Tab R2428 User manual

www.tab.si
Lithium-Ion Phosphate Energy Storage System
R2428 Operation Manual
R2428_Operating_Manual_13.05.2021.indd 1R2428_Operating_Manual_13.05.2021.indd 1 17.5.2021 11:35:4217.5.2021 11:35:42

R2428_Operating_Manual_13.05.2021.indd 2R2428_Operating_Manual_13.05.2021.indd 2 17.5.2021 11:35:4217.5.2021 11:35:42

Contents
1. Safety Precautions 5
1.1 Before Connecting 5
1.2 In Using 6
2. Introduction 7
2.1 Features 7
2.2 Specications 8
2.3 Equipment Interface Instruction 9
3. Safe handling of lithium batteries Guide 12
3.1 Schematic Diagram of Solution 12
3.2 Explanation of Symbol 13
3.3 Tools 13
3.4 Safety Gear 14
4. Installation 14
4.1 Package Items 14
4.2 Installation Location 16
5. Trouble Shooting Steps 20
5.1 Problem determination 20
5.2 Preliminary determination steps 20
6. Emergency Situations 21
R2428_Operating_Manual_13.05.2021.indd 3R2428_Operating_Manual_13.05.2021.indd 3 17.5.2021 11:35:4217.5.2021 11:35:42

Symbol in label, manual and product
Caution! Warning! Reminding.
Safety related information.
Risk of battery system failure or life cycle reduces.
Do not reverse connection the positive and negative.
Do not place at the children and pet touchable area.
Warning electric shock.
Warning Fire.
Read the product and operation manual before operating the
battery system!
Grounding.
Recycle label.
R2428_Operating_Manual_13.05.2021.indd 4R2428_Operating_Manual_13.05.2021.indd 4 17.5.2021 11:35:4317.5.2021 11:35:43

1. Safety Precautions
Reminding
1. It is very important and necessary to read the user manual carefully (in the acces-
sories) before installing or using battery. Failure to do so or to follow any of the in-
structions or warnings in this document may result in electrical shock, serious injury,
or death, or can damage battery, potentially rendering it inoperable.
2. If the battery is stored for long time, it is required to charge it every six months, and
the SOC should be no less than 90%;
3. Battery needs to be recharged within 12 hours, after fully discharged;
4. Do not expose the battery module and cables in an outdoor environment;
5. All the battery terminals must be disconnected for maintenance;
6. Please contact the supplier within 24 hours if there is something abnormal.
7. Do not use cleaning solvents to clean battery;
8. Do not expose battery to ammable or harsh chemicals or vapors;
9. Do not paint any part of battery, include any internal or external components;
10. Do not connect battery with PV solar wiring directly;
11. Any foreign object is prohibited to insert into any part of battery.
12. The warranty claims are excluded for direct or indirect damage due to items above.
Warning
1.1 Before Connecting
1. After unpacking, please check product and packing list rst, if product is damaged
or lack of parts, please contact with the local retailer;
2. Before installation, be sure to cut off the grid power and make sure the battery is in
the switch-off mode;
3. Wiring must be correct, do not mistake the positive and negative cables, and en-
sure no short circuit with the external device;
5
R2428_Operating_Manual_13.05.2021.indd 5R2428_Operating_Manual_13.05.2021.indd 5 17.5.2021 11:35:4317.5.2021 11:35:43

4. It is prohibited to connect the battery and AC power directly;
5. The embedded BMS in the battery is designed for 24VDC system, please DO NOT
connect battery in series;
6. Battery system must be well grounding and the resistance must be less than
100mΩ;
7. Please ensured the electrical parameters of battery system are compatible to relat-
ed equipment;
8. Keep the battery away from water and re.
1.2 In Using
1. If the battery system needs to be moved or repaired, the power must be cut off and
the battery is completely shut down;
2. It is prohibited to connect the battery with different type of battery.
3. It is prohibited to put the batteries working with faulty or incompatible inverter;
4. It is prohibited to disassemble the battery (QC tab removed or damaged);
5. In case of re, only dry powder re extinguisher can be used, liquid re extinguishers
are prohibited;
6. Please do not open, repair or disassemble the battery except staffs from TAB or
authorized by TAB. We do not undertake any consequences or related responsibility
which because of violation of safety operation or violating of design, production and
equipment safety standards.
6
R2428_Operating_Manual_13.05.2021.indd 6R2428_Operating_Manual_13.05.2021.indd 6 17.5.2021 11:35:4317.5.2021 11:35:43

2. Introduction
R2428 lithium iron phosphate battery is one of new energy storage products developed and
produced under TAB’s quality requirements, it can be used to support reliable power for var-
ious types of equipment and systems. R2428 is especially suitable for application scene of
high power, limited installation space, restricted load-bearing and long cycle life.
R2428 has built-in BMS battery management system, which can manage and monitor cells
information including voltage, current and temperature, further provide protection base on
above information. The BMS can also balance cells during charging to extend cycle life.
Multiple batteries can connect in parallel to expand capacity and power in parallel for larger
capacity and longer power supporting duration requirements.
2.1 Features
◊The whole module is non-toxic, non-polluting and environmentally friendly;
◊Cathode material is made from LiFePO4 with safety performance and long cycle life;
◊Battery management system BMS)has protection functions including over-dis-
charge, over-charge, over-current and high/low temperature;
◊The system can automatically manage charge and discharge state and balance cur-
rent and voltage of each cell;
◊Flexible conguration, multiple battery modules can be in parallel for expanding ca-
pacity and power
◊Adopted self-cooling mode rapidly reduced system entire noise;
◊The module has less self-discharge, up to 6 months without charging it on shelf, no
memory effect, excellent performance of shallow charge and discharge;
◊Working temperature range is from -10°C to 55°C, (Charging 0~55°C; discharging
-10~55°C) with excellent discharge performance and cycle life;
◊Small size and light weight, standard of 19-inch embedded designed module is com-
fortable for installation and maintenance.
7
R2428_Operating_Manual_13.05.2021.indd 7R2428_Operating_Manual_13.05.2021.indd 7 17.5.2021 11:35:4417.5.2021 11:35:44

2.2 Specications
55
Communication
Working Temperature °C°C Charge
°C°C Discharge
Shelf Temperature °C°C
Ingress Protection
Humidity
Design life °C°F
R2428_Operating_Manual_13.05.2021.indd 8R2428_Operating_Manual_13.05.2021.indd 8 17.5.2021 11:35:4417.5.2021 11:35:44

2.3 Equipment Interface Instruction
R2428 Product Front Interface
Power / SW Switch
Power Switch: ON: the battery standby, no output. OFF: turn off the battery completely.
SW Switch: Press 2s to turn on or turn off battery
SOC
SOC light: 4 green LED to show the battery’s current capacity.
Alarm
Alarm light: YELLOW LED to show the battery has alarm, Combine with SOC LEDs to show
which kind of alarm in detail. Please check below table ‘LED Indicators Instructions’ for the
detailed denition.
Protection
Protection light: RED LED to show the battery is under BMS protection. Combine with SOC
LEDs to show which kind of protection in detail. Please check below table ‘LED Indicators
Instructions’ for the detailed denition.
LED Indicators Instructions
It`s important to check the detailed alarm/protection denition follow the below table for
trouble-shooting and maintenance service.
R2428_Operating_Manual_13.05.2021.indd 9R2428_Operating_Manual_13.05.2021.indd 9 17.5.2021 11:35:4517.5.2021 11:35:45

Pro-
tect
76%
75
Description
Turn off
Power off - - - -- -
Turn on Flash once.
Idle
Charge
Float charge
per sec.
Discharge
→
→ →
Soft start - -
working.
-
-
-
Protection
ADD Switch
ADD Switch: 4 ADD switches, Dip1 to denite different baud rate. ”0”and”1”,
refer to picture right. “0XXX” setup the baud rate 115200, and “1XXX” setup
the baud rate 9600.
The settings will be active only after restart the battery.
Using RS485: all batteries need to set the ADD switch. And should be the same.
Using CAN: the ADD switch has no inuence on CAN baud rate.
R2428_Operating_Manual_13.05.2021.indd 10R2428_Operating_Manual_13.05.2021.indd 10 17.5.2021 11:35:4517.5.2021 11:35:45

Console
Console Terminal: (RJ11 port) for professional engineer to debug or service.
L 0/1 / RS485
Link Port0/1 or RS485 Communication Terminal: (RJ45 port) follow TAB Low voltage
RS485 protocol for R2428, for communication between multiple parallel batteries and be-
tween master battery to host equipment.
CAN
CAN Communication Terminal: (RJ45 port) follow TAB Low voltage CANBUS protocol, for
communication between master battery and host equipment.
Denition of RJ45 Port Pin
No.
--
-- GND
--
--
5 --
6 --
7
When using RS485, it is required to keep undened PIN empty. If not may cause battery
communication function error.
Denition of RJ11 Port Pin
No.
GND
RXD
TXD
GND
R2428_Operating_Manual_13.05.2021.indd 11R2428_Operating_Manual_13.05.2021.indd 11 17.5.2021 11:35:4517.5.2021 11:35:45

Power Terminals +/-
Power cable terminals: there are two pair of terminals with same function,
one connects to equipment, the other one paralleling to other battery module
for capacity expanding. For each single module, each terminal can achieve
charging and discharging function.
It must keep pressing this Lock Button during pulling out the power plug.
BMS function:
Cells Balance
Capacity Retention Calculate
Short Circuit Soft Start
Hot Swap
3. Safe handling of lithium batteries Guide
3.1 Schematic Diagram of Solution
R2428_Operating_Manual_13.05.2021.indd 12R2428_Operating_Manual_13.05.2021.indd 12 17.5.2021 11:35:4617.5.2021 11:35:46

3.2 Explanation of Symbol
3.3 Tools
The following tools are required to install the battery pack
Wire cutter Crimping Modular Plier Screw Driver
NOTE
Use properly insulated tools to prevent accidental electric shock or short circuits.
If insulated tools are not available, cover the entire exposed metal surfaces of the available
tools, except their tips, with electrical tape.
R2428_Operating_Manual_13.05.2021.indd 13R2428_Operating_Manual_13.05.2021.indd 13 17.5.2021 11:35:4617.5.2021 11:35:46

3.4 Safety Gear
It is recommended to wear the following safety gear when dealing with the battery pack
Insulated gloves Safety goggles Safety shoes
4. Installation
4.1 Package Items
Unpacking and check the Packing List
1) For battery module package:
Two power cables and one communication cable for each battery package:
Grounding cable:
Grounding cables use 10AWG yellow-green cables.
R2428_Operating_Manual_13.05.2021.indd 14R2428_Operating_Manual_13.05.2021.indd 14 17.5.2021 11:35:4717.5.2021 11:35:47

R2428 modules’ grounding is based on metal directly touch
between the module’s surface (SGCC) and rack’s surface.
If uses normal rack, may need to remove the paint at the
corresponding place.
Or install a grounding cable to the grounding point
of the modules.
2) For battery system connects to inverter:
Two long power cables (max. current capacity 120A) and one communication cable for
each energy storage system:
NOTE
These three long cables are NOT in battery package, they are in another extra small cable
box.
If there is anything missed, please contact dealer.
R2428_Operating_Manual_13.05.2021.indd 15R2428_Operating_Manual_13.05.2021.indd 15 17.5.2021 11:35:4717.5.2021 11:35:47

4.2 Installation Location
Make sure that the installation location meets the following conditions:
• An indoor environment
• The area is completely waterproof.
• The oor is at and level.
• There are no ammable or explosive materials.
• The ambient temperature is within the range from 0°C to 50°C.
• he temperature and humidity are maintained at a constant level.
• There is minimal dust and dirt in the area.
CAUTION
If the ambient temperature is out of the operating range, the battery pack stops operating
to protect itself. The optimal temperature range for the battery pack to operate is 0°C to
50°C. Frequent exposure to harsh temperature may deteriorate the performance and life of
the battery pack.
R2428_Operating_Manual_13.05.2021.indd 16R2428_Operating_Manual_13.05.2021.indd 16 17.5.2021 11:35:4817.5.2021 11:35:48

Installation
A. Put battery modules into the cabinet and connect the cables:
(1) Put the battery into the cabinet, follow below picture;
(2) Fix each module with the cabinet with 4 screws;
(3) Connect the cables between battery modules, including grounding cables, follow
below picture.
R2428_Operating_Manual_13.05.2021.indd 17R2428_Operating_Manual_13.05.2021.indd 17 17.5.2021 11:35:4817.5.2021 11:35:48

(4) Connect the cables to inverter.
The power cables’ current capacity is 120Amps(peak).
If the battery system is supposed to congure with an inverter/charger
≥100Amps/2.5kW, must congure multiple pairs of external power cables following the
inverter/charger size.
Power Cable connection:
• For 1 pair of external power cable, connect as A + D or B + C, donot connect as A+B or
C+D to avoid unbalancing current transmitted.
• For 2 pairs of external power cable, connect as A + D and B + C.
• For more than 2 pairs of external cable, need split the battery module into another string
to further handle the connection.
(5) There shall be a manual disconnecting device (breaker, etc.) between battery system
and inverter.
R2428_Operating_Manual_13.05.2021.indd 18R2428_Operating_Manual_13.05.2021.indd 18 17.5.2021 11:35:4917.5.2021 11:35:49

B. Power On
Double check all the power cable and communication cable, check the
ADD switch.
(1) Switch the breaker between battery system and inverter.
(2) turn all the power switch ON.
(3) The one connects communication cable to inverter is the Master Battery Module,
others are slaves (1 master battery congure with maximum 19 slave batteries).
(4) Press the Start Button (SW) of master battery to power on, all the battery LED light
will be on after master battery starts.
If all the battery LED lights on, and then off, which means the battery system is good and
working.
R2428_Operating_Manual_13.05.2021.indd 19R2428_Operating_Manual_13.05.2021.indd 19 17.5.2021 11:35:4917.5.2021 11:35:49

5. Trouble Shooting Steps
Please check the ‘LED Indicators Instructions’ table for the detailed faulty denition be-
fore any trouble-shooting steps.
5.1 Problem determination
1. Whether the battery can be turned on or not;
2. If battery is turned on, check the red and yellow light is off, ashing or lighting, follow
the ‘LED Indicators Instructions’;
3. If the red and yellow light is off, further check whether the battery can be charged/dis-
charged.
5.2 Preliminary determination steps.
1. Battery cannot turn on, switch on the lights are all no lighting or ashing.
Solution: Turn power switch ON, and then charge the battery with external power supply
voltage 26V or more, if the battery still unable to turn on, turn the power switch off and
contact the installer.
2. The battery can be turned on but cannot charge or discharge. If the red/yellow light is
lighting, that means system is abnormal, please follow the ‘LED Indicators Instructions’
to check:
a. Over/Low temperature: Above 55°°C or under -10°C, the battery could not work.
Solution: turn off the battery module, move battery to the normal operating tem-
perature range between -10°C and 55°C.
b. Over Current: If current is > 100A, battery protection will turn on.
Solution: Check and change the settings on power supply or load side. And wait
until battery release the protection.
c. Short circuit/Reverse polarity:
Check power cable and grounding cable connection whether is wrong or missing.
Check inverter/charger connected of a potential short circuit source.
d. High Voltage: If charging voltage above 28.5V, battery protection will turn on.
Solution: Check and change the settings on power supply side. And wait until bat-
tery release protection or discharge the battery.
e. Low Voltage: When the battery discharges to 23.2V or less, battery protection will
turn on.
Solution: Charge the battery by external charger, with voltage ≤28.5Vdc, current
≤55Amps.
R2428_Operating_Manual_13.05.2021.indd 20R2428_Operating_Manual_13.05.2021.indd 20 17.5.2021 11:35:4917.5.2021 11:35:49