Synapse BMS-GW Series User guide

Document Revision: 1.A
Auto Discovery
Template Revision: 3
BMS Gateway BMS-GW (ProtoAir FPA-W44)
Start-up Guide
For Interfacing the SimplySNAP Site Controller
(SS420/450)
To Building Automation Systems:
BACnet MS/TP, BACnet/IP, Modbus RTU and Modbus TCP/IP
APPLICABILITY & EFFECTIVITY
Explains BSM-GW/ProtoAir hardware and how to install it.
The instructions are effective for the above as of February 2019.

SimplySNAP BMS Gateway/ProtoAir Start-up Guide
Contact Information
Technical Support
Thank you for purchasing the BMS Gateway/ProtoAir from Synapse Wireless.
Please call Synapse Wireless for technical support of the BMS Gateway/ProtoAir product.
Sierra Monitor Corporation does not provide direct support. If Synapse Wireless needs to escalate the
concern, they will contact Sierra Monitor Corporation for assistance.
Support Contact Information:
Synapse Wireless
6723 Odyssey Drive
Huntsville, Alabama 35806
Customer Service:
877-982-7888
Website: www.synapsewireless.com
Additionally, a ticket can be opened at www.synapse-wireless.com/resources/contact-support/

SimplySNAP BMS Gateway/ProtoAir Start-up Guide
Quick Start Guide
Quick Start Guide
1. Record the information about the unit. (Section 3.1)
2. Configure COM settings for the device to connect to the BMS-GW/ProtoAir. (Section 3.2)
3. Connect the BMS-GW/ProtoAir 3 pin RS-485 R2 port to the field protocol cabling. (Section 4.1)
4. Connect power to the BMS-GW/ProtoAir’s 3 pin connector. (Section 4.4)
5. Connect a PC to the BMS-GW/ProtoAir via Ethernet cable or by the BMS-GW/ProtoAir’s Wi-Fi Access
Point. (Section 5)
6. Set the field protocol settings via the Web Configurator. (Section 7.1)
7. Use the Discovery function to configure the BMS-GW/ProtoAir and to find any connected devices.
(Section 7.2)

SimplySNAP BMS Gateway/ProtoAir Start-up Guide
Table of Contents
TABLE OF CONTENTS
1Certification..........................................................................................................................................7
1.1 BTL Mark –BACnet®Testing Laboratory.......................................................................................7
2Introduction..........................................................................................................................................8
2.1 ProtoAir Gateway............................................................................................................................8
3ProtoAir Setup......................................................................................................................................9
3.1 Record Identification Data ..............................................................................................................9
3.2 Configuring Device Communications .............................................................................................9
3.3 Attaching the Antenna ....................................................................................................................9
4Interface the ProtoAir to Devices.....................................................................................................10
4.1Wiring Field Port to RS-485 Serial Network .................................................................................10
4.2 Bias Resistors...............................................................................................................................11
4.3 Termination Resistor.....................................................................................................................12
4.4 Power-Up ProtoAir........................................................................................................................13
5Connect the PC to the ProtoAir........................................................................................................14
5.1 Connecting to the ProtoAir via Ethernet.......................................................................................14
5.1.1 Enable Access Through the Local Browser ..........................................................................14
5.1.1.1 Changing the Subnet of the Connected PC...................................................................14
5.1.1.2 Changing the IP Address of the ProtoAir with FieldServer Toolbox..............................15
5.2 Connecting to the ProtoAir Over Wi-Fi Access Point...................................................................16
6Update Network Settings ..................................................................................................................17
6.1.1 Common Settings..................................................................................................................18
6.1.2 Update Wired Network Settings............................................................................................19
6.1.3 Update Wi-Fi Client Settings.................................................................................................20
7Configure the ProtoAir......................................................................................................................21
7.1 Select BMS Protocol and Configure Settings...............................................................................21
7.1.1 BACnet Settings –Additional Information.............................................................................22
7.1.1.1 Setting the MAC Address for the BACnet MS/TP Network............................................22
7.1.1.2 Set the ProtoAir BACnet Device Instance......................................................................23
7.1.2 Modbus Settings –Additional Information.............................................................................24
7.1.2.1 Setting the Modbus Slave ID..........................................................................................25
7.2Discover Devices Connected to the ProtoAir ...............................................................................26
7.3 Configure Devices and Data Points..............................................................................................27
7.3.1 General Configuration Instructions........................................................................................27
7.3.2 Modbus Map Window............................................................................................................29
7.4 Clearing Configuration..................................................................................................................30
Appendix A Troubleshooting...................................................................................................................31
Appendix A.1 Lost or Incorrect IP Address .............................................................................................31
Appendix A.2 Viewing Diagnostic Information ........................................................................................32
Appendix A.3 Checking Wiring and Settings...........................................................................................33
Appendix A.4 LED Diagnostics for Communications Between ProtoAir and Devices............................34
Appendix A.5 Taking a FieldServer Diagnostic Capture.........................................................................35
Appendix A.5.1 Using the FieldServer Toolbox...................................................................................35
Appendix A.5.2 Using FS-GUI.............................................................................................................38
Appendix A.6 Wi-Fi Signal Strength........................................................................................................39
Appendix A.7 Factory Reset Instructions ................................................................................................39
Appendix A.8 Kaspersky Endpoint Security 10.......................................................................................40

SimplySNAP BMS Gateway/ProtoAir Start-up Guide
Table of Contents
Appendix B Additional Information.........................................................................................................41
Appendix B.1 SSL/TLS for Secure Connection.......................................................................................41
Appendix B.1.1 Configuring FieldServer as a SSL/TLS Server ..........................................................41
Appendix B.1.1.1 Simple Secure Server Configuration ...................................................................41
Appendix B.1.1.2 Limiting Client Access..........................................................................................42
Appendix B.1.1.3 Upload the Authority File to the FieldServer........................................................42
Appendix B.1.1.4 Certificate Validation Options ..............................................................................43
Appendix B.1.1.5 Set up Server Certificate .....................................................................................43
Appendix B.1.2 Configuring FieldServer as SSL/TLS Client...............................................................44
Appendix B.1.2.1 Simple Secure Client Configuration.....................................................................44
Appendix B.1.2.2 Limit Server Access.............................................................................................44
Appendix B.1.2.3 Certificate Validation Options ..............................................................................44
Appendix B.1.2.4 Set up Client Certificate.......................................................................................44
Appendix B.2 Updating Firmware............................................................................................................45
Appendix B.3 BACnet: Setting Network_Number for More Than One ProtoAir on the Subnet..............45
Appendix B.4 Securing ProtoAir with Passwords....................................................................................46
Appendix B.5 Wi-Fi Access Point Network Settings ...............................................................................47
Appendix B.6 Mounting ...........................................................................................................................48
Appendix B.7 Physical Dimension Drawing ............................................................................................49
Appendix B.8 Structure of the Device Tree.............................................................................................50
Appendix C Reference..............................................................................................................................51
Appendix C.1 Specifications....................................................................................................................51
Appendix C.1.1 Compliance with UL Regulations...............................................................................51
Appendix D Limited 2 Year Warranty......................................................................................................52

SimplySNAP BMS Gateway/ProtoAir Start-up Guide
Page 6 of 52
LIST OF FIGURES
Figure 1: ProtoAir Part Numbers...................................................................................................................9
Figure 2: Connection from ProtoAir to RS-485 Field Network....................................................................10
Figure 3: Bias Resistor DIP Switches .........................................................................................................11
Figure 4: Termination Resistor DIP Switch.................................................................................................12
Figure 5: Required Current Draw for the ProtoAir.......................................................................................13
Figure 6: Power Connections......................................................................................................................13
Figure 7: Ethernet Port Location.................................................................................................................14
Figure 8: Web Configurator Landing Page –Showing Network Settings Tab............................................17
Figure 9: Common Network Settings..........................................................................................................18
Figure 10: Ethernet Port Network Settings .................................................................................................19
Figure 11: Wi-Fi Client Network Settings....................................................................................................20
Figure 12: Select BMS Protocol..................................................................................................................21
Figure 13: BACnet MS/TP Settings Window...............................................................................................22
Figure 14: BACnet/IP Settings Window ......................................................................................................23
Figure 15: Modbus RTU Settings Window..................................................................................................24
Figure 16: Modbus TCP/IP Settings Window –Using Slave ID..................................................................25
Figure 17: Modbus TCP/IP Settings Window –Using Slave ID Offset.......................................................25
Figure 18: Discovery Window .....................................................................................................................26
Figure 19: Discovering Devices ..................................................................................................................26
Figure 20: The Device Tree ........................................................................................................................27
Figure 21: View & Change Parameters on a Point.....................................................................................27
Figure 22: View & Edit Node Parameters...................................................................................................28
Figure 23: Saving Configurations................................................................................................................28
Figure 24: Saved Configurations ................................................................................................................28
Figure 25: Modbus Map Window ................................................................................................................29
Figure 26: Saved Configurations ................................................................................................................29
Figure 27: Clear Configuration Window......................................................................................................30
Figure 28: Ethernet Port Location...............................................................................................................31
Figure 29: Error Messages Screen.............................................................................................................32
Figure 30: Nodes Information Screen.........................................................................................................32
Figure 31: Diagnostic LEDs ........................................................................................................................34
Figure 32: Ethernet Port Location...............................................................................................................35
Figure 33: Wi-Fi Signal Strength Listing .....................................................................................................39
Figure 34: Kaspersky ES10 Settings ..........................................................................................................40
Figure 35: Web Anti-Virus Trusted URLs....................................................................................................40
Figure 36: Web Configurator –Network Number Field...............................................................................45
Figure 37: FS-GUI Passwords Page...........................................................................................................46
Figure 38: Password Recovery Page .........................................................................................................46
Figure 39: Wi-Fi AP Network Settings ........................................................................................................47
Figure 40: DIN Rail......................................................................................................................................48
Figure 41: ProtoAir FPA-W44 Dimensions .................................................................................................49
Figure 42: Specifications.............................................................................................................................51

SimplySNAP BMS Gateway/ProtoAir Start-up Guide
Page 7 of 52
1 CERTIFICATION
1.1 BTL Mark –BACnet®
1
Testing Laboratory
1
BACnet is a registered trademark of ASHRAE
The BTL Mark on ProtoAir is a symbol that indicates that a product has
passed a series of rigorous tests conducted by an independent laboratory
which verifies that the product correctly implements the BACnet features
claimed in the listing. The mark is a symbol of a high-quality BACnet product.
Go to www.BACnetInternational.net for more information about the BACnet
Testing Laboratory. Click here for the BACnet PIC Statement.

SimplySNAP BMS Gateway/ProtoAir Start-up Guide
Page 8 of 52
2 INTRODUCTION
2.1 ProtoAir Gateway
NOTE: The BMS Gateway (BMS-GW) is a co-branded hardware and software solution
manufactured by Sierra Monitor Corporation (SMC). The Synaspe Wireless p/n for this
product is BMS-GW. However, within this document, the BMS-GW will be referred to as the
ProtoAir, which is the product name provided by SMC.
The ProtoAir wireless gateway is an external, high performance building automation multi-protocol
gateway that is preconfigured to auto-discover the SimplySNAP site controller SS420/450 (hereafter simply
called “device”) connected to the ProtoAir and automatically configures them for BACnet/IP, BACnet
MS/TP, Modbus TCP/IP and Modbus RTU.
It is not necessary to download any configuration files to support the required applications. The ProtoAir is
pre-loaded with tested profiles/configurations for the supported devices.
FPA-W44 Connectivity Diagram:
The ProtoAir can connect with Sierra Monitor’s SMC Cloud. The SMC Cloud allows technicians, the OEM's
support team and Sierra Monitor's support team to remotely connect to the ProtoAir. The SMC Cloud
provides the following capabilities for any registered devices in the field:
•Remotely monitor and control devices.
•Collect device data and view it on the SMC Cloud Dashboard and the SMC Smart Phone App.
•Create user defined device notifications (alarm, trouble and warning) via SMS and/or Email.
•Generate diagnostic captures (as needed for troubleshooting) without going to the site.
For more information about the SMC Cloud, refer to the SMC Cloud Start-up Guide.

SimplySNAP BMS Gateway/ProtoAir Start-up Guide
Page 9 of 52
3 PROTOAIR SETUP
3.1 Record Identification Data
Each ProtoAir has a unique part number located on the side or the back of the unit. This number should be
recorded, as it may be required for technical support. The numbers are as follows:
Model
Part Number
ProtoAir
FPA-W44-1620
Figure 1: ProtoAir Part Numbers
•FPA-W44 units have the following 3 ports: RS-485 + Ethernet + RS-485
3.2 Configuring Device Communications
•The device needs to be on the same IP subnet as the ProtoAir and the configuration PC.
•Record the following device information:
oIP Address
oIP Port
oUsername
oPassword
NOTE: This information is required for Section 7.
3.3 Attaching the Antenna
Wi-Fi Antenna:
Screw in the Wi-Fi antenna to the front of the unit as shown in Figure 41.
NOTE: Using an external antenna is also an option. An external antenna can be plugged into the
SMA connector. The best antenna for the job depends on the range, topography and
obstacles between the two radios.

SimplySNAP BMS Gateway/ProtoAir Start-up Guide
Page 10 of 52
4 INTERFACE THE PROTOAIR TO DEVICES
4.1 Wiring Field Port to RS-485 Serial Network
•Connect the RS-485 network wires to the 3-pin RS-485 connector on the R2 port. (Figure 2)
oUse standard grounding principles for RS-485 GND
•See Section 6 for information on connecting to an Ethernet network.
BMS
Wiring
ProtoAir
Pin #
Pin
Assignment
RS-485 +
Pin 1
RS-485 +
RS-485 -
Pin 2
RS-485 -
-
Pin 3
RS-485 GND
Figure 2: Connection from ProtoAir to RS-485 Field Network
G
-
+

SimplySNAP BMS Gateway/ProtoAir Start-up Guide
Page 11 of 52
4.2 Bias Resistors
To enable Bias Resistors, move both the BIAS- and BIAS+ dip switches to the right as shown in
Figure 3.
The ProtoAir bias resistors are used to keep the RS-485 bus to a known state, when there is no
transmission on the line (bus is idling), to help prevent false bits of data from being detected. The bias
resistors typically pull one line high and the other low - far away from the decision point of the logic.
The bias resistor is 510 ohms which is in line with the BACnet spec. It should only be enabled at one
point on the bus (for example, on the field port were there are very weak bias resistors of 100k). Since
there are no jumpers, many gateways can be put on the network without running into the bias resistor
limit which is < 500 ohms.
NOTE: See www.ni.com/support/serial/resinfo.htm for additional pictures and notes.
NOTE: The R1 and R2 DIP Switches apply settings to the respective serial port.
NOTE: If the gateway is already powered on, DIP switch settings will not take effect unless the
unit is power cycled.
R1 Bias Resistor DIP
Switches (2 and 3)
Figure 3: Bias Resistor DIP Switches
R2 Bias Resistor DIP
Switches (2 and 3)

SimplySNAP BMS Gateway/ProtoAir Start-up Guide
Page 12 of 52
4.3 Termination Resistor
If the ProtoAir is the last device on the serial trunk, then the End-Of-Line Termination Switch needs to be
enabled. To enable the Termination Resistor, move the TERM dip switch to the right as shown in
Figure 4.
Termination resistor is also used to reduce noise. It pulls the two lines of an idle bus together. However,
the resistor would override the effect of any bias resistors if connected.
NOTE: The R1 and R2 DIP Switches apply settings to the respective serial port.
NOTE: If the gateway is already powered on, DIP switch settings will not take effect unless the
unit is power cycled.
R1 Termination
Resistor DIP Switch (1)
Figure 4: Termination Resistor DIP Switch
R2 Termination
Resistor DIP Switch (1)

SimplySNAP BMS Gateway/ProtoAir Start-up Guide
Page 13 of 52
4.4 Power-Up ProtoAir
Check power requirements in the table below:
Power Requirement for ProtoAir External Gateway
Current Draw Type
ProtoAir Family
12VDC
24V DC/AC
FPA –W44 (Typical)
250mA
125mA
NOTE: These values are ‘nominal’ and a safety margin should be added to the power supply of
the host system. A safety margin of 25% is recommended.
Figure 5: Required Current Draw for the ProtoAir
Apply power to the ProtoAir as shown below in Figure 6. Ensure that the power supply used complies with
the specifications provided in Appendix C.1.
•The ProtoAir accepts 12-24VDC or 24VAC on pins 4 and 5.
•Frame GND should be connected.
Power to
ProtoAir
ProtoAir
Pin #
Pin
Assignment
Power In (+)
Pin 4
V +
Power In (-)
Pin 5
V -
Frame Ground
Pin 6
FRAME GND
Figure 6: Power Connections

SimplySNAP BMS Gateway/ProtoAir Start-up Guide
Page 14 of 52
5 CONNECT THE PC TO THE PROTOAIR
There are two ways to connect the PC to the ProtoAir, either by Ethernet cable (Section 5.1) or Wi-Fi
Access Point (Section 5.2).
5.1 Connecting to the ProtoAir via Ethernet
First, connect a Cat-5 Ethernet cable (straight through or cross-over) between the local PC and ProtoAir.
5.1.1 Enable Access Through the Local Browser
There are two methods to enable access to the ProtoAir in the local browser, either by changing the
subnet of the connected PC (Section 5.1.1.1) or using the FieldServer Toolbox to change the IP
Address of the ProtoAir (Section 5.1.1.2).
NOTE: Only perform one method or the other.
5.1.1.1 Changing the Subnet of the Connected PC
The default IP Address for the ProtoAir is 192.168.1.24, Subnet Mask is 255.255.255.0. If the PC and
ProtoAir are on different IP networks, assign a static IP Address to the PC on the 192.168.1.xxx network.
For Windows 10:
•Find the search field in the local computer’s taskbar (usually to the right of the windows icon )
and type in “Control Panel”.
•Click “Control Panel”, click “Network and Internet” and then click “Network and Sharing Center”.
•Click “Change adapter settings” on the left side of the window.
•Right-click on “Local Area Connection” and select “Properties” from the dropdown menu.
•Highlight and then click the Properties button.
•Select and enter a static IP Address on the same subnet. For example:
•Click the Okay button to close the Internet Protocol window and the Close button to close the
Ethernet Properties window.
Ethernet Port
Figure 7: Ethernet Port Location

SimplySNAP BMS Gateway/ProtoAir Start-up Guide
Page 15 of 52
5.1.1.2 Changing the IP Address of the ProtoAir with FieldServer Toolbox
•Ensure that FieldServer Toolbox is loaded onto the local PC. Otherwise, download the
FieldServer-Toolbox.zip via the Sierra Monitor website’s Software Downloads.
•Extract the executable file and complete the installation.
•Double click on the FS Toolbox Utility and click Discover Now on the splash page.
•Find the desired gateway and click the Configure Device button (gear icon) to the right of the
gateway information.
NOTE: If connectivity status is green, then the IP Address doesn’t need to be changed (the
ProtoAir is already on the same subnet). Skip to the next section.
•Select Network Settings in the Configure Device window.
•Modify the IP Address (N1 IP Address field) of the gateway Ethernet port.
oChange additional fields as needed
NOTE: If the gateway is connected to a router, the Default Gateway field of the gateway should be
set to the IP Address of the connected router.
NOTE: Do not change the DHCP Server State (N1 DHCP Server State field).
NOTE: If DNS settings are unknown, set DNS1 to “8.8.8.8” and DNS2 to “8.8.4.4”.
•Click Update IP Settings, then click the “Change and restart” button to reboot the Gateway and
activate the new IP Address. See the FieldServer Toolbox and GUI Manual for more information.

SimplySNAP BMS Gateway/ProtoAir Start-up Guide
Page 16 of 52
5.2 Connecting to the ProtoAir Over Wi-Fi Access Point
When the ProtoAir is first powered up, the Wi-Fi Access Point will be enabled allowing direct connection
to the ProtoAir with Wi-Fi.
To connect to the ProtoAir Wi-Fi Access Point:
•Click the icon (found in the bottom-right corner of the computer screen) to open the available
Wireless Network Connections.
•Select the desired ProtoAir and click Connect.
•Enter the Security key. The default is 12345678.
The available Wireless Network Connection menu should now show that the computer is connected to
the ProtoAir.

SimplySNAP BMS Gateway/ProtoAir Start-up Guide
Page 17 of 52
6 UPDATE NETWORK SETTINGS
After setting a local PC on the same subnet as the ProtoAir (Section 5.1 or Section 5.2), open a web
browser on the PC and enter the IP Address of the ProtoAir; the default Ethernet address is
192.168.1.24, the default Wi-Fi access point address is 192.168.50.1.
NOTE: If the IP Address of the ProtoAir has been changed by previous configuration, the
assigned IP Address can be discovered using the FS Toolbox utility. See Appendix A.1 for
instructions.
From the Web Configurator landing page, click the Network Settings tab to open the Network Settings page
for the ProtoAir.
Configure the network settings of the ProtoAir using the following methods:
•When using the Ethernet port to connect to the local network (Section 6.1.2).
•When connecting the ProtoAir to a local wireless access point, configure the Wi-Fi Client Settings
in the ProtoAir (Section 6.1.3).
NOTE: For Wi-Fi Access Point network information see Appendix B.5.
Figure 8: Web Configurator Landing Page –Showing Network Settings Tab

SimplySNAP BMS Gateway/ProtoAir Start-up Guide
Page 18 of 52
6.1.1 Common Settings
The Common Settings make it possible to choose the primary connection when both Ethernet and Wi-Fi
Client connections are available.
NOTE: The default Primary Connection is Ethernet.
To change the primary connection when both Ethernet and Wi-Fi Client connections are available:
•Select the desired option from the Primary Connection drop-down menu.
•Click Save, then click on Refresh to restart the ProtoAir and activate the new settings.
NOTE: If using Wi-Fi Client and not Ethernet, change Primary Connection to Wi-Fi.
Figure 9: Common Network Settings

SimplySNAP BMS Gateway/ProtoAir Start-up Guide
Page 19 of 52
6.1.2 Update Wired Network Settings
To change the IP settings, follow these instructions:
•Enable DHCP Client State to automatically assign IP Settings or modify the settings manually as
needed, via these fields: IP Address, Netmask, Default Gateway and Domain Name Server1/2.
NOTE: If connected to a router, set the Default Gateway to the same IP Address as the router.
•Click Save, then click on Refresh to restart the ProtoAir and activate the new IP Address.
NOTE: If the ProtoAir was open in a browser, the browser will need to be updated with the new
Wi-Fi details before the ProtoAir will be accessible again.
Figure 10: Ethernet Port Network Settings

SimplySNAP BMS Gateway/ProtoAir Start-up Guide
Page 20 of 52
6.1.3 Update Wi-Fi Client Settings
From the Network Settings page, scroll down to the Wi-Fi Client section. To change the Wi-Fi client settings,
follow these instructions:
•Set the Wi-Fi Status to ENABLED for the ProtoAir to communicate with other devices via Wi-Fi.
•Enter the Wi-Fi SSID and Wi-Fi Password for the local wireless access point.
•Enable DHCP to automatically assign all Wi-Fi Client network settings or manually modify the
setting using the fields immediately below (IP Address, Network, etc.).
NOTE: If connected to a router, set the IP gateway to the same IP Address as the router.
•Click Save, then click on Refresh to restart the gateway and activate the new Wi-Fi settings.
•Go to Common settings (Section 6.1.1) to set the Primary Connection to Wi-Fi Client.
Figure 11: Wi-Fi Client Network Settings
This manual suits for next models
1
Table of contents
Other Synapse Gateway manuals
Popular Gateway manuals by other brands

Cisco
Cisco Physical Access CIAC-GW-K9 Installing and configuring

SpeedStream
SpeedStream 6500 Series user guide

Balluff
Balluff Subnet16 BIS Z-GW-001-IND installation guide

Alcatel-Lucent
Alcatel-Lucent OmniAccess 8550 installation guide

ThingsMatrix
ThingsMatrix TMX03 user manual

IntesisBox
IntesisBox IBKNXMEB0100000 user manual

Dell
Dell Edge Gateway 3001 Getting started guide

Juniper
Juniper SRX-4600 Hardware guide

DEUTSCHMANN AUTOMATION
DEUTSCHMANN AUTOMATION UNIGATE MB EtherCAT instruction manual

Real Time Automation
Real Time Automation 460BMSAWS-NNA1 Product user guide

Robustel
Robustel M1000 Pro V2 user guide

ESD
ESD CAN-PN Hardware manual