Syris SY110SA User manual

SYRIS SY110SA
Operating Manual
Ver:1.60
Apr.15.2006

SY110SA SINGLE DOOR CONTROLLER
Table of content
TABLE OF CONTENT...............................................................................................................................2
INTRODUCTION ..................................................................................................................................- 1 -
Ⅰ. DO DEFAULT CONTRAST TABLE.............................................................................................. - 1 -
Ⅱ. DI DEFAULT CONTRAST TABLE ...............................................................................................- 1 -
Ⅲ. OPERATION ....................................................................................................................................- 1 -
0) LOGIN THE CONTROLLER.......................................................................................................... - 1-
1) ADD CARD (THIS FUNCTION REQUIRES TO LOGIN THE CONTROLLER FIRST) .................................... - 1-
2) DELETE CARD (THIS FUNCTION REQUIRES TO LOGIN THE CONTROLLER FIRST).............................. - 2-
3) CHANGE PASSWORD ................................................................................................................... - 2-
4) FUNCTION KEY BASIC PARAMETER SETTING ................................................................................ - 2-
Ⅳ. SIMPLE WIRING DIAGRAM .......................................................................................................- 3 -
ⅤADVANCED FUNCTION SETUP TABLE....................................................................................- 4 -
ⅥDO COMPLETE FUNCTION CONTRAST TABLE...................................................................- 5 -
ⅦDI COMPLETE FUNCTION CONTRAST TABLE ....................................................................- 5 -
ⅧREADER DISPLAY STATUS TABLE ...........................................................................................- 5 -
ⅨADVANCED FUNCTION................................................................................................................- 5 -
Ⅹ. ADVANCED WIRING DIAGRAM ................................................................................................ - 6 -

- 1 -
Introduction
This document including the sequence of setup SY110SA functions. The input sequence is from left to
right, please select the function and enter by the listed input order.
Ⅰ. DO Default Contrast Table
Ⅱ. DI Default Contrast Table
※All the DI function can not be change. Standard construction, no need
to setup any parameter.
Ⅲ. Operation
0) LOGIN THE CONTROLLER
Insert the “ ” + main password + “EN” (The lenght of the main password is 1~10 digits)
Please press “ ” and enter 1~10 digits main passwords then press “EN“ to login the system ( the
default main password “1234“)
1) ADD CARD (This function requires to login the controller first)
Choose add card function (four kinds of add card method)
1-1 Add one card: please enter the new user ID then present card
“ADD” + user ID1+ EN
1-2 Add one card: please enter new user ID and card ID, without swap the card
“ADD” + user ID + “ ” + card ID2+“EN”
1-3 Add multi-cards: please enter the first and last user ID then present cards
“ADD” + first user ID + “ADD” + last user ID + “EN”
1-4 Auto add card: the system will automatically search the available user ID to add card
“ADD” + “EN” + swap the card
1User ID available range: 1 to 2000
2Card ID maximum 10 digits
DO Notation
DO #1 Controller inner output point
DI Function Notation
DI #1 Open door button Controller inner
contact
DI #2 Door detect Controller inner
contact
DI #3 (Bell key)
or (Call Key)
Door bell input Controller inner
contact

SY110SA SINGLE DOOR CONTROLLER
- 2 -
2) DELETE CARD (This function requires to login the controller first)
2-1 Delete one card: please enter the new user ID (no need to present card)
“DEL” + user ID3+ “EN”
2-2 Delete one card: enter the card serial number which wants to delete and no need to present card
“DEL” + “ ” + Card ID4+ “EN” (the card ID is decimal)
2-3 Delete multi-cards: delete multi-cards needs to enter the first and last user ID then present cards
“DEL” + the first user ID + “DEL” + the last user ID + “EN”
2-4 Delete one card: enter the delete card order then present card.
“DEL” + “EN” + swap the card
2-5 Delete all cards, no need to present cards
“DEL” + “ ” + “DEL” + “ ” + “DEL” + “ ” + “DEL” + “ ” + “EN”
3) CHANGE PASSWORD
To change user password, you will need to enter the old password then press “ ” key and enter the
new password, click “ ” again then enter the new password and press “EN” to complete the process.
To change main password: (the main password which you use to login)
Please press “ ” key then enter main password after login and repeat the action again.
“ ” + old main password + “ ” + new main password + “ ” + again new main password +
“EN”
Apply the master card to main password: (the main password which you use to login)
“ ” + main password + “ ” + N + “EN”
When N = 0 or 1, N = 0 means disable the use of master card, N = 1 means enable the use of master card.
If you enable the use of master card, the user needs to present the master card within 10 sec. after insert
the main password.
Notice: The main password only can be changed when the original password5(Initial Password) is equal
to “000000000”.
4) FUNCTION KEY Basic Parameter Setting
Function name Enter steps Remarks
Logout “FUN” + 0 + “EN” Logout controller
Access Mode “FUN” + 1 + “ ” + N+ “EN” N=1~4, when N=1 means card only access mode
N=2 means card or password only access mode
N=3 means card plus card access mode
N=4 means password only access mode
Setup Persomal PIN “FUN” + 2 + “ ” + User ID +
“ ” +PIN + “EN”
Setup personal PIN
Cover the old PIN when user ID repeat
*PIN range: 1~10 digits. Ex: 1234 or 335566 or 1234567890
*This mark means the setting is the factory defualt.
3User ID available range: 1~2000
4Card ID maximum 10 digits
5The system original PIN default =“0000000000”. The user cannot change other main password once the main password set
has been changed. To change the main password, please refer section IX

SY110SA SINGLE DOOR CONTROLLER
- 3 -
Ⅳ. Simple Wiring Diagram
Relay
CPU
Beeper
Common ( COM )
Normal Close ( NC )
Normal Open ( NO )
DO FeatureRelay
Green NC
Blue COM
Violet NO
Open Door
Push Button
Door Sensor
Force Alarm
Brown D1
Black GND
Green SI
Orange SO
Blue DI1
Violet DI2
Red V+
White D0 GND
Black GND
Red V+ Power supply
Connet to
8V~15VDC
E.M.
Lock
Digital Input point 1 & 2
Signal Output point (External module)
Connect External Reader
Violet
Blue
Orange
Green
Brown
White
Black
Red Power Output to External (Reader / Module)

SY110SA SINGLE DOOR CONTROLLER
- 4 -
ⅤAdvanced Function Setup Table
Function Name Enter Steps Remark:
The use of Door Output “FUN” + 3 + “ ” + N + “ ” +
TTT + “EN”
TTT is the setup time, range: 06~255 (5*) sec.
N= 0~2, N = 0 means disable relay action
N = 1 means action by controller inner relay*
N = 2 means action by external module relay
Door Bell “FUN” + 4 + “ ” + N + “ ” +
TTT + “EN”
TTT is the setup time, range: 0~255 (3*) sec.
N= 0~2, N = 0 means disable door bell function
N = 1 means enable the inner relay as door bell function
N = 2 means enable external relay as door bell function*
Alarm Output Point Setup “FUN” + 5 + “ ” + N + “ ” +
TTT + “EN”
TTT is the setup time, range: 0~255 (30*) sec.
N= 0~2, N = 0 means stop the alarm signal output*
N = 1 means take inner relay for alarm function
N = 2 means take external relay for alarm function
Push Button Input Point
Setup
“FUN” + 6 + “ ” + N + “EN” N7is the DI ID, N= 0~6 (1*)
N = 0 means the use of open door push button
N = 1~6 means enable the DI as door open push button function
Door Sensor Input Point
Setup
“FUN” + 7 + “ ” + N + “EN” N is the DI ID, N= 0~6 (2*)
N = 0 means to stop the use of door sensor*
N = 1~6 means enable the DI as door sensor function
Door Bell Input Point Setup “FUN” + 8 + “ ” + N + “EN” N us the DI ID, N= 0~6 (3*)
N = 0 means to stop the use of door sensor
N = 1~6 means enable the DI as open door push button function
Push Button #2 Input Point
Setup
“FUN” + 9 + “ ” + N + “EN” N is the DI ID, N= 0~6 (4*)
N = 0 means the use of open door push button
N = 1~6 means enable the DI as door open push button function
Door Bell #2 Input Point
Setup
“FUN” + 10 + “ ” + N + “EN” N us the DI ID, N= 0~6 (6*)
N = 0 means to stop the use of door sensor
N = 1~6 means enable the DI as open door push button function
Setup Date “FUN” + 20 + “ ” +yy +mm+dd +
hh+mm+ss+ “EN”
Setup Time/Date
yy=year, mn = month, dd=day, ; hh =hour, mm=minute, ss=
second,
Door alway open “FUN” + 21 + “ ” + N + “EN” N=1or 0, N = 0 means disable door always open function*
N = 1 means enable door always open function
Door forced open “FUN” + 30 + “ ” + N + “EN” N= 1or 0, N = 0 means disable door forced open function*
N = 1 means enable door forced open, alarm output function
Door Open Timeout “FUN” + 31 + “ ” + N + “ ” +
TTT + “EN”
N= 1or 0, N = 1means enable door open timeout function
N = 0 means disable door open timeout function*
(Door open time + TTT = timeout time)
TTT is the time allow you to close the door, range: 0~ 255 sec. (10
*)
Tamper Switch “FUN” + 32 + “ ” + N + “EN”
*Controller inner contact point
N= 1or 0, N = 0 means disable tamper switch function*
N = 1 means disable tamper switch function
Card Type “FUN” + 40 + “ ” + N +“EN” N = 1~3, N = 1 means regular EM Card*, when N = 2 means
using SYRIS card, N = 3 means using Two Page Card.
Card Data Bytes format “FUN” + 41 + “ ” + N +“EN” N = 1~3, N = 1 means using 2 Bytes, when N = 2 means using 3
Bytes*, when N = 3 means using 4 Bytes format.
Setup Main Password “FUN” + 50 + “ ” + N + “ ”+
main password + “EN”
Only if the initial password havn’t been changed, you can modify
the main password. There are three sets of the main password you
can use. Use N to select which main password you want to use
(N=1~3). The default main password is “1234“*. Also, if other
set of the main password had been changed before, this function
will be disabled.
Restore Factory Default “FUN” + 86 + “ ” + 87 + “EN” All the setup data including card data and master card data will be
clean by executing this step, the controller will restore to factory
default.
Restore Main Password “FUN” + 98 + “ ” + 99 + “EN” Restore three set of the main password back to factory default, and
disable the use of the Master card. If the Initial password is not
equal to “0000000000“ This function will be disabled.
*This marks means the setting is factory defualt.
6IF you set the “TTT” to “0”, then it means that the door will be opened / closed when you swap the card. (Swap to change the status).
7The Input point you can use is from DI1~DI6, for detail information, please refer to the next page of the contrast table.

SY110SA SINGLE DOOR CONTROLLER
- 5 -
ⅥDO Complete Function Contrast Table
ⅦDI Complete Function Contrast Table
※The entire DI is free to use, change parameter and setup way, please refer the advanced function setup table last page.
ⅧReader Display Status Table
Lights and sounds
No. Description OK LED BELL LED ERROR LED Sound Notation
0 Normal status Off On Off No action
1 Correct status On On Off Short beep(0.5 sec)Return to original status
2 Error status Off On On Two short beep Return to original status
3 Login Off Flashes Off No action Continued until logout
4 Setup complete status On On Off Long beep(1 sec)Return to original status
5 Await password
enter/Card sense status Flashes On Off Long beep(0.5 sec)Continued until enter
complete or timeout
6 Alarm status Off On Flashes Short beep
Continued until
disarmed or restore
7 Lock status Flashes On Flashes No action Continued until local
control
8 Initializing On On On
Long beep(1 sec)Return to original status
※The timeout limit of card sense and password enter is 20 sec., the system will logout when timeout or press【EN】.
※The system will automatically logout if there does not has any event happen within 60 sec.
※Enter password incorrect over three times will lock the controller and can not login for 60 sec.
ⅨAdvanced Function
1. The “Initail Password” by default it is “0000000000” 10 zero. If this password never had been
changed, then you will be able to modify it while power up the controller and within 60 seconds, key in
the command below to change: “ ” + “ADD” + “ ” + new initial password + “ ” + new
initial password + “EN”
2. Restore the main password (This function can only be proceeding while power up the controller
within 60 sec; the default main password is “1234”): Press “ ” + “DEL” + Initail password + “EN”.
3. There are some other extra functions which require the MDUSB-S-1 and utility tool. With proper
tools, you will be able to (upload/download) the setting (from/to) controller. You can also back up the
holder data, I/O data, Card number, personal password, controller parameter, master password, master
card’s card number.
DO Notation
DO #1 Controller inner contract
DO# 2 External module DO contact
DI Notation
DI #1 Controller inner contact
DI #2 Controller inner contact
DI #3 (Bell key) or (Call Key) Controller inner contact
DI #4 The first DI of external module
DI #5 The second DI of external module
DI #6 (Bell key) or (Call Key) External keypad reader

SY110SA SINGLE DOOR CONTROLLER
- 6 -
Ⅹ. Advanced Wiring Diagram
SY110 Wiring Diagram
SYRIS New Version
SYRDS1 , SYRDS5
SYRDK5 , SYRDL5
Relay
Open Door
Push Button
Door Sensor
Force Alarm
Brown D1
Black GND
Green SI
Orange SO
Blue DI1
Violet DI2
Red V+
White D0
DI4 Blue
DI5 Brown
RELAY(繼電器)
DO3
Reader Power
and
Reader Network
+8 ~ 15V Red
GND Black
D0 White
D1 Brown
BEEPER Violet
LED Green
+8 ~ 15V Red
GND Black
DI Green
DO Orange
NC Green
COM Blue
NO
Violet
MD120EXT-1S
CPU
GND
Common ( COM )
Normal Close ( NC )
Normal Open ( NO )
DO FeatureRelay
Connet to
8V~15VDC
Beeper
Green NC
Blue COM
Violet NO
M2
Brown COM
Orange NO
TAMPER SW
M4
Black GND
Red V+
M1
Table of contents
Other Syris Intercom System manuals