Parker ALIGN-MG-NA User manual

1
ALIGN™ Multi-Gas Generator
Installation, Operation, and Maintenance Manual
IOM_PKR_Align Multi-Gas Generator_022021.indd 1IOM_PKR_Align Multi-Gas Generator_022021.indd 1 2/17/2021 1:11:40 PM2/17/2021 1:11:40 PM

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL ALIGN™ MULTI-GAS GENERATOR
2
IOM_PKR_Align Multi-Gas Generator_022021.indd 2IOM_PKR_Align Multi-Gas Generator_022021.indd 2 2/17/2021 1:11:40 PM2/17/2021 1:11:40 PM

3
INSTALLATION, OPERATION, AND MAINTENANCE MANUAL ALIGN™ MULTI-GAS GENERATOR
TABLE OF CONTENTS
Page
1. WARRANTY.................................................................................................................................... 4
2. SAFETY INFORMATION ................................................................................................................5
2.1 Markings and Symbols.....................................................................................................6
3. DESCRIPTION................................................................................................................................7
3.1 Intended Use....................................................................................................................7
3.2 Technical Specifications ..................................................................................................7
3.3 Overview of Components.................................................................................................8
3.4 Regulatory Certifications..................................................................................................9
4. INSTALLATION ...........................................................................................................................8
4.1 Receiving the Generator ..................................................................................................9
4.2 Inspecting the Equipment ...............................................................................................10
4.3 Removing the Shipping Brackets....................................................................................10
4.4 Installation Location .....................................................................................................11
4.4.1 Environmental & Space Requirements.............................................................11
4.4.2 Tubing Requirements........................................................................................12
4.4.3 Electrical Supply Requirements ........................................................................12
4.5 Set Up
4.5.1 Generator Set Up..............................................................................................13
4.5.2 Optional Exhaust Vent Installation....................................................................13
5. START UP AND OPERATION.......................................................................................................15
5.1 Start Up ..........................................................................................................................15
5.2 Shutting Down the Generator .........................................................................................16
6. PREVENTATIVE MAINTENANCE & SERVICE.............................................................................17
6.1 Cleaning..........................................................................................................................17
6.2 Service Kits .....................................................................................................................17
6.3 Non-Preventative Maintenance Replacement Parts .......................................................18
7. TROUBLESHOOTING & DIAGNOSTICS ......................................................................................19
7.1 Troubleshooting ..............................................................................................................19
7.2 Error Messages...............................................................................................................20
7.3 Resetting the Temperature Switches .............................................................................21
8. ACCESSORIES .............................................................................................................................22
IOM_PKR_Align Multi-Gas Generator_022021.indd 3IOM_PKR_Align Multi-Gas Generator_022021.indd 3 2/17/2021 1:11:40 PM2/17/2021 1:11:40 PM

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL ALIGN™ MULTI-GAS GENERATOR
4
WARRANTY (NORTH AMERICA ONLY)
FOR INFORMATION CONTACT YOUR LOCAL REPRESENTATIVE
Parker Hannin guarantees to the original purchaser of this product, that if the product fails
or is defective within 12 months from the date of purchase, when this product is operated and maintained
according to the instructions provided with the product, then Parker guarantees, at Parker’s option, to re-
place the product, repair the product, or refund the original price for the product. This warranty applies only
to defects in material or workmanship and does not cover: wear components on compressors, routine main-
tenance recommended by the instructions provided with this product, or lter cartridges. Any modication of
the product without written approval from Parker will result in voiding this warranty. Complete details of the
warranty are available on request. This warranty applies to units purchased in North America.
COMPRESSOR LIMITED WARRANTY
COMPRESSOR 3 YEAR / 10,000 HOUR EXTENDED PARTS LIMITED WARRANTY -
Compressor Manufacturer warrants each Compressor Pump or Scroll Air-End against defects in material or
workmanship from the date of purchase for a period of Three years or 10,000 hours, whichever may occur
rst. This warranty applies to the exchange of part(s) of the compressor pump or air-end found to be defec-
tive by an Authorized Service Center.
COMPRESSOR 1 YEAR / 5,000 HOUR INLET TO OUTLET LIMITED WARRANTY - Compressor
Manufacturer warrants each Compressor Unit, System, Pump, or Air-End against defects in material or
workmanship from the date of purchase for a period of One Year or 5,000 Hours, whichever may occur rst.
This warranty applies to the exchange of defective component part(s) and labor performed by an Authorized
Service Center.
Complete details of the Warranty are available on request.
1. WARRANTY
IOM_PKR_Align Multi-Gas Generator_022021.indd 4IOM_PKR_Align Multi-Gas Generator_022021.indd 4 2/17/2021 1:11:40 PM2/17/2021 1:11:40 PM

5
INSTALLATION, OPERATION, AND MAINTENANCE MANUAL ALIGN™ MULTI-GAS GENERATOR
Do not install and operate this equipment until the safety information and instructions in this user guide have
been read and understood by all personnel concerned.
USER RESPONSIBILITY:
FAILURE OR IMPROPER SELECTION OR IMPROPER USE OF THE PRODUCTS DESCRIBED HEREIN
OR RELATED ITEMS CAN CAUSE DEATH, PERSONAL INJURY AND PROPERTY DAMAGE, AND VOID
THE SAFTEY CERTIFICATION.
This document and other information from Parker Hannin Corporation, its subsidiaries and authorized dis-
tributors provide product or system options for further investigation by users having technical expertise.
The user, through its own analysis and testing, is solely responsible for making the nal selection of the
system and components and assuring that all performance, endurance, maintenance, safety and warning
requirements of the application are met. The user must analyze all aspects of the application, follow appli-
cable industry standards, and follow the information concerning the product in the current product catalogue
and in any other materials provided from Parker or its subsidiaries or authorized distributors.
To the extent that Parker or its subsidiaries or authorized distributors provide component or system options
based upon data or specications provided by the user, the user is responsible for determining that such
data and specications are suitable and sufcient for all applications and reasonably foreseeable uses of
the components or systems.
Only competent personnel trained, qualied, and approved by Parker Hannin should perform installation,
start-up, service and repair procedures.
This equipment is for indoor use only. Do not operate outdoors.
Nitrogen is nontoxic and largely inert. It can act as a simple asphyxiant by displacing oxygen in air. Inhala-
tion of nitrogen in excessive concentrations can result in unconsciousness without any warning symptoms
such as dizziness and fatigue.
The generator should be installed in an area with adequate ventilation to reduce the ammability of the oxy-
gen-rich permeate stream. The system should not be installed in an area where the permeate stream poses
the risk of explosion or combustion.
Use of the equipment in a manner not specied within this user guide may result in an unplanned release of
pressure, which may cause serious personal injury or damage.
When handling, installing, or operating this equipment, personnel must employ safe engineering practices
and observe all related regulations, health & safety procedures, and legal requirements for safety.
Never place liquids on top of the generator.
Do not store anything on top of the generator.
Never sit or climb on top of the generator.
Ensure casters are locked before starting up the generator.
Ensure that the equipment is depressurized and electrically isolated, prior to carrying out any of the sched-
uled maintenance instructions specied within this user guide.
2. SAFETY INFORMATION
IOM_PKR_Align Multi-Gas Generator_022021.indd 5IOM_PKR_Align Multi-Gas Generator_022021.indd 5 2/17/2021 1:11:40 PM2/17/2021 1:11:40 PM

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL ALIGN™ MULTI-GAS GENERATOR
6
Parker Hannin cannot anticipate every possible circumstance which may represent a potential hazard.
The warnings in this manual cover the most known potential hazards, but cannot be all-inclusive. If the
user employs an operating procedure, item of equipment or a method of working which is not specically
recommended by Parker Hannin the user must ensure that the equipment will not be damaged or become
hazardous to persons or property.
Most accidents that occur during the operation and maintenance of machinery are the result of failure to
observe basic safety rules and procedures. Accidents can be avoided by recognizing that any machinery is
potentially hazardous.
Note: Any interference with the calibration warning labels will invalidate the gas generator’s warranty and
may incur costs for the recalibration of the gas generator.
Should you require an extended warranty, tailored service contracts or training on this equipment, or any
other equipment within the Parker Hannin range, please contact your local Parker Hannin ofce. Details
of your nearest Parker Hannin sales ofce can be found at www.parker.com/labgas.
Retain this user guide for future reference.
2.1 Marks and Symbols
The following markings and international symbols are used on the equipment and within this manual:
Marking Description
Electrical Ground
Warning: Do not remove covers while generator
is operational.
Warning: Fans are inside, consult the manual.
Warning: Do not perform maintenance while the
generator is pressurized.
Warning: Exposed electrical connections inside.
Caution
Caution: Electrical Hazard
Warning: Exposed, rotating pulley
When disposing products for end of life including
electronic parts and assemblies, follow local waste
disposal regulations
IOM_PKR_Align Multi-Gas Generator_022021.indd 6IOM_PKR_Align Multi-Gas Generator_022021.indd 6 2/17/2021 1:11:41 PM2/17/2021 1:11:41 PM

7
INSTALLATION, OPERATION, AND MAINTENANCE MANUAL ALIGN™ MULTI-GAS GENERATOR
To guarantee the optimum efciency of the nitrogen and dry air membranes it is recommended that
the ALIGN Multi-Gas Generator be run at or below the recommended pressure and ow for each of
the outlet gases, as laid out in the Technical Specications, Section 3.2.
3 DESCRIPTION
The ALIGN Multi-Gas Generator is intended to supply lab-grade nitrogen, dry air and zero air to
LC-MS and other instrumentation systems within a laboratory setting.
3.1 Intended Use
This specication is valid when the equipment is located, installed, operated, and maintained as
specied within this manual.
3.2 Technical Specications
System Specifications
Regulatory Information
CSA Certification Standard CAN/CSA C22.2 No. 61010-1-12 3rd Edition
IEC Standard IEC 61010-1: 2010
UL Standard UL 61010-1
IEC 61010 Installation Category II
IEC 61010 Pollution Degree 2
Impact Code IK08
EMC Compliance EN61326-1/CISPR 11
Generator Physical Specifications
Dimensions (L x W x H) 34.5” (87.6 cm) x 23.74” (60.3 cm) x 24.62” (62.5 cm)
Product Weight 333 lbs (151 kgs)
Shipping Weight 575 lbs (261 kgs)
Sound Level <55 dB(A) at 1 meter
Heat Dissipation 5221 BTU/Hour
Drain Port 1/4” Tube
Outlet Gas Specifications
Nitrogen Gas Purity1up to 99% N2 with respect to O2
Nitrogen Gas Organics Elimination of up to 99.999% organics
Nitrogen Gas Max Flow/Pressure 19 SLPM/80 psig (5.5 barg, 552 kPa)
Air 1 Purity1<0.1 ppm total hydrocarbons / -35°F (-37°C) atm
dew point
Air 1 Max Flow/Pressure 25 SLPM/110 psig (7.6 barg, 758 kPa)
Air 2 Purity1<0.1 ppm total hydrocarbons / -35°F (-37°C) atm
dew point
Air 2 Max Flow/Pressure 25 SLPM/110 psig (7.6 barg, 758 kPa)
Suspended Liquids None
IOM_PKR_Align Multi-Gas Generator_022021.indd 7IOM_PKR_Align Multi-Gas Generator_022021.indd 7 2/17/2021 1:11:41 PM2/17/2021 1:11:41 PM

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL ALIGN™ MULTI-GAS GENERATOR
8
1For purity at specific flow rates and pressures please contact Parker Hannifin.
For humidity and temperature information outside of this range please contact Parker Hannifin.
3For altitudes outside of this range please contact Parker Hannifin.
3.3 Overview of Components
System Specifications Cont
Outlet Gas Specifications Cont’
Phthalates None
Max Tank Operating Pressure 115±2 psig (7.9±0.1 barg, 793 kPa)
Gas Outlets 1/4’’ NPT
Environmental Requirements
Min/Max Ambient Temperature 60°F/ 85°F (16°C/29°C)
Max Ambient Relative Humidity 243% at 86°F
Max Recommended Operating Altitude 32000 m
Electrical Requirements
Electrical Supply for ALIGN-MG-NA, ALIGN-MG-JA 230VAC ± 15%, 50/60 Hz, 1 Phase, 20A, NEMA 6-20R receptacle
Electrical Supply for ALIGN-MG-WD 230VAC ± 15%, 50/60 Hz, 1 Phase, 32A, IP44 receptacle
Power Consumption 15A@230VAC, 2500 Watts
Fuses (F1, F2) JJS Class T, 600V, 25A, 14.2 mm Dia x 38.1 mm
IOM_PKR_Align Multi-Gas Generator_022021.indd 8IOM_PKR_Align Multi-Gas Generator_022021.indd 8 2/17/2021 1:11:43 PM2/17/2021 1:11:43 PM

9
INSTALLATION, OPERATION, AND MAINTENANCE MANUAL ALIGN™ MULTI-GAS GENERATOR
3.4 Regulatory Certications
The generator is certied to the electrical safety requirements as specied by the IEC, UL, and CSA
Standards by the certifying agency, the CSA Group. All three models carry the CSA and CE marking and
are certied to the CB Scheme.
This product meets EMC compliance. The internal receiver tank is CRN registered and ASTM certied.
4 INSTALLATION
4.1. Receiving the Generator
All installation, operation, and maintenance activities for the ALIGN Multi-Gas Generator should be
performed by trained personnel practicing appropriate health and safety practices to avoid personal
injury or damage.
The ALIGN Multi-Gas Generator is packed in a wooden shipping container. Upon receipt of the
product, carefully inspect the packaging for damage. If the packaging is damaged, inform the delivery
company immediately and contact Parker Hannin Customer Service at 800-343-4048.
Remove the wire L-shaped fasteners from the indicated side of the container (see Figures 1&2).
DO NOT ATTEMPT TO LIFT THE GENERATOR FROM THE CONTAINER.
DO NOT MOVE THE GENERATOR BEFORE SECURING THE RAMP.
Fold down the side of the crate so it can be used as a ramp. Securing pins are located at the bottom
of the crate. Insert these pins into the holes at the top of the ramp. Remove the shelf and foam around
the generator. Remove the components and accessories from the shelf inside the crate.
Figure 1 Figure 2
Perform with 2 people: Release the generator’s locked casters and carefully guide the generator
down the ramp. Move the generator and installation kit to its installation location.
(see Figures 3-6)
IOM_PKR_Align Multi-Gas Generator_022021.indd 9IOM_PKR_Align Multi-Gas Generator_022021.indd 9 2/17/2021 1:11:45 PM2/17/2021 1:11:45 PM

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL ALIGN™ MULTI-GAS GENERATOR
10
4.2. Inspect the Equipment
DO NOT ATTEMPT TO POWER UP THE GENERATOR UNTIL COMPLETING ALL STEPS BELOW.
Inspect the generator and check for signs of damage. Verify that the following items are included with
the shipment:
If the generator is damaged or any items are missing, inform the delivery company immediately and contact
Parker Hannin.
Qty Description
1 Drain Silencer Assembly
1 Condensate Bottle
3 ¼’’ NPT to ¼’ Tubing Elbow
1 Power Cord
3 50’ Tubing
1 Tube Cutter
2 Spare Fuses
4.3. Removing the Internal Shipping Brackets
Figure 6Figure 3
Remove
Foam
Unlock Casters
Ramp Pin
Inserts
The generator is shipped with internal brackets to prevent damage during transit. To access these brack-
ets, remove the front and rear panels of the generator using a medium Philips screwdriver. The rear panel
screws are covered by caps that can be removed using a small flathead screwdriver. Next, locate and
remove the yellow brackets from the generator by removing the four securing bolts with a 9/16’’
socket wrench. (See Figures 7-10)
Please retain these brackets, as they must be re-installed if the generator is transported at any
time in the future.
Figure 4 Figure 5
IOM_PKR_Align Multi-Gas Generator_022021.indd 10IOM_PKR_Align Multi-Gas Generator_022021.indd 10 2/17/2021 1:11:56 PM2/17/2021 1:11:56 PM

11
INSTALLATION, OPERATION, AND MAINTENANCE MANUAL ALIGN™ MULTI-GAS GENERATOR
Replace front and rear panels before proceeding.
4.4. Choosing an Installation Location
This equipment is not suitable for use in any hazardous, ammable, or explosive environments.
Keep the generator away from excessive heat and open flame.
The accumulation of nitrogen can displace oxygen thereby creating an asphyxiation hazard.
Always ensure that the equipment is operated in a well-ventilated area.
Locate the generator as close to the instrument as possible following the requirements given below:
4.4.1. Environmental & Space Requirements
The generator is for indoor use only. Do not install outdoors. The generator must be installed
in a climate-controlled room, meeting the environmental specications set in Section 3.2.
It is critical that nothing is placed within 12 inches of the exhaust vent, located at the left rear
side of the generator. An optional Vent Kit is available to route exhaust heat away from the
generator, see Section 8 for purchasing information.
Do not install the generator where hot exhaust air from other equipment may be drawn into
the intake at the rear of the generator. The area should be free of excessive dust, toxic or
flammable gases, solvent fumes, and moisture.
Figure 7 Figure 8
Figure 9 Figure 10
IOM_PKR_Align Multi-Gas Generator_022021.indd 11IOM_PKR_Align Multi-Gas Generator_022021.indd 11 2/17/2021 1:11:57 PM2/17/2021 1:11:57 PM

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL ALIGN™ MULTI-GAS GENERATOR
12
4.4.2. Tubing Requirements
Temperature or humidity variation along the length of tubing may affect gas purity. When possi-
ble, avoid placing the generator in a separate room and running tubing through walls and ceilings.
When tubing is open to atmosphere, it’s recommended to purge the lines before connecting to the
instrument.
Additional generator-approved tubing is available from Parker Hannin. Any tubing used must be
phthalate-free. Use of non-approved tubing may reduce gas purity. See Section 8 for ordering
details.
4.4.3. Electrical Supply Requirements
Parker supplies a step-up transformer for installations where the voltage may drop below
195VAC and a step-down transformer if the facility voltage may reach 255 VAC or higher. See
Section 8 for ordering details.
Do not position the equipment so that it is difcult to operate or disconnect the plug from
the electrical supply. The equipment is connected to protective earth (ground) through
the power cord. It is essential that electrical supply is equipped with a protective earth
(ground) terminal. Do not use alternative power cords.
Location of the generator with proper ventilation is critical. Install the generator in a clean, well
ventilated area. To provide adequate ventilation and access for service, a minimum of 6 inches
clearance is required behind the generator (see Figure 11). Fresh intake air enters from un-
derneath the generator at the rear. Warm exhaust air exits from the left, rear side, which must
always be kept clear. A minimum of 12 inches clearance is required on the left side of the
generator (see Figure 11).
Figure 11
IOM_PKR_Align Multi-Gas Generator_022021.indd 12IOM_PKR_Align Multi-Gas Generator_022021.indd 12 2/17/2021 1:12:02 PM2/17/2021 1:12:02 PM

13
INSTALLATION, OPERATION, AND MAINTENANCE MANUAL ALIGN™ MULTI-GAS GENERATOR
The supply line should be dedicated to the generator. No other equipment should operate using
the same line. It is the customer’s responsibility to provide a fused electrical supply to the gener-
ator. It is recommended that this supply have surge protection. (See Section 3.2 for the electrical
specication).
Only Parker Hannin-approved power cords should be used. The power cord technical speci-
cations can be found in Table 2 below. See Section 8 for ordering details should you need a
replacement power cord.
Generator
Part Number Region Electrical
Specifications
Physical
Specifications
Regulatory
Specifications
ALIGN-MG-NA North America 20A, 250VAC 12AWG/3, SJT, 8 Ft. CSA, UL
ALIGN-MG-JA Japan 20A, 250VAC 12AWG/3, PSE, 8 Ft. PSE, JET
ALIGN-MG-WD
Europe, India, UK 32A, 250VAC 10AWG/3, PCE, 8 Ft.
WDE, IMQ-HD-22,
IP44, IEC309/1+2,
CEE17, BS4343
China 32A, 250VAC 10AWG/3, PCE, 8 Ft. VDE, IMQ-HD-22,
CE, OVE, CCC
Australia 32A, 250VAC 10AWG/3, PCE, 8 Ft. VDE, IMQ-HD-22
Table 2. Power Cords
4.5 SET UP
4.5.1 Generator Set Up
1. Ensure that the installation location has been chosen in accordance with the requirements in
Section 4.4.
2. Install the three NPT-1/4’’ tubing elbows to the three gas outlets using a 9/16’’ wrench.
3. Press the drain tubing assembly into the elbow marked “DRAIN” at the rear of the generator.
Place the blue silencer in the supplied drain bottle or other approved drainage system.
4. For each of the three outlets, cut tubing to the appropriate length to connect the generator to
the instrument. Press the tubing into the three elbows, but do not connect the tubing to the
instrument.
Reference Figure 12 below for clarication on Steps 2-4.
Once equipment has been installed in the chosen location, lock all four casters.
IOM_PKR_Align Multi-Gas Generator_022021.indd 13IOM_PKR_Align Multi-Gas Generator_022021.indd 13 2/17/2021 1:12:02 PM2/17/2021 1:12:02 PM

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL ALIGN™ MULTI-GAS GENERATOR
14
4.5.2 Optional Exhaust Vent Installation
Parker Hannin offers the option to vent the exhaust heat away from the generator using the Exhaust
Vent Kit (part #B06-0394).
To install:
1. Screw the six cap screws into the threaded holes around the generator’s vent using the supplied
5/32” hex key. Screws will stand out from the surface of the sheetmetal.
2. Install the exhaust vent by placing it over the screws and sliding down until it is fully seated.
3. Secure the ducting using the supplied clamps. Route to the desired exhaust location.
For duct lengths above 15 ft, use of the Exhaust Vent Booster Fan (part #B06-0398) with the Exhaust
Vent Duct Extension (part #B04-0693) is required.
Reference Figures 13 & 14 for clarication on installation of the Exhaust Vent Kit and a depiction of how
to assemble the Exhaust Vent Booster Fan and Duct Extension.
Figure 12
IOM_PKR_Align Multi-Gas Generator_022021.indd 14IOM_PKR_Align Multi-Gas Generator_022021.indd 14 2/17/2021 1:12:07 PM2/17/2021 1:12:07 PM

15
INSTALLATION, OPERATION, AND MAINTENANCE MANUAL ALIGN™ MULTI-GAS GENERATOR
5. START-UP AND OPERATION
Only competent personnel trained, qualied, and approved by Parker Hannin should perform
commissioning procedures.
5.1. Start-Up
Before attempting start-up, ensure that the shipping brackets have been removed, as laid out in
Section 4.3. Ensure that the outlet tubing is not connected to the instrument and the outlet valves
are closed before attempting start-up.
1. Plug the power cord into the receptacle at the rear of the generator. Then, insert the cord into
the designated power supply. See Section 3.2 for further details on the electrical
requirements.
2. Press the green POWER button on the front panel of the generator. The generator will start,
and the green LED will illuminate while the motor ramps up to its maximum speed.
3. Open the cover of the Pressure Control Panel on the top of the generator by pressing down to
release the latch to read the TANK PRESSURE gauge. The generator should reach a steady
state pressure of 115 psig in about a minute. Note: the speed of the motor at normal opera-
tion will vary depending on pressure and ow demands and will not always need to run at full
speed.
4. Pull up on the pressure regulator knobs to unlock them. One at a time, adjust the pressure
regulators to 20 psi.
5. Ensure that the outlet tubing is disconnected from the instrument to perform the initial purge
and allow the generator to reach operating temperature. Slowly turn the yellow valve handles
at the rear of the generator, approximately 10°-20° so that gas is venting to atmosphere. Allow
the gases to purge for an hour, then close the valves.
6. Connect the tubing to the instrument but do not open the valves on the generator.
7. Adjust the pressure regulators to the instrument specications.
Figure 13 Figure 14
Perform this Start-Up procedure upon initial receipt of the generator and any time the generator
is being restarted from cold. Purging the lines and allowing the generator to reach operating
temperature are critical in ensuring gas purity.
IOM_PKR_Align Multi-Gas Generator_022021.indd 15IOM_PKR_Align Multi-Gas Generator_022021.indd 15 2/17/2021 1:12:07 PM2/17/2021 1:12:07 PM

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL ALIGN™ MULTI-GAS GENERATOR
16
8. Slowly, fully open the valves to allow the ow of gas to the instrument.
9. As the instrument begins to draw gas from the generator the readings on the pressure gauges
may change. Adjust the gas pressures as needed using the regulator knobs.
10. Once the pressure is set, press down on the regulator knobs to lock them in place. If the
pressure needs to be adjusted in the future, pull up on the knobs to unlock them.
5.2. Shutting Down the Generator
1. Ensure that gas is no longer required by the instrument. Keep the yellow outlet valves open.
2. Switch the generator off by pressing the green POWER button.
3. Depressurize the system:
a. PREFERRED METHOD: Wait at least 20 minutes for the generator to depressurize.
b. QUICK METHOD (~2 Min): Unplug the generator from the wall. Open the front panel by
loosening the two retaining screws at the bottom. Next, slightly loosen the two brass bleed
screws on the bottom of the two right-most blue lters. DO NOT FULLY REMOVE THE
BRASS BLEED SCREWS. See Figure 14 below for clarication. When the tank pressure
gauge reads zero, tighten the brass bleed screws.
4. Disconnect the power cord from the supply. Fully close all 3 outlet valves using the yellow valve
handles. The generator is now fully shut down and ready for transportation or service.
5. To transport the generator:
a. Disconnect the tubing from the instrument’s inlets and the generator’s outlets. Disconnect
the drain tube assembly and the power cord from the generator. Reinstall the shipping
brackets as shown in Section 4.3.
b. Unlock the casters and move the generator using at least two people.
c. Repack the generator in the shipping crate by following the steps in Section 4.3 in reverse
order. New crates and shipping brackets can be ordered from Parker. See Accessories in
Section 8 for more information.
Bleed Screw
Figure 14
IOM_PKR_Align Multi-Gas Generator_022021.indd 16IOM_PKR_Align Multi-Gas Generator_022021.indd 16 2/17/2021 1:12:08 PM2/17/2021 1:12:08 PM

17
INSTALLATION, OPERATION, AND MAINTENANCE MANUAL ALIGN™ MULTI-GAS GENERATOR
6. PREVENTATIVE MAINTENANCE
The recommended service procedures identied below, along with all other repair and calibration work,
should be undertaken by a Parker Hannin-approved technician.
Figure 15 details the service intervals for the ALIGN Multi-Gas Generator. Failure to follow these intervals
may void the warranty.
DO NOT perform service or cleaning on the generator while it is plugged in.
6.1. Cleaning
Inspect the inlet air duct underneath the rear of the generator daily to ensure it is unobstructed and clear of
dust and debris.
If required, clean the outside of the generator with a damp cloth. Avoid excessive moisture around any electri-
cal sockets and labels. A mild detergent may be used, however, do not use abrasives or solvents.
6.2. Service Kits
12 month Service Kit
Required Every 8000Hrs or 12 Months (Whichever Comes First).
Part Number: MKALIGN-MG-1
V-Belt Carbon Tower BX-Filter Element DX-FIlter Element Water Separator
Intake Filter Tip Seals Pipe Sleeve Drain Silencer Particulate Filter
Eco Drain Assy
Kit Part Number 12 Months / 8,000
Hours
24 Months / 16,000
Hours
36 Months / 24,000
Hours
48 Months / 32,000
Hours
MKALIGN-MG-1 X X X
MKALIGN-MG-2 X
Figure 15
Grease Gun Kit
IOM_PKR_Align Multi-Gas Generator_022021.indd 17IOM_PKR_Align Multi-Gas Generator_022021.indd 17 2/17/2021 1:12:15 PM2/17/2021 1:12:15 PM

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL ALIGN™ MULTI-GAS GENERATOR
18
48 month Service Kit
Required Every 32,000Hrs or 48 Months (Whichever Comes First)
Part Number: MKALIGN-MG-2
V-Belt Carbon Tower BX-Filter Element DX-FIlter Element Water Separator
Intake Filter Drain Silencer Particulate Filter Eco Drain AssyCompressor
6.3. Non-Preventative Maintenance Replacement Parts
Description Part Number
Filter Autodrain B06-0346
Dryer Membrane B06-0391
Nitrogen Membrane B06-0390
Motor B06-0363
Pressure Regulator A01-0549
Installation Kit B06-0362
Gas Generation Sub-Assembly B06-0399
Power Cord See Table in Section 8
Motor Mount B06-0286
25A Fuse A03-0529
IOM_PKR_Align Multi-Gas Generator_022021.indd 18IOM_PKR_Align Multi-Gas Generator_022021.indd 18 2/17/2021 1:12:17 PM2/17/2021 1:12:17 PM

19
INSTALLATION, OPERATION, AND MAINTENANCE MANUAL ALIGN™ MULTI-GAS GENERATOR
7. TROUBLESHOOTING & DIAGNOSTICS
There are potential safety risks to performing troubleshooting activities. The provided pro-
tective measures must be followed to ensure personnel safety. All troubleshooting activities
should only be performed while the generator is powered off, depressurized, and unplugged
from its power source while wearing safety glasses and gloves.
The personnel will verify the safe state of the generator after the maintenance or repair is com-
pleted.
Problem:
The generator has turned off and the red “SYSTEM FAULT” LED
light is on.
1. Depressurize the generator as outlined in Section 5.2.
2. Remove the front panel by unscrewing the two retaining screws. See Figure 11 for details.
Do not reach inside of the generator while it is still powered.
3. Read the error message from the LED display on the VFD, located in the upper left-hand
corner.
4. Record the error message and reinstall the front panel.
5. If the error message is listed in Section 7.2 below, follow the corresponding instructions.
6. If the error message is not listed, call Parker HanninTechnical Support for help diagnosing
Problem:
Instrument is not receiving an adequate gas supply, but the
generator is still operational.
1. Check that the yellow valve handles are in-line with the silver outlets
(in the “open” conguration).
2. Check that the pressure regulators are set to meet the instrument’s needs.
3. If problem persists: Depressurize the generator as outlined in Section 5.2. Do not unplug the
generator at this time. Call Parker Technical Support at 1-800-343-4048 or send an email to
To Troubleshoot:
To Troubleshoot:
7.1. Troubleshooting
IOM_PKR_Align Multi-Gas Generator_022021.indd 19IOM_PKR_Align Multi-Gas Generator_022021.indd 19 2/17/2021 1:12:17 PM2/17/2021 1:12:17 PM

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL ALIGN™ MULTI-GAS GENERATOR
20
7.2 Error Messages
Fault Description Troubleshooting
GP Ground Fault • Contact Parker Technical Support for a technician to inspect
the motor.
LU Under
Voltage
Protection
• This error indicates low supply voltage. Check that the supply
voltage meets the requirements in Section 3.2.
• Install a voltage booster. Available from Parker Hannifin. See
Accessories in Section 8.
OC1 Overcurrent • Contact Parker Technical Support for a technician to inspect the
motor.
OE DC
Over-Voltage
• This error indicates high supply voltage. Check that the supply
voltage meets the requirements in Section 3.2.
• Install a voltage reducer. Available from Parker Hannifin. See
Accessories in Section 8.
PF1 Input Phase
Loss
• Check that the power supply meets the requirements in Table/
Section 3.2.
PF0 Output
Phase Loss
• Contact Parker Technical Support for a technician to inspect the
motor.
ESP Input Signal
Fault
• Follow the procedure laid out in Section 7.3. If the SYSTEM
FAULT light remains on, contact Parker Technical Support.
IOM_PKR_Align Multi-Gas Generator_022021.indd 20IOM_PKR_Align Multi-Gas Generator_022021.indd 20 2/17/2021 1:12:18 PM2/17/2021 1:12:18 PM
This manual suits for next models
2
Table of contents
Other Parker Laboratory Equipment manuals
Popular Laboratory Equipment manuals by other brands

Roche
Roche cobas h232 Quick reference guide

Medem
Medem SEC-Lw installation instructions

Buchi
Buchi V-300 Operation manual

ASEG GALLONI
ASEG GALLONI MODULAR 6 Operating and maintenance manual

Novasina
Novasina LabMaster-aw operating instructions

Waters
Waters TA Instruments Sample/Temperature Stage Operator's guide