2. This
requires removal of the fan assembly and filter cassettes.
Secure the chiller to the front edge of the SILVER C air
handling unit within the unit via the inspection cover, see
Illustration 3.
To secure accessories to the front edge
In this case, fastening is done with the bolts supplied and pre-fitted rivet nuts in
predrilled holes.
To secure accessories to the rear edge
Alternative 1, External installation
Alternative 2, Internal installation
Illustration 2
Illustration 3
COOL DX Chiller
COOL DX Chiller
Remove the cover and insulation. Secure the chiller to the SILVER C air handling unit
with the bolts supplied and pre-fitted rivet nuts. Refit the blanking plate and the
insulation.
The SILVER C air handling unit, rear
Illustration 1
COOL DX chiller, rear

GB.COOLDX.SI.G.190603
We reserve the right to alter specifications. www.swegon.com 11
3.3.4 Connection to SILVER C air handling unit,
COOL DX, sizes 060-080
The sealing strips are factory-fitted to the unit.
Dock the chiller directly to the SILVER C air handling unit
by means of the supplied bolts (4 bolts) + pre-fitted rivet
nuts, see the illustration.
You may need to remove the filter cassettes.
In this case, fastening is done with the bolts supplied and pre-fitted rivet nuts in
predrilled holes.
COOL DX Chiller
3.3.5 Stand-alone COOL DX
The variant with end connection panel should be selected.
Ducts connect between the SILVER C air handling unit and
COOL DX chiller, see section 3.3 Basic Installation Diagram
COOL DX.
3.3.6 Supply air filter
The supply air filter in the SILVER C air handling unit should
be dismantled and moved to the COOL DX unit.

GB.COOLDX.SI.G.190603
We reserve the right to alter specifications.
12 www.swegon.com
4 POWER CONNECTION
The cross sectional dimension of the power supply cable
should take into consideration the ambient temperature
and way the cable is run.
Important:
Installation must be carried out by a authorised electri-
cian.
4.1 Power connection
Incoming power supply
Sizes 008-020, all capacity variants, and size 030, capacity
variant 1:
5-core system, 400 V ±10%.
Size 030, capacity variants 2 and 3 and size 040-080 all
capacity variants:
4-core system, 400 V ±10%.
COOL DX, sizes 008-040, 060-1/2
Open the inspection door in front of the electrical equip-
ment cubicle.
Open the inspection door of the electrical equipment
cubicle.
Pull the incoming cable for power supply through pre-
drilled hole in the cover panel of the chiller (supplied cable
gland is mounted), through the space for compressors
and through the cable gland of the electrical equipment
cubicle. Locate the cable in a safe way. Make sure that the
cable does not touch the compressors or other compo-
nents, since surfaces could be hot or vibrate.
Connect the incoming power supply to the safety switch
situated in the electrical equipment cubicle, see the illus-
tration. The wiring terminal for incoming earth is situated
right next to the safety switch.
See section 10, Technical data.
Sizes 060–3, 080
Remove the cover on the external safety switch.
Connect the incoming power supply to the safety switch,
see the illustration. The wiring terminal for incoming earth
is situated right next to the safety switch.
See section 10, Technical data.
4.2 Connection signal 0-10 V
Terminals 103 and 104 are connected to give a signal,
0-10 V. For more information, also see the electrical wiring
diagram supplied separately.
Factory-fitted
cables
Supply is con-
nected here
Safety switch block.

GB.COOLDX.SI.G.190603
We reserve the right to alter specifications. www.swegon.com 13
5 COMMISSIONING
5.1 Preparations
5.1.1 Before initial start up
• The power supply should be connected.
• Terminals 105 and 106 in COOL DX electrical cabi-
net must be connected (closed switch), otherwise
the cooling machine will not start despite the signal
0 – 10 V, and no compressors are activated. (These
terminals can be used to connect an external thermo-
stat to activate/deactivate signal 0 – 10 V for a specific
temperature).
• Terminals 103 and 104 shall be connected to give a
signal, 0-10 V.
A free contact for a general alarm is located on terminals
100, 101 and 102.
5.1.2 Control functions
Silver Cool DX is equipped with two controls:
• IC208CX Dixell, hardware version 7.3 or 4.2
• Siemens (model: 12/24 RC 6ED1052-1MD08-0BA0)
Signal 0-10 V is received by the Siemens control which
converts it to digital output signals (see below) and for-
wards these to control IC208CX.
Control IC208CX is set at the factory to moto-condenser
mode and starts or stops the compressors via the digital
output signals from the Siemens control. All control and
safety functions for the refrigerant circuit are regulated by
control IC208CX.
For conversion of the signal, 0 – 10 V to digital output
signals, see below.
When the 0-10 V increases:
• Point 1: Q1 and Q2 = OFF
• Point 2: signal increases to above 1 V, then Q1= ON
and Q2 = OFF
• Point 3: signal increases to above 4 V, then Q1= OFF
and Q2 = ON
• Point 4: signal increases to above 7 V, then Q1= ON
and Q2 = ON
When the 0-10 V decreases:
• Point 4: signal decreases to below 7 V, then Q1= OFF
and Q2 = ON
• Point 3: signal decreases to below 4 V, then Q1= ON
and Q2 = OFF
• Point 2: signal decreases to below 1 V, then Q1= ON
and Q2 = OFF
• Point 1: Q1 stops when the signal reaches 0 V
Q1 and Q2 are the digital output signals that are sent to
control IC208CX to activate compressor 1 and 2.
Q1= compressor with lower cooling capacity
Q2 = compressor with higher cooling capacity
For more information about control and safety functions,
see separate instructions for IC208CX control.
5.1.3 Pressure sensor
The chiller has two in-service pressure switches in each
cooling circuit, one for low pressure and one for high pres-
sure.
If the operating pressure, in any of the circuits, exceeds
or drops below a limit value, the relevant compressor is
switched off. See separate instructions for IC208CX con-
trol for further information.
The compressor is permitted to restart when the restart
delay has expired.
Pressure sensor settings:
Value Setting Factory
range settings
Compressor 1
Low pressure limitation 1-10 bar 4.5 bar
High pressure limitation 25-50 bar 39.0 bar
High pressure alarm limit 25-50 bar 42 bar
Compressor 2
Low pressure alarm limit 1-10 bar 4.5 bar
High pressure limitation 25-50 bar 39.0 bar
High pressure alarm limit 25-50 bar 42 bar

GB.COOLDX.SI.G.190603
We reserve the right to alter specifications.
14 www.swegon.com
6 ALARMS
For an alarm description, see the separate instructions for
IC208CX control.
5.1.4 Phase sequence monitor
The COOL DX unit is equipped with phase sequence
guard for compressors (not size 008 capacity variant 1).
The phase sequence monitor is installed in the electrical
cabinet.
Phase sequence monitor
1
2
The phase sequence is correct when LED 1 is lit.
The voltage is connected when LED 2 is lit.
1
PSC
DPA51 3-Phase monitoring relay
5.1.5 Measure whether the phase-sequence is
wrong
Warning
May only be performed by authorised or trained service
personnel.
• Stop the COOL DX by selecting SHUT OFF in the
menu SETTINGS.
• Set the safety switch to position OFF on the COOL
DX.
• Switch the power supply to COOL DX.
Important:
Check that the incoming power supply to the COOL DX
is isolated by measuring.
• Transpose the two phase wires on the incoming
power supply cable in order to
obtain correct phase sequence (direction of rotation).
• Switch on the power supply to COOL DX.
• Set the safety switch to ON.
• Start COOL DX as described in the section dealing
with starting up, see Section 5.1.2.

GB.COOLDX.SI.G.190603
We reserve the right to alter specifications. www.swegon.com 15
7 MAINTENANCE
7.1 Cleaning
If needed, clean the inside cleaning of the unit by vacuum
cleaning and wiping surfaces with a damp cloth.
Inspections should be performed twice a year.
7.2 Handling of refrigerant
The refrigerant used is R 410A.
The refrigerant circuit is completely charged when the unit
is delivered.
Warning
Under no circumstances may the refrigerant circuit be
opened by unauthorised personnel, since it contains
gas under high pressure. Only an accredited refrigera-
tion company shall be permitted to modify or repair the
refrigeration circuit.
The COOL DX is equipped with a safety valve to prevent
excessively high pressure in the system caused by e.g. a
fire.
Important:
Contact Swegon Service in the event of leakage of
refrigerant.
Warning
If refrigerant is exposed to fire or in some other way
becomes superheated in the atmosphere, poisonous
gases can form.
Important:
Filling of refrigerant must be performed in accordance
with the recommendations of the refrigerant manufac-
turer.
Avoid direct skin contact with refrigerant and lubricant.
Use tightly sitting protective glasses, protective gloves
and covering work clothes.
Arrange ventilation/point extraction.
In the event of eye contact
rinse the eyes using an eye-wash shower (or with luke-
warm water) for 20 minutes. seek a doctor.
In the event of contact with skin
carefully wash with soap and lukewarm water.
In the event of frostbite
seek a doctor.
7.3 Leakage tracing interval/
Obligation to report
Must be carried out according to the F-Gas Regulation
EU/517/2014 and associated local legislation.
7.4 Service
Only service personnel trained by Swegon should be per-
mitted to modify the chiller.

GB.COOLDX.SI.G.190603
We reserve the right to alter specifications.
16 www.swegon.com
8 TROUBLE SHOOTING AND
LEAKAGE TRACING
8.1 Troubleshooting Schedule
Symptoms Possible cause Action
Compressor is not operating The voltage has been isolated.
Incorrect phase sequence.
The compressor safety circuit has been broken.
Defective compressor.
Check the operating/safety switch. Check the condi-
tion of the fuses.
Check and change the phase sequence.
Check, reset if needed.
Replace the compressor.
Too low cooling capacity The voltage has been isolated.
Incorrect phase sequence.
No air flow or too low air flow across the evaporator.
Thermostat/control equipment incorrectly set or defec-
tive.
Check the operating/safety switch. Check the condi-
tion of the fuses.
Check and change the phase sequence.
Check the air flow.
Adjust the setting or replace faulty components.
The compressor switches off
because the low pressure sensor
has measured an excessively low
value.
Inadequate refrigerant.
No air flow or too low air flow across the evaporator.
The expansion valve is defective.
The low pressure switch is defective.
The cooling system is leaking. Tighten the leak and
charge with refrigerant.
Check the air flow.
Check, replace.
Check, replace.
The compressor switches off
because the high pressure sensor
has measured an excessively high
value.
No air flow or too low air flow across the condenser.
Excessively high exhaust air temperature.
The high pressure sensor is defective.
Check the air flow.
Check the exhaust air temperature.
Check, replace.
Significant freezing on the
evaporator.
The expansion valve is defective or incorrectly set.
No air flow or too low air flow across the evaporator.
Check. Replace or adjust setting.
Check the air flow.
8.2 Leakage Tracing
Leakage tracing should be carried out at least once per
year as a precaution. The leakage tracing inspection must
be documented.
If the cooling system is leaking, this will become apparent
firstly by impaired cooling performance, or if the leakage is
substantial, when the chiller does not operate at all.
If you suspect that the cooling system is leaking refriger-
ant, check the level of refrigerant in the sight glass located
on the liquid line of the chiller.
If you see continuous and a substantial amount of bub-
bling in the sight glass and the chiller operates at appreci-
ably lower capacity than normal, the system is probably
leaking. One or several bubbles appearing when the chiller
is started up, operation at reduced capacity or normal
operation need not necessarily indicate a refrigerant defi-
ciency.
If it is bubbling in the sight glass and the chiller operates at
appreciably lower capacity, call for qualified service help.
NOTE! Maintenance work in the refrigerant system is per-
mitted to be carried out only by an accredited inspectorate
(a company with requisite authorisation).

GB.COOLDX.SI.G.190603
We reserve the right to alter specifications. www.swegon.com 17
9 DIMENSIONS
COOL DX 008
Size L B H K M Duct connection2)
008 900 995 1085 749 709 Ø 400
COOL DX 012
Size L B H K M Duct connection2)
012 900 1199 1395 953 709 Ø 500
2) For the locations of the duct connections, see the corresponding
SILVER C air handling unit
5050
16 K
1)
M
1)
Base beams are accessories.
1) End connection panel, optional.
2) For the locations of the duct connections, see the corresponding
SILVER C air handling unit
1) End connection panel, optional.
1) End connection panel, optional.
2) For the locations of the duct connections, see the corresponding
SILVER C air handling unit
16
1)
M
1)
5050 K
454521 K
1)
M
1)
COOL DX 020, 030, 040, 060, 080
Size L B H K M Duct connection2)
020
030
040
060
080
900
900
1100
1100
1100
1400
1600
1990
2318
2637
1551
1811
2159
2288
2640
1154
1354
1744
2072
2395
709
709
884
884
884
1000 x 400
1200 x 500
1400 x 600
1600 x 800
1800 x 1000

GB.COOLDX.SI.G.190603
We reserve the right to alter specifications.
18 www.swegon.com
Sizing
There are many factors that influence what size of chiller is
required.
COOL DX is designed to handle very different prerequi-
sites.
10 GENERAL TECHNICAL DATA
Cooling system COOL DX
COOL
DX
Size
Cap.
var-
iant
Nom.
air
flow
(m3/s)
Min
air
flow
(m3/s)
Nom.
cooling
cap.1)
(kW)
Nom.
Power
required
(kW)
Refrigerant
(kg)
Power
supply
Weight
excl. end
conn.
panel
(kg)
Weight
of each
end conn.
panel, if
required2)
(kg)
Circuit
1
Circuit
2
008 1 0.55 0.22 9.8 2.39 1,20 1.30 3-phase+N, 400 V ±10%, 16 A 194 8
2 0.70 0.3 13.9 4.33 1,20 1.30 3-phase+N, 400 V ±10%, 20 A 215 8
012 1 0.85 0.35 15.4 3.95 1,50 1.70 3-phase+N, 400 V ±10%, 20 A 260 10
2 1.05 0.4 20.9 6.53 1,50 1.70 3-phase+N, 400 V ±10%, 25 A 287 10
020 1 1.1 0.45 15.4 4.06 1,20 1,50 3-phase+N, 400 V ±10%, 25 A 243 11
2 1.3 0.5 23.3 5.73 2,50 2,80 3-phase+N, 400 V ±10%, 25 A 283 11
3 1.6 0.6 31.0 9.15 2,10 2.40 3-phase+N, 400 V ±10%, 40 A 314 11
030 1 1.8 0.7 25,0 6.33 1,80 2.00 3-phase+N, 400 V ±10%, 32 A 322 17
2 2.0 0.8 35.8 9.34 3.00 3,20 3-phase, 400 V ±10%, 25 A 374 17
3 2.4 1.0 46.2 13.5 2.90 3.30 3-phase, 400 V ±10%, 40 A 414 17
040 1 2.9 1.1 38.6 8.40 3.30 4.00 3-phase, 400 V ±10%, 25 A 468 22
2 3.1 1.3 48.4 12.3 3.30 4.50 3-phase, 400 V ±10%, 40 A 476 22
3 3.6 1,5 67.0 17.5 5.50 4.50 3-phase, 400 V ±10%, 50 A 529 22
060 1
2
3
3.9
4.1
5,0
1,5
1.6
2.0
56.2
66.7
97.5
11.8
17.1
26.3
4.50
5,00
6.00
5.50
5.20
7,50
3-phase, 400 V ±10%, 40 A
3-phase, 400 V ±10%, 50 A
3-phase, 400 V ±10%, 80 A
708
779
852
31
31
31
080 1
2
3
5.2
6.0
7.0
2.0
2.4
2.8
67.0
96.5
134.0
13.3
24.8
36.4
6,60
6,50
9.00
7,30
9.00
11.50
3-phase, 400 V ±10%, 50 A
3-phase, 400 V ±10%, 80 A
3-phase, 400 V ±10%, 100 A
852
979
1035
38
38
38
For correct sizing we refer to our ProUnit air handling unit
selection program.
1) For an outdoor temperature of 26°C, 50% RH (capacity variant 1), 27°C, 50% RH (capacity variant 2) or 28°C, 50% RH (capacity variant 3), and
an extract air temperature of 26°C.
2) The first weight applies to a small end connection panel; the second weight applies to a large end connection panel. COOL DX can be supplied
completely without end connection panels or with a maximum of 2 small and two large end connection panels depending on the variant selected.

GB.COOLDX.SI.G.190603
We reserve the right to alter specifications. www.swegon.com 19
11 INTERNAL WIRING DIAGRAM
11.1 COOL DX, size 08, capacity variant 1
Cx = Condenser
QFx = Fuse
KMx = Contactor
Q = Load separator
Rx = Crankcase heater
LINEA PROTETTA A CURA DEL CLIENTE
LINE PROTECTION BY CUSTOMER
LIGNE PROTEGEE PAR LE CLIENT
LINIE KUNDENS. GESCHUEZT
-QF2
/3.2
-QF01
-QF1 -QF3
/3.3
1~
M
S
-PE
-M1
RC
1~
M
S
-PE
-M2
RC
RM1.1
RM1.
2R
M2.2
RM2.1
230V
24V 230V
-TC1
-QF02
L2
L1
N
-Q
L3
10
3
2
7
-PE:3
-X103
-R1 -R2
-X100
-X104
-X100
21
22
-KM1
/3.6
21
22
-KM2
/3.7
10
10
grey
black
brown
blue
-PE:1
1
2
-KM1
/3.6
3
4
5
6
blue
bl
br
blue 4G1,5 mm²
-W1
bl
br
-PE:2
1
2
-KM2
/3.7
3
4
5
6
blue
br
bl
blue 4G1,5 mm²
-W2
1
-RM1
5
2
-CM1
-CS1 1
-RM2
5
2
-CM2
-CS2
-X1C1 R1 S1 -X1C2 R2 S2
4
0
1
10 /2.0
00 /2.0
0/2.3
1
/2.3

GB.COOLDX.SI.G.190603
We reserve the right to alter specifications.
20 www.swegon.com
LINEA PROTETTA A CURA DEL CLIENTE
LINE PROTECTION BY CUSTOMER
LIGNE PROTEGEE PAR LE CLIENT
LINIE KUNDENS. GESCHUEZT
1~
M
S
-PE
-M1
RC
-PSC
L1:
L1
-L2:
L2
-L3:
L3
11 14
-QF2
/3.2
-QF1
LIMITE FORNITURA
RM1.2
RM1.1
-QF01
230V
24V 230V
-TC1
-QF02
L2
L1
N
-Q
L3
-PE:1
1
2
-KM1
/3.6
3
4
5
6
1
2
-KM2
/3.7
3
4
5
6
1
2
3
4
5
6
-QM2
I> I>
I>
13
14
/3.3
WVU
PE
-M2 3~
M
-PE:2
blueblue
brown
grey
black
-W1
-W2
grey
brown
black
blue
brown
grey
black
grey
black
brown
black
black
brown
1
-RM1
5
2
-CM1
-CS1
-X1C1 R1 S1
-PE:3
-X103
-R1 -R2
-X100
-X104
-X100
21
22
-KM1
/3.6
21
22
-KM2
/3.7
10
3
2
7
10
10
4
0
1
10 /2.0
00 /2.0
0/2.3
1
/2.3
29 /3.3
32 /3.3
11.2 The COOL DX size 08, capacity variants 2, size 12 and 20, all capacity
variants and size 30, capacity variant 1
Cx = Condenser
QFx = Fuse
KMx = Contactor
PSC = Control system for phase sequence
Qmx = Motor protection
Q = Load separator
Rx = Crankcase heater
This manual suits for next models
7
Table of contents
Other Swegon Chiller manuals
Popular Chiller manuals by other brands

Airwell
Airwell Itelco-Clima CLS Series Installation and maintenance manual

York
York YVAM INSTALLATION PROCEDURE

Hoshizaki
Hoshizaki Lancer S8E V2 Series Installation, operation & service manual

York
York YK-EP Operation and maintenance manual

Robur
Robur GA ACF Installation, use and maintenance manual

Mueller
Mueller CP2-10 Installation and operation manual

Marco
Marco FRIIA Lite Service manual

Temptek
Temptek CF Series instruction manual

Carrier
Carrier HERMETIC CENTRIFUGAL LIQUID CHILLERS 19XR Product data

Trane
Trane CGWF Installation operation & maintenance

Daikin
Daikin EWAQ-E Series Installation, operation and maintenance

Nordcap
Nordcap SKF 10 GN 1/1 PLUS user manual