Swegon REACT Va User manual

REACT Va
Instructions for Use 20200928
Art. 1546059
The document was originally written in Swedish
Symbol key
Symbols on the machine.
This product complies with applicable EU directives
Symbols in this user manual
Warning/Caution!
Risk of crushing
Application area
The product is a variable flow damper or constant flow damper
designed for comfort ventilation indoors. The product is used to
regulate the supply air or extract air flow in ventilation ducts.
The product may not be used for anything other than its
intended use.
General
Read through the entire instructions for use before you
install/use the product and save the instructions for
future reference. It is not permissible to make changes
or modify this product other than those specified in this
document.
The packaging contains the following
items:
1 x REACT V
1 x Instructions for use
Protective equipment
Always use appropriate personal protective equipment
for the work in question, in the form of gloves, respirators
and protective glasses during handling, installation,
cleaning and service/maintenance.
Electrical safety
Permitted voltage, see “Electrical data”. It is not permissible
to insert foreign objects into the product’s contactor
connections or the electronics's ventilation openings; risk
for short circuiting.
24 V isolation transformer to be connected should comply with
the provisions of IEC 61558-1.
Cable sizing must be carried out for cabling between the product
and the power supply source.
Disconnect the power supply when working on products that
are not required to run in production.
Always follow the local/national rules for who shall be permitted
to carry out this type of electrical installation.
Other risk
When the product is voltage fed, the damper will be
either open or close and there can be a certain risk
for pinch injuries, for example, on the fingers if these
are placed between the damper blade and ventilation
duct when the damper blade rotates. The product’s
actuator is equipped with a release button that permits
manual control of the damper blade, always ensure this
is activated before working on the internal parts of the
damper.
If the product is equipped with a spring return actuator there
is no release button, manual control is performed using the
supplied hex key where the damper blade is cranked to the
required position and then locked. Do not forget to disable the
lock after working on it.
Handling
• Always use appropriate transport and lifting devices when the
product is to be handled to reduce ergonomic loads.
• The product must be handled with care.
• It is not permissible to carry the product by the measuring
tube.
Installation
• Moist, cold and aggressive environments must be avoided.
• Avoid installing the product near a heat source.
• Assemble the product according to applicable industry
regulations.
• Install the product so that it is not accessible by unauthorized
persons, for example above a suspended ceiling.
• Install the product for easy access during service/maintenance.
• Supplement the duct system with a cleaning hatch in the
vicinity of the product to facilitate cleaning.
• If the product is mounted above a fixed ceiling, the inspection
hatch must be located so that the product is accessible for
inspection.
• If the product is mounted so that it is possible to gain access
to the inside of the product, it must be supplemented with
appropriate protection, for example, a ventilation unit.
• If the product is mounted in cold areas, the whole product
must be insulated on the outside against condensation.
• For installation, the accessory FSR is recommended.
• The product can be installed position-independent.
• It is recommended to mount the product so that the
product’s display is visible.
• The product must be laid down prior to installation so that it
cannot fall over.
• Check to make sure that the product does not have any
visible defects.
• Check that the product is properly secured after it has been
installed.
• Use the product’s eyes to secure the cables with cable ties.
• Check that all cables are properly secured in place after
installation.
• Check that the actuator/controller is properly mounted in
place.

REACT V
2Swegon reserves the right to alter specications. 20200928
Installation, torque, dimensions and weights
Figure 4. Dimensions (mm), REACT V circular and REACT V circular
with spring return. The damper can be installed at an optional
angle.
A
EE
Ød
C
30
Figure 1. Requires a straight duct section of 3 x Ø for sound
attenuators with baffle or centre body.
Figure 2. Installation in the duct system. The ducts must be firmly
fixed to the frame of the building on each side of REACT V.
B
Figure 3. Straight duct section requirements, circular ducts,
quantity Ø before the product:
Figures 1-5 require no straight duct section (figure 3*illustrates
the T piece with cleaning hatch).
Figure 6 requires a straight duct section before the damper
equivalent to 4 x the diameter of the duct.
1.
2.
3*.
4.
5.
6.
B
1. REACT V
2. FSR Clamp
3. Sound attenuator
1. REACT V
2. FSR Clamp
A
E
E
Ød
C
64
100
3
6
0
°
140
3
6
0
°
Circular design
Size ØD (mm)
A (mm)
B (mm)
C (mm)
E (mm)
Normal
motor
Spring
return
Flow range
Tolerance Q*±5%
with at least ±x l/s
Min. Max=Vnom*)
Torque ( Nm)
Weight (kg)
Torque ( Nm)
Weight (kg)
l/s
m3/h
l/s
m3/h
100 475 485 190 50 51.6 52.7 518 67 241 2
125 475 485 215 50 51.8 52.9 932 108 389 2
160 475 485 255 50 52.1 53.1 16 58 184 662 2
200 475 485 300 50 52.7 53.7 25 90 292 1051 3
250 525 535 350 50 53.4 54.5 40 144 470 1692 5
315 560 570 415 50 10 4.5 10 6.0 63 227 747 2689 8
400 695 705 505 60 10 6.5 10 8.0 102 367 1240 4464 13
500 820 840 605 60 10 9.1 10 10.6 164 590 1900 6840 20
630 915 935 735 60 15 14.0 20 15.5 300 1080 2950 10620 32
*) Vnom at 120 Pa in pressure reading.
*Installed according to the instructions
Installation – all designs
• The product’s air flow measurement requires a straight duct
section as per the installation figures.
• In unfavourable conditions before or with disruption, the
product’s tolerances cannot be guaranteed.
• Instructions for Use are supplied with the product on deliv-
ery, but can also be downloaded from www.swegon.com.
Installation – circular version
• Installation is position dependent.
• Can be installed horizontally or vertically.

3
20200928 Swegon reserves the right to alter specications.
REACT V
85
2020 B20
220
250
20
20
H
Figure 7. Dimensions (mm), REACT V rectangular, REACT V
rectangular with spring return.
Installation – rectangular design
Dimension B in the figure and table below is found in the
table “Rectangular design” to the left.
NOTE! Damper spindles must be installed horizontally.
Straight duct section before REACT V in rectangular
ducts
Type of disruption E (m2=5%) E (m2=10%)
One 90° bend E = 3 x B E = 2 x B
T piece E = 3 x B E = 2 x B
Figure 5. Straight section requirements, rectangular ducts.
Figure 6. Straight duct section requirements, rectangular REACT
V and sound attenuator with baffle. Installation with a straight
duct section applies to both the supply air and the extract air.
Straight duct section before/after REACT V – sound
attenuator with baffle
1
x
B
1
3
2
1. = Rectangular REACT V
2. = Straight duct ≥3xB.
3. = Sound attenuator with baffle.
Rectangular design
Size WxH (mm)
Normal
motor
Spring
return Flow range
Tolerance Q*±5%
with at least ±x l/s
Torque (Nm)
Weight (kg)
Torque (Nm)
Weight (kg)
Min. Max=Vnom*)
l/s m3/h l/s m3/h
200 x 200 57.2 58.0 67 240 365 1314 8
300 x 200 5 8.4 59.2 100 360 548 1971 12
400 x 200 5 9.9 510.7 133 480 730 2628 17
500 x 200 5 11. 4 512.2 167 600 913 3285 21
600 x 200 5 12.9 513.7 200 720 1095 3942 25
700 x 200 5 14.4 515.2 233 840 1278 4599 29
800 x 200 5 15.4 516.2 267 960 1460 5256 33
1000 x 200 10 18.4 10 19.9 333 1200 1825 6570 42
300 x 300 5 10.9 511.3 152 548 834 3003 19
400 x 300 5 12.4 512.9 203 731 1112 4004 25
500 x 300 5 13.9 514.4 254 914 1390 5004 32
600 x 300 5 15.4 515.9 305 1096 1668 6005 38
700 x 300 10 16.8 10 17. 8 355 1279 1946 7006 44
800 x 300 10 18.4 10 19.4 406 1462 2224 8007 51
1000 x 300 10 21.4 10 22.4 508 1827 2780 10009 63
400 x 400 5 14.0 514.5 273 983 1495 5382 34
500 x 400 10 16.0 10 18.0 341 1228 1869 6728 43
600 x 400 10 17.4 10 18.5 409 1474 2243 8073 51
700 x 400 10 19.6 10 20.6 478 1720 2616 9419 60
800 x 400 10 21.1 10 22.2 546 1965 2990 10764 68
1000 x 400 10 24.2 10 25.2 682 2457 3738 13456 85
1200 x 400 15 27. 2 20 29.2 819 2948 4485 16147 102
1400 x 400 15 30.3 20 32.2 955 3439 5233 18838 119
1600 x 400 15 33.3 20 35.3 1092 3931 5980 21529 136
500 x 500 10 18.5 10 19.5 429 1543 2347 8449 54
600 x 500 10 20.5 10 21.6 514 1851 2816 10139 64
700 x 500 10 22.6 10 23.6 600 2160 3286 11829 75
800 x 500 10 24.6 10 25.6 686 2468 3755 13519 86
1000 x 500 15 28.6 20 30.6 857 3085 4694 16898 107
1200 x 500 15 32.7 20 34.6 1028 3702 5633 20278 129
1400 x 500 15 36.8 20 38.7 1200 4319 6572 23658 150
1600 x 500 15 40.8 20 42.8 1371 4936 7510 27037 171
600 x 600 10 22.7 10 23.7 618 2227 3388 12195 77
700 x 600 10 24.8 10 25.8 722 2598 3952 14228 90
800 x 600 15 26.8 20 27.8 825 2969 4517 16260 103
1000 x 600 15 30.9 20 32.9 1031 3711 5646 20325 129
1200 x 600 15 35.0 20 37.0 1237 4453 6775 24390 155
1400 x 600 15 39.2 20 41.1 1443 5195 7904 28455 180
1600 x 600 15 43.3 20 45.2 1649 5937 9033 32521 206
700 x 700 15 27.6 20 29.5 844 3038 4622 16638 105
800 x 700 15 30.3 20 32.2 964 3472 5282 19014 121
1000 x 700 15 34.9 20 36.8 1205 4339 6602 23768 151
1200 x 700 15 40.6 20 42.6 1446 5207 7923 28522 181
1400 x 700 15 45.7 20 47.7 1688 6075 9243 33275 211
*) Vnom at 120 Pa in pressure reading.
*Installed according to the instructions
1. Controller/Actuator always on the side of the rectangular damper.
E = Straight section.
W = Width, duct.
H = Height, duct.
E
E
1xB
1xB
1

REACT V
4Swegon reserves the right to alter specications. 20200928
Connection, spring return
1-2 – Supply voltage 24 V AC/DC
1-3 – Control signal (Y) 0..10 / ( 2..10 ) V
1-4 – Actual value signal (U) 0..10 / ( 2..10 ) V
A-B – Modbus
For further calculations of Y and U see the formulas page 8.
Load on output 4: max. 0.5 mA
LN
24 V AC/DC
AB 0..10 V DC
(2..10 V DC)
a. b. c. d. e.
0..10 V DC
(2..10 V DC)
Y U
1 2 3 4
-+
AAB
Modbus
-+
GUAC
CA CB
-+
NOTE! Electrical connection of the spring return actuator from
the factory is completed.
Figure 9. Wiring diagram, spring return.
LN
24 V AC/DC
AB 0..10 V DC
(2..10 V DC)
a. b. c. d. e.
5 Nm
3 W 5 VA
100s (90°) 95°
250 Pa max. 100 kPa
QX XX / XX
227VM-024-05
5
Nm
3
W 5
V
A
V
V
1
0
00s (90°) 95°
2
5
50 Pa max. 100 kPa
QX XX
22
227VM-024-05
XX /
22
27
0..10 V DC
(2..10 V DC)
Y U
1 2 3 4
-+
AAB
+Y U
1 2 3 4 A B
-
Modbus
-+
BK RD WH OG PK GY
CA CB
-+
Figure 8. Wiring diagram, normal version.
Connection, normal version
1-2 – Supply voltage 24 V AC/DC
1-3 – Control signal (Y) 0..10 / ( 2..10 ) V
1-4 – Actual value signal (U) 0..10 / ( 2..10 ) V
A-B – Modbus
For further calculations of Y and U see the formulas page 8.
Load on output 4: max. 0.5 mA
Connections
Regulation and forced control via analogue
control signal
See connection in the wiring diagram, figure 8 and 9.
a. Open the damper: 24 VAC (L) via diode/rectifier
(positive half-wave)
b. Regulate to set max. value: 24 VAC/DC (L)
c. Regulate to set min. value: Mode = 0 – 10 V, no control
signal
d. Close the damper: 24 VAC/DC (N)
• Mode = 0 – 10 V, min. value = 0
• Mode = 2 – 10 V
e. Regulate according to control signal 0-10 V / 2-10 V
• Mode = 0 – 10 V
0 V = min. value
10 V = max. value
• Mode = 2 – 10 V
0 V = close damper
2 V = min. value
10 V = max. value

5
20200928 Swegon reserves the right to alter specications.
REACT V
Vnom
Vnom
Flow
Flow
Vmin
Vmin
Vmax
Vmax
T
T
est
est
Mode
Mode
Adr
Adr
I/s
Test
m /h
3
VnomVnom FlowFlow
VminVmin
VmaxVmax
TTestest
ModeMode
AdrAdr
I/s
Test
m /h
3
Addr
• Used for Modbus. for particulars on how to use
Modbus, see next page.
Handling
Menus
Vnom
Vnom
Flow
Flow
Vmin
Vmin
Vmax
Vmax
T
T
est
est
Mode
Mode
Adr
Adr
I/s
Test
m /h
3
VnomVnom FlowFlow
VminVmin
VmaxVmax
TTestest
ModeMode
AdrAdr
I/s
Test
m /h
3
Flow
• Switch between l/s and m3/h via the edit wheel.
• A “Lit” square on the display indicates the
selected unit.
Vnom
Vnom
Flow
Flow
Vmin
Vmin
Vmax
Vmax
T
T
est
est
Mode
Mode
Adr
Adr
I/s
Test
m /h
3
VnomVnom FlowFlow
VminVmin
VmaxVmax
TTestest
ModeMode
AdrAdr
I/s
Test
m /h
3
Test
• Disconnects automatically after 10 hours.
• Turn the edit wheel to choose between the
following modes:
oFF – Test mode switched off, the controller regulates
normally
on – Test mode is on, the damper is locked in its
position
oP –Opens the damper fully
cL – Closes the damper completely
Lo –The damper is regulated to the selected Vmin
Hi – The damper is regulated to the selected Vmax
123 – Shows the current software version
Vnom
Vnom
Flow
Flow
Vmin
Vmin
Vmax
Vmax
T
T
est
est
Mode
Mode
Adr
Adr
I/s
Test
m /h
3
VnomVnom FlowFlow
VminVmin
VmaxVmax
TTestest
ModeMode
AdrAdr
I/s
Test
m /h
3
Mode
• Shows the selected control and actual value signal
• Switch between 0-10 and 2-10 V via the edit
wheel
Vnom
Vnom
Flow
Flow
Vmin
Vmin
Vmax
Vmax
T
T
est
est
Mode
Mode
Adr
Adr
I/s
Test
m /h
3
VnomVnom FlowFlow
VminVmin
VmaxVmax
TTestest
ModeMode
AdrAdr
I/s
Test
m /h
3
Vnom
• Used for factory configuration.
Vnom
Vnom
Flow
Flow
Vmin
Vmin
Vmax
Vmax
T
T
est
est
Mode
Mode
Adr
Adr
I/s
Test
m /h
3
VnomVnom FlowFlow
VminVmin
VmaxVmax
TTestest
ModeMode
AdrAdr
I/s
Test
m /h
3
Vmax
• Select new value for Vmax via the edit wheel.
• Vmax must be greater than Vmin
Vnom
Vnom
Flow
Flow
Vmin
Vmin
Vmax
Vmax
T
T
est
est
Mode
Mode
Adr
Adr
I/s
Test
m /h
3
VnomVnom FlowFlow
VminVmin
VmaxVmax
TTestest
ModeMode
AdrAdr
I/s
Test
m /h
3
Vmin
• Select new value for Vmin via the edit wheel.
• Vmin should be less than Vmax.
Figure 10. REACT interface.
1 – Select the required function by turning the “Function wheel”.
2 – Set the value or select submenus by turning the “Edit” wheel.
3 – The value flashes twice when a new value is accepted.
4 – Release button. (Not available on the spring return).
Made in Germany
24 VAC/DC 50/60 Hz
0...+50°C IP 42
Edit
10°
Vnom Flow
Vmin
Vmax
Test
Mode
Adr
Do not
open
I/s
Test
m /h
3
1
23
4
VnomVnom FlowFlow
VminVmin
VmaxVmax
TTestest
ModeMode
AdrAdr
I/s
Test
m /h
3

REACT V
6Swegon reserves the right to alter specications. 20200928
Function Description
Addr
Enables you to set the actuator's Modbus address, by turning the "edit wheel". It
is possible to set the address from 1 till 247. If you turn the value selector to end
stop "+", the display will show a "2". This makes it possible to select the second
level. If you select the second level, this is indicated in the display by a small circle.
The following functions are available at the second level:
Flow Return to previous level
Vmin Not used.
Vmax Not used.
Test Not used.
Mode Shows the angle of the rotation (0…255 digital 0....100%)
Addr. Used for selecting communication settings for Modbus. See table below.
Vnom
Used for setting response delay for the Modbus communication (see separate
documents)
How to use Modbus
Modbus tables are available in a separate document (REACT-Modbus-m)
Display number EEPROM value Communication rate Parity Stop bits
1301200 None 2
2311200 Even 1
3321200 Odd 1
4 3 2400 None 2
5 4 2400 Even 1
6 5 2400 Odd 1
7 6 4800 None 2
8 7 4800 Even 1
9 8 4800 Odd 1
10 99600 None 2
11 10 9600 Even 1
12 11 9600 Odd 1
13 12 19200 None 2
14413 19200 Even 1
15 14 19200 Odd 1
16 15 38400 None 2
17 16 38400 Even 1
18 17 38400 Odd 1
19318 1200 None 1
20 19 2400 None 1
21 20 4800 None 1
22 21 9600 None 1
23 22 19200 None 1
24 23 38400 None 1
3Limited data length per reading of max. 8 addresses
4Default setting

7
20200928 Swegon reserves the right to alter specications.
REACT V
Cleaning
Ideally, the product should be cleaned in connection with
the cleaning of the rest of the ventilation system.
Cleaning of electrical components
• If needed, use a dry cloth to clean the components.
• Never use water, detergent and cleaning solvent or a
vacuum cleaner.
External cleaning
• If necessary use tepid water and a well-wrung cloth.
• Never use detergent and cleaning solvent or a vacuum
cleaner.
Internal cleaning
• When cleaning the ventilation system, the product
must be dismantled if there are no cleaning hatches
close to the product.
• Cleaning equipment such as whisks and the like must
not be fed through the product.
• If necessary remove dust and other particles that can
be present in the product.
• Never use detergent and cleaning solvent or a vacuum
cleaner.
Service/maintenance
• The product does not require any maintenance, except
for any cleaning when necessary.
• In connection with a service, mandatory ventilation
inspection or cleaning of the ventilation system, check
that the general condition of the product appears to be
good. Pay particular attention to the suspension, cables
and that they sit firmly in place.
• It is not permissible to open or repair electrical
components.
• If you suspect that the product or a component is
defective, please contact Swegon.
• A defective product or component must be replaced by
an original spare part from Swegon.
Materials and surface treatment
All sheet-metal parts are galvanized sheet steel (Z275).
Disposal
Waste must be handled according to local regulations.
Product warranty
The product warranty or service agreement will not be
valid/will not be extended if: (1) the product is repaired,
modified or changed, unless such repair, modification
or change has been approved by Swegon AB; or (2) the
serial number on the product has been made illegible or
is missing.
Trouble shooting
The product does not communicate over Modbus
• Make sure that the product is energized.
• Check the product's Modbus connection.
• Check the product's communication settings.
• Check that the product has the right and unique
Modbus address.
The product shows the incorrect/no air flow
• Make sure that the product is energized.
• Check that the product’s set size corresponds with the
physical size.
• Make sure that the product is installed according to the
recommended distance to disruptions, see “Installation”.
• Check that there is an air flow.
• Make sure that the product is correctly oriented in
terms of air direction. The air flow must follow the
instructions on the product.
• Check that the measuring tube is mounted correctly,
plus to plus (red), minus to minus (blue).
• Check that the measuring tubes are undamaged and
not creased.
• Check with the help of the k-factor and pressure diffe-
rence between the red and blue measuring tubes that
the flow is within the product’s measurement range.
The product does not regulate the air flow
• Make sure that the product is energized.
• Check that the damper motor has not become
detached from the damper spindle.
• Check that the damper motor works by pressing in
the motor’s release button, turn the damper spindle,
release the release knob and then see whether the
damper motor starts to move.
• Check that the product is connected correctly.
• Check that the product is not force controlled.

REACT V
8Swegon reserves the right to alter specications. 20200928
4,00 V
V DC
U
1 2 4
CA CB
AB
3
Y
Figure 11. Shows connection of a voltmeter to check the actual
value on the normal version.
Formulas for calculating air flow
The following applies for analogue control.
Control signal 0..10 V DC give the following formulas:
• Calculation of the current pressure (Vact) when you know the
value of the control signal (Y):
Y
10 V DC
Vact = Vmin + (Vmax – Vmin)
Vact
Vnom
U = 10 V DC
Y – 2 V DC
8 V DC
Vact = Vmin + (Vmax – Vmin)
Control signal 2..10 V DC gives the following formulas:
• Calculation of the current flow (Vact) when you know the
value of the the control signal (Y):
Vact
Vnom
U = 2 V DC + 8 V DC
• Calculation of the current actual value (U) when you know
the value of the current flow (Vact):
• Calculation of the current actual value (U) when you know
the value of the current flow (Vact):
Key to formulas opposite:
Y = control signal in [V] DC
U*= actual value signal in [V] DC, always refers to 0-Vnom.
Vact = current air flow in [l/s, m3/h]
Vmin = set min. flow in [l/s, m3/h]
Vmax = set max. flow in [l/s, m3/h]
Vnom = nominal flow in [l/s, m3/h], see tables page 2 & 3.
*Note! Does not indicate damper position.
4,00 V
V DC
U
1 2 4
CA CB
AB
3
Y
Figure 12. Shows connection of a voltmeter to check the actual
value on the spring return.
Performance checks.

9
20200928 Swegon reserves the right to alter specications.
REACT V
Replacing the damper motor
Figure 13. Dismantling the damper motor.
1.Disconnect the cable.
2.Disconnect the measuring tubes.
3.Set damper motor to the open position.
4.Loosen the nuts on the spindle clamp (nuts: 8mm).
5.Dismantle 2 screws for the locking strip (screws: TX20).
6.Lift off the damper motor and spindle adapter
(The rectangular design has a round damper spindle and no spindle adapter).
7.Reassemble in the reverse order.
NOTE!
Normal motor
Positioning of the damper blade and locking strip, see figures 14 and 15.
Figure 15. Damper open. Jumper to the left.Figure 14. Recess in the damper spindle indicates the position
of the damper.

REACT V
10 Swegon reserves the right to alter specications. 20200928
Technical data
IP class: IP42
Corrosivity class: C3
Pressure class: A
Leakage classes according to SS-EN 1751
- Leakage class, casing: C
- Leakage class circular damper, closed: 4
- Leakage class rectangular damper,
closed:
3
Running times open/close (90°):
5 Nm: 100 s
10 / 15 Nm: 150 s
Spring return actuator, running time electricity (90°):
5 Nm: 100 s
10 / 20 Nm: 150 s
Return time spring: max. 20 s (90°)
Ambient temperature
Operation: 0 – +50 °C
Storage: -20 – +50°C
RH: 10 - 95%
(non-condensing)
CE marking: 2006/42/EC (MD)
2014/30/ EU (EMC)
2011/65/EU (RoHS2)
Electrical data
Normal
Power supply: 24 V AC/DC ±20% 50 - 60 Hz
Fixed connection cable,
1000 mm with cable size. 4 x 0.75 mm 2
2 x 0.38 mm 2
Power consumption, for transformer rating:
REACT V 5 Nm 2.5 W 4.0 VA
REACT V 10 Nm 2.5 W 5.5 VA
REACT V 15 Nm 3.0 W 5.5 VA
Spring return
Power supply: 24 V AC/DC ±20% 50 - 60 Hz
Connection to screw terminals,
cable size. 6 x 0.5-2.5 mm 2
Power consumption, for transformer rating:
REACT V-SR 5 Nm 5.6 W 7.8 VA
REACT V-SR 10 Nm 5.6 W 9.3 VA
REACT V-SR 20 Nm 8.6 W 9.3 VA

11
20200928 Swegon reserves the right to alter specications.
REACT V
Declaration of Conformity
Swegon AB hereby affirms that:
REACT V complies with the essential characteristic demands
and relevant regulations specified in the directives, 2006/42/
EC (MD), 2014/30/EU (EMC) and 2011/65/EU (RoHS2):
The following standards have been observed:
EN ISO 12100:2010 Safety of machinery - General principles for
design - Risk assessment and risk mitigation
EN 60204-1:2006 Safety of machinery - Electrical equipment of
machines - Part 1: Generic standards
EN 60730-1:2011 Automatic electrical controls for household
and similar use - Part 1 Generic standards
EN 61000-6-2:2007 Electromagnetic compatibility (EMC). Generic
standards. Immunity for industrial environments
EN 61000-6-3:2007
Electromagnetic compatibility (EMC). Generic
standards. Emission standard for residential,
commercial and light-industrial environments
Person responsible for this declaration:
Name: Freddie Hansson, R&D Manager Tomelilla
Address: Industrigatan 5, 273 21 Tomelilla, Sweden
Date: 200601
This declaration is applicable only if the product has been
installed according to the instructions in this document
and if no modifications or changes have been made on
this product.
References
www.swegon.com
Building Materials Declaration
REACT V Product data sheet
REACT Function Guide
REACT Modbus

REACT V
Table of contents