Swegon BACnet gateway User manual

20170724 We reserve the right to alter specifications.
GLOBAL
1
BACnet support for up to 4 units with double flow and heat recovery equipped with TAC5 control boards and SAT ETH-
ERNET. The BACnet Standardized Device Profile (Annex L) of the BACnet device is: BACnet Application Specific Control-
ler (B-ASC). The supported Data Link Layer Options are BACnet / IP and MS/TP slave.
2. Standard objects supported
Object Type
Analog Input Object_Identier, Object_Name, Object_Type, Present_Value,
Status_Flags, Event_State, Out_Of_Service, Units, Description.
Analog Value Object_Identier, Object_Name, Object_Type, Present_Value,
Status_Flags, Event_State, Out_Of_Service, Units, Description.
Integer Value Object_Identier, Object_Name, Object_Type, Present_Value,
Status_Flags, Event_State, Out_Of_Service, Units, Description.
Device
Object_Identier, Object_Name, Object_Type, System_Status,
Vendor_Name, Vendor_Identier, Model_Name, Firmware_Revision,
Application_Soware_Version, Protocol_Version,
Protocol_Revision, Protocol_Services_Supported, Protocol_Object_Types_Supported, Object_List, Max_
APDU_Length_Accepted, Segmentation_Supported.
1. Overview
BACnet gateway

GLOBAL
We reserve the right to alter specifications. 20170744
2
Setpoint - Supply Flow IV R4
Actual Supply Flow IV R7
Set Speed Supply IV W4
K2 Analog input AI1
K3 Analog input AI2
Working Mode IV R1
Speed Selection I II III IV R2
Type of unit for ow IV R3
Running Hours IV R9
Antifrost Status IV R10
Dampers Status IV R12
Postventilation IV R13
Control Mode IV R14
Filters Hours IV R16
Digital Outputs Status IV R19
CPs - Voltage reference 1 AV W2
CPs - Voltage reference 2 AV W4
Speed Mode IV W1
Speed Select - I II III IV W2
MANU/AUTO IV W3
BOOST IV W7
Control Board Reset IV W10
Running Hours Reset IV W11
Filters Hours Reset IV W 2
Setpoint - Exhaust Flow IV R5
Actual Exhaust Flow IV R8
Set Speed Exhaust IV W5
Exhaust/Supply ratio IV R6
T° exhaust AI5
Defrost Status IV R18
Setpoint – Preheat Temperature AVR1
OUT INT ELECT PREHEAT IV R20
T° out AI3 T° extract AI4
Bypass Status IV R11
Setpoint – T° Freecool AV W5
Force Bypass IV W6
Current Postheat setpoint AV R3
Setpoint – T° Postheat AV W1
Heat Stop IV W9T° antifrost internal
hydraulic postheater AI6
OUT INT HYDRAULIC POSTHEAT AV R5
OUT INT ELECT POSTHEAT IV R21
Setpoint – Comfort Temperature AV R2
Changeover Status IV R17
External coils Antifreeze Status IV R15
T° antifrost external hydraulic postheater AI8
OUT EXT HYDRAULIC POSTHEAT AV R6
OUT EXT ELECT POSTHEAT IV R22
T° antifrost external hydraulic postcooler AI9
Current Postcool setpoint AV R4
OUT EXT HYDRAULIC POSTCOOL AV R7
Setpoint – T° Postcool AV W3
Cool Stop IV W8
T° supply AI7
CP SENSOR MODBUS SUPPLY IV R23

20170724 We reserve the right to alter specifications.
GLOBAL
3
3.1 Analogue Input (RO): A1
Object
Instance Object Name Min/Max
1K2 Analog input 0-10,0 [V]
Analog input on K2 contact
2K3 Analog input 0-10,0 [V]
Analog input on K3 contact
3T° out -99,9-99,9 [°C]
Outside temperature measured on T1 sensor (-999=open, +999=short circuit)
4T° extract -99,9-99,9 [°C]
Extract temperature measured on T2 sensor (-999=open, +999=short circuit)
5T° exhaust -99,9-99,9 [°C]
Exhaust temperature measured on T3 sensor (-999=open, +999=short circuit)
6T° antifrost internal hydraulic postheater -99,9-99,9 [°C]
Temperature for the antifrost protection of the hydraulic postheater inside the unit meas-
ured on T4 sensor (-999=open, +999=short)
7T° supply -99,9-99,9 [°C]
Supply temperature measured on T5 sensor (-999=open, +999=short)
8T° antifrost external hydraulic postheater -99,9-99,9 [°C]
Temperature for the antifrost protection of the hydraulic postheater external to the unit
measured on T7 sensor (-999=open, +999=short)
9T° antifrost external hydraulic postcooler -99,9-99,9 [°C]
Temperature for the antifrost protection of the hydraulic postcooler external to the unit
measured on T8 sensor (-999=open, +999=short)

GLOBAL
We reserve the right to alter specifications. 20170744
4
3.1 Analogue Value (RO): AV R
Object
Instance Object Name Min/Max
1Setpoint – Preheat Temperature -9,9-9,9 [°C]
Preheat T° setpoint
2Setpoint – Comfort Temperature 0,1-99,9 [°C]
Current Comfort T° setpoint (KWout/NV/BA+/BA-) (0=OFF)
3Current Postheat setpoint 0,1-99,9 [°C]
Current Postheat setpoint (KWout/NV/BA+/KWext) (0=OFF)
4Current Postcool setpoint 0,1-99,9 [°C]
Current PostCooling setpoint (BA-) (0=OFF)
5OUT INT HYDRAULIC POSTHEAT 0-10,0 [V]
Output for the power control of the hydraulic postheater inside the unit
6OUT EXT HYDRAULIC POSTHEAT 0-10,0 [V]
Output for the power control of the hydraulic postheater external to the unit
7OUT EXT HYDRAULIC POSTCOOL 0-10,0 [V]
Output for the power control of the hydraulic postcooler external to the unit

20170724 We reserve the right to alter specifications.
GLOBAL
5
3.3 Integer Value (RO): IV R
Object
Instance Object Name Min/Max
1Working Mode 0-9
Current Working mode (0=OFF 1=CA 2=LS 3=CPf 4=CPs (5=CAs) 6=TQ 9=InitPa)
2Speed Selection I II III 0-3
Current speed (0=STOP 1=LOW/I 2=MEDIUM/II 3=HIGH/III)
3Type of unit for ow 0-4
Current main Setpoint unit (0= m3/h 1=Pa 2=0,1V 3=torque% 4=l/s)
4Setpoint - Supply Flow 0-99999
Current setpoint for the supply fan (unit dened in object “Type of unit for ow”)
5Setpoint - Exhaust Flow 0-99999
Current setpoint for the exhaust fan (unit dened in object “Type of unit for ow”)
6Exhaust/Supply ratio 5-999
% (F3F4/F1F2)
7Actual Supply Flow 0-99999
Actual Supply Flow (unit dened in object “Type of unit for ow”)
8Actual Exhaust Flow 0-99999
Actual Exhaust Flow (unit dened in object “Type of unit for ow”)
9Running Hours 0-999999 [H]
Run time, working hours
10 Antifrost Status 0-2
0=OFF 1=REC ON 2=NV ON
11 Bypass Status 0-2
0=CLOSED/OFF 1=OPEN/ON 2=PARTIALLY OPEN
12 Dampers Status 0-2
0=CLOSED 1=OPENING/CLOSING 2=OPEN
13 Postventilation 0-1
Post ventilation status (0=NO 1=YES)
14 Control Mode 0-10
Control by (1=ERROR 2=FIREALARM 3=VIEWER 4=CBR 5=VIEWSCHED 6=MBSCHED
7=MB40201 8=BYPASS 9=BOOST 10=MB40204)
15 External Batteries Antifreeze Status 0-3
BA+ BA- Antifreeze status (0=OFF, 1=BA+ ON or BA+/- ON, 2=BA- ON, 3=BA+ and BA-
ON)
16 Filters Hours 0-999999 [H]
Filters alarm: hours count

GLOBAL
We reserve the right to alter specifications. 20170744
6
3.3 Integer Value (RO): IV R
Object
Instance Object Name Min/Max
17 Changeover Status 0-1
Automatic changeover between heating and cooling (0=inactive, 1=heating, 2=cooling)
18 Defrost Status 0-2
0=IDLE, 1=ACTIVE, 2=STOP to drain water
19 Digital Outputs Status 0-65536
Contains a bit for each of the digital outputs:
bit0="AL1 (alarm)"
bit1="BYPASS 1 (For on/o bypass: 0=closed/o 1=open/on. For prop_bypass: 0=down
1=up"
bit2="BYPASS 2 (For on/o bypass: always on. For prop_bypass: 0=stop 1=run)"
bit3="CT"
bit4="KWin"
bit5="KWout"
bit6="OR1 SAT “pressure alarm””
bit7="OR2 SAT “fan on”"
bit8="OR3 SAT “water pump NV”"
bit9="OR4 SAT “bypass on”"
bit10="SATBA WP"
bit11="SATBA OUT9 KWext"
20 OUT INT ELECT PREHEAT 0-100
Output percentage for the power control of the electrical preheater
21 OUT INT ELECT POSTHEAT 0-100
Output percentage for the power control of the electrical postheater inside the unit
22 OUT EXT ELECT POSTHEAT 0-100
Output percentage for the power control of the electrical postheater external to the unit
23 CP SENSOR MODBUS SUPPLY 0-9999 [Pa]
Pressure measured by the Modbus sensor located on the supply duct
24 CP SENSOR MODBUS EXHAUST 0-9999 [Pa]
Pressure measured by the Modbus sensor located on the exhaust duct

20170724 We reserve the right to alter specifications.
GLOBAL
7
3.4 Analogue Value (R/W): AV W
Object
Instance Object Name Min/Max
1Setpoint – T° Postheat 0-99,9 [°C]
Postheating T° setpoint (0=OFF)
2CPs - Voltage reference 1 0-10,0 [V]
CPs mode: setpoint voltage for [CPs on SUP] or [CPs on EXH]
3Setpoint – T° Postcool 0-99,9 [°C]
Postcooling T° setpoint (0=OFF)
4CPs - Voltage reference 2 0-10,0 [V]
CPs mode: setpoint voltage for [CPs on SUP + EXH]
5Setpoint – T° Freecool 0-99,9 [°C]
Freecooling T° setpoint (0=OFF)

GLOBAL
We reserve the right to alter specifications. 20170744
8
3.3 Integer Value (R/W): IV W
Object
Instance Object Name Min/Max
1Speed Mode 0-3
Communication determines speed (0=NO 1=Predened Speed I-II-III 2=TIMETABLE 3=set
values in objects)
2Speed Select - I II III 0-3
Selection of predened speed (0=OFF 1=LOW 2=MEDIUM 3=HIGH)
3MANU/AUTO 0-1
MANUAL/AUTO mode (0=MANUAL 1=AUTO/Time scheduler)
4Set Speed Supply 0-99999
Set supply Flow (m3/h or l/s) or Torque (%)
5Set Speed Exhaust 0-99999
Set exhaust Flow (m3/h or l/s) or Torque (%)
6Force Bypass 0-2
Override: force bypass ON or OFF, 0=normal, 1=force_on, 2=force_o
7BOOST 0-1
force boost mode, 0/1
8Cool Stop 0-1
Override: force cooling to stop if set to 1. Note that cooling will start if this object is set to
0 and if Heat Stop object is set to 1.
9 Heat Stop 0-1
Override: force heating to stop if set to 1.
10 Control Board Reset 0-1
Do RESET of controller, clear alarms (0=NO, 1=RESET). Autoreset
1 Running Hours Reset 0-1
Do reset of run time, working hours (0=NO, 1=RESET). Autoreset
12 Filters Hours Reset 0-1
Do reset of lters hours (0=NO, 1=RESET). Autoreset

20170724 We reserve the right to alter specifications.
GLOBAL
9
4. Installation
LED 1 - GREEN: ON
LED 2 - GREEN: BACnet comm.
LED 3 - Device state
LED 4 - GREEN: Modbus comm.
LED 5 - GREEN: Not used
LED 6 - GREEN: Not used
Connector 3: Ethernet 1 Port (RJ45 Plug)
Connector 4: Ethernet 2 Port (RJ45 Plug)
Power supply:
0V = Ground
+V = Positive wire
VAC : min 8V ; max 24V
VDC : min 12V ; max 25V
The default configuration is indicated in the following
table:
BACnet gateway:
o IP ADDRESS gateway: 192.168.1.9
o SUBNET MASK: 255.255.255.0
o GATEWAY: 0.0.0.0
o PORT: 47808
o BACnet device name: Lemmens
o Device Identifier: 1
- Unit n°1: IP ADDRESS: 192.168.1.1
- Unit n°2: IP ADDRESS: 192.168.1.2
- Unit n°3: IP ADDRESS: 192.168.1.3
- Unit n°4: IP ADDRESS: 192.168.1.4
4.1 Topology
5. Configuration
5.1 Default configuration

GLOBAL
We reserve the right to alter specifications. 20170744
10
It is possible to reduce the number of units that will be
controlled through the Bacnet gateway, or to change the
IP address of the gateway and of the units as well.
- Download from www.lemmens.com website
the configuration 2 files.
- Installation package of "Compositor SW67673”.
- Package “Install BACnet Config”.
- Install first the software "Compositor SW67673”.
- Extract the package “Install BACnet Config” in
the Project folder of Compositor.
5.2 Custom configuration
Example of installation:
Start BACnet config.exe:
With the interface it is possible to:
o Remove a unit or add a unit
o Change the gateway IP configuration
o Change the gateway communication port
o Change the last number of the IP address of the
units on the corresponding row inside the table.
N.B.: for the units, only the last number of the IP address
can be changed since it must be within the same range of
the gateway IP address.
o Save the configuration
o Open a previously saved configuration
5.3 Upload configuration
The module has a default configuration loaded, so there
should be no need to make any changes if the default
configuration can be used.
Procedure to change the configuration of the module:
1. Set up first the computer used for downloading in
order to be able to communicate with the gateway:
Set IP address of the computer to 192.168.1.10.
The net mask will be 255.255.255.0.
The gateway is not used so 0.0.0.0.

20170724 We reserve the right to alter specifications.
GLOBAL
11
2. Press the button “Open Configuration” (on Step 1 row)
and then choose the folder corresponding to the desired
project for downloading.
3. Press the button “Update Device” (step 5). The fol-
lowing dialog box will appear where there is no need to
change anything (the IP address may be different from
the picture, according to the one configured in the pro-
ject).
4. Press the button “Ping”, then the text “Device Found”
will appear:
5. Press the button “Next”, the following dialog box will
appear where only “Configuration” and “Read the con-
figuration when finish” must be checked:
6. Press the button “Execute update firmware”.
7. The status update window will appear to show the
evolution of the downloading.
8. If error message, do the verifications as described in
step 9:

GLOBAL
We reserve the right to alter specifications. 20170744
12
9. Check that the firewall allows the update software to
go through it. Here is an example with Windows 10 ©:
10. Try to repeat the operations for the updating;
Try to restart the PC;
If using Windows Seven or Vista,7, 8 or 10, make sure to
have the administrator privileges;
Check the LAN settings.
Try with another PC.
5.4 Resetting the IP address:
The gateway comes with default IP address 192.168.1.9.
If this address has been changed later on and the address
is not known anymore, follows this procedure to set the
back the factory address.
1. Turn off the Device;
2. Put Dip2 of ‘Dip-Switch A’ at ON position (Fig.1)
3. Turn on the device
4. Connect the Ethernet cable;
5. Insert the IP “192.168.2.205”;
6. Press the “Ping” button, must appear “Device Found!”
7. Press the “Next” button;
8. Check all operations;
9. Press the “Execute update firmware” button to start
the upload;
10. When all the operations are “OK” turn off the Device;
11. Put Dip2 of ‘Dip-Switch A’ at OFF position (Fig.2)
12. Turn on the device.
13. Upload a configuration (see 5.2).
Fig.1
Fig.2

20170724 We reserve the right to alter specifications.
GLOBAL
13
Data Link Layer Options:
BACnet IP, (Annex J)
MS/TP slave (Clause 9), baud rate(s): 9600, 19200, 38400, 57600, 76800, 115200
Point-To-Point, EIA 232 (Clause 10), baud rate(s): 9600, 115200
Character Sets Supported:
ISO 10646 (UTF-8)
Network Security Options:
Non-secure Device - is capable of operating without BACnet Network Security