Talis ERHARD HALIOSTM User manual

P1/19
IOM_FIH210201_HALIOS STD-PREM_EN
The technical data and performance may be modified
without prior notice depending on the technical advances.
Table of contents
1 Safety and general aspects
2 Product and functional
description
3 Transport, handling and lifting
4 Storage
5 Installation into the pipeline
6 Commissioning and Operation
7 Maintenance
8 Hydraulic characteristics
9 CE marking
10 After sales service contact
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
HALIOSTM & HALIOSTM PREMIUM
DIN UNDERGROUND FIRE HYDRANT
DN80, PN16, Single shut-off (UHA) or Double shut-off (UHAD)
SERIES 0410250 / 0410270
IOM_FIH210201_HALIOS STD-PREM_EN

P2/19
IOM_FIH210201_HALIOS STD-PREM_EN
The technical data and performance may be modified
without prior notice depending on the technical advances.
1- SAFETY AND
GENERAL ASPECTS
1.1 Preface
Dear user, prior to initial operation, read these operating
and maintenance instructions thoroughly to ensure safe and
economical operation.
The operating and maintenance instructions contain all
information required for operation and maintenance of the
hydrant.
These operating and maintenance instructions are part of the
complete documentation.
Prior to commissioning the hydrant, all safety requirements
must be complied with.
The hydrant, shall only be operated by qualified and trained staff.
If maintenance work is neglected or
carried out by untrained persons,
our warranty obligation, according
to our terms and conditions of
delivery, will not apply.
Please use only original spare parts
supplied by our company to ensure
best quality and exchangeability.
The manufacturer prohibits the
making of any modifications to the hydrant. If the user modifies
the hydrant, this may void the manufacturer’s warranty.
We reserve the right to make technical modifications to the
data and representations contained in these Operating and
Maintenance Instructions for the purpose of improving the
hydrant.
1.2 Basic safety instructions
1.2.1 Adherence to operating instructions
Prior to unloading, transport, commissioning and maintenance
of the hydrant, the operating and maintenance instructions must
be thoroughly read and strictly observed.
In the case of non-compliance with these Operating Instructions,
we will not be liable for any damage or consequences resulting
therefrom.
In addition to the operating and maintenance instructions and the
regulations concerning prevention of accidents applicable in the
user’s country and place of installation, the approved technical
rules for relevant worker qualifications and safety standards
must also be adhered to.
The user's staff are responsible for ensuring that they are
familiar with the local rules concerning safety and prevention of
accidents.
The technical data pertaining to the ordered product(s) are binding
for the type of design. Modifications can only be considered
if they are specified to us in time before starting production.
Every product is checked for completeness, performance, and
tightness before leaving the factory.
1.2.2 Intended use
Due to their design and the materials used, our hydrant of
standard design are approved for those media (concentration,
pressure, temperature) which are indicated in the technical
brochure and operating instructions specific to the product.
Deviating operating instructions and fields of application are
subject to the manufacturer’s approval.
1.2.3 Duties of the user
Whoever, on the user's premises is engaged in mounting,
commissioning, operation and maintenance of this hydrant,
should read the complete Operating Instructions (especially any
referenced basic safety instructions) and understand them. This
particularly applies to staff who work only occasionally.
This hydrant
shall only be operated
by qualified and
trained staff.
WARNING
In the event of non-compliance with
these Installation, Operation and
Maintenance manual, we shall not be
liable for any damages or operating
problems resulting therefrom.
Misuse, particularly on hydrant
pressured by liquids, can result
in personal injury and damage to
property.
WARNING
The following chapter “Basic safety
instructions“ has to be strictly observed
in order to maintain health and safety of
the operating and maintenance staff and
to ensure operativeness of the hydrant.
Non-compliance with these instructions
may jeopardise the manufacturer’s duty
of guarantee and warranty.
FOLLOW OPERATING INSTRUCTIONS!

P3/19
IOM_FIH210201_HALIOS STD-PREM_EN
The technical data and performance may be modified
without prior notice depending on the technical advances.
FOLLOW OPERATING INSTRUCTIONS!
WARNING
It is strictly forbidden to modify,
remove, by-pass or override the safety
installations.
In the absence of prior written approval by the manufacturer, do
not carry out any modifications to the accessories and equipment
surrounding the hydrant which may jeopardise safety! Changes
at the hydrant carried out on one’s own authority void the
manufacturer’s liability for any damage resulting therefrom.
This applies also to installation and setting of safety devices and
hydrant, as well as welding at supporting parts.
1.2.4 Dangers when handling the hydrant
Our hydrants are designed to the state of the art and according
to the approved safety rules. However, these hydrants can
constitute a danger for persons and property especially when
handled by untrained staff in an unskilled manner or when
they are not used in accordance with their proper purpose. This
may cause danger to life and limb of the user or third parties or
damage to the hydrants and other property.
Access to the danger zone shall only be possible when the hydrant
is out of operation and when it is ensured that the conveying units
and the following units are shut down, in order to avoid danger to
the operating and maintenance staff.
Whoever, in the user’s facilities, is engaged in mounting,
dismantling or remounting, operation and service (inspection,
maintenance, repair) of the hydrants, must familiarise
themselves with the applicable regulations in force locally.
Work at the hydrant site (as e.g. control, maintenance and repair
work) shall only be carried out when the area has been secured
and shut down and when power at the area has been switched
off.
Before removing safety devices and/or carrying out work on the
hydrants, the pipe section must be made pressureless to avoid
risk. Unauthorized, erroneous or unexpected operation, as well
as dangerous movements caused by stored energy (compressed
air, pressurized water, hydraulic system), must be avoided.
A copy of the operating and maintenance instructions must
always be available on site and must be protected against oil and
grease.
If necessary, or as specified by the rules, use suitable personal
protective equipment!
Any instructions concerning safety and dangers at the working
area must be observed and a written copy must be maintained
in legible condition and periodically renewed or replaced, if
necessary.
During operation, protective gloves must be worn.
In the event of changes to the hydrant or its operating
performance which might affect safety aspects, operation must
be stopped immediately and the problem reported to the relevant
department/person!
Before any maintenance operation on the hydrant, the network
section where the hydrant is installed must be isolated upstream,
and depressurized in order to relieve the hydrant free from
pressure. Failure to comply with this recommendation will lead
to a situation of danger to persons and property.
When maintenance and repair work at the hydrant has been
finished prior to commissioning of the hydrant, check whether all
safety devices and equipment have been remounted and make
sure that they are operative.
If work is carried out in the vicinity of the hydrant that may lead to
soiling (e.g. concrete work, masonry, painting, sandblasting) the
hydrant must be covered effectively.
1.2.5 Working conditions for operators
Take care that there is sufficient space available for operation,
mounting and maintenance work. Access to the hydrant must be
provided in such a way that this work can be carried out by using the
appropriate technical means (tools, measuring instruments, etc.)
The operator should not work directly above the hydrant to
prevent personal injury.
The operator should not work directly above the hydrant to
prevent personal injury.
The user must provide adequate instructions in order to ensure
that the working area is clean and suitably arranged.
WARNING
Observe the applicable rules concerning
safety, and wear the necessary personal
protective equipment. Risk of injury!
1.2.6 Safety and protective equipment (graphics)
Use ear muffs and helmet
Use eye protection Use protective gloves
Wear safety boots

P4/19
IOM_FIH210201_HALIOS STD-PREM_EN
The technical data and performance may be modified
without prior notice depending on the technical advances.
1.2.7 Personal protective equipment
If operating problems or malfunctions can occur at the hydrant
(e.g. risk caused by substances acting on the hydrant), the person
at risk – if necessary or specified by rules – must use suitable
personal protective equipment to avert hazards which may arise
due to the valve being pressured with up to 16 bar.
1.2.8 Presentation and explanation of the
danger symbols on the hydrant
The corresponding pictograms and explanations are included in
the relevant operating instructions specific to the product and/or
in the corresponding danger analysis.
1.2.9 Safety measures during normal
operation
When using the hydrant, observe the approved technical rules:
- European standards, and regulation in force. For areas which
must be supervised, observe the relevant laws and regulations,
e.g. trading regulations, regulations for prevention of accidents,
steam boiler regulations, regulations for gas mains under
high pressure, regulations for combustible liquids as well as
technical regulation works instructions, etc,
- Law on emissions, technical instructions for protection against
noise, disposal of working media according to Directive of the
Council 75/439/EEC,
- Regulations specific to the country concerning approval for
discharging substances hazardous to water into the collective
sewage water system,
- Water resources laws that are specific to the country,
- Rules for accident prevention that are specific to the country,
- Safety regulations for hydraulic hose pipes.
- European Construction Products Directive 89/106/CEE.
- DVGW worksheet W331
1.2.10 Dangers caused by electric energy
A potential danger may arise when the hydrant is installed close
to the electricity supply.
DANGER
Work at electric installations should
only be carried out by trained
electricians and only when the
current is switched off.
Danger from high electric voltage!
1.2.11 Particularly dangerous places
If the hydrant has been installed according to the instructions,
there will be no immediate danger.
However, vibration may cause damage to seals and screwed
connections. As a result, the flow medium may escape!
Depending where the hydrant has been installed, there may be a
risk of explosion caused by electric contact.
1.2.12 Safety instructions concerning
maintenance, repair, trouble shooting
WARNING
Before carrying out work on the
hydrant, the inspection valve must
be closed and the pipe section must
be depressurised.
1.2.13 Modification of hydrant design
Prior to any change to the design by the user, the manufacturer's
approval must be obtained. Otherwise, the warranty becomes
void.
1.2.14 Hydrant cleaning and waste disposal
for environmental protection (flow media and
lubricating agents)
The hydrant can be cleaned with water and soap at a max.
temperature of 40°C.
When using high-pressure cleaning devices, maintain a
minimum distance of 30 cm between the nozzle and the surface
to be cleaned at 100 bars.
For disposal of flow media and lubricating agents, see operating
instructions specific to the product.
1.2.15 Noise level at the hydrant
Unacceptable noise at the hydrant only occurs if the given
operating conditions are out of control (cavitation or water
hammer)

P5/19
IOM_FIH210201_HALIOS STD-PREM_EN
The technical data and performance may be modified
without prior notice depending on the technical advances.
HALIOSTM and HALIOSTM Premium
DIN Underground Fire Hydrant with Single Shut Off - Type UHA
Series 0410250
Area of application according to EN14339
Flange DN80 according to EN1092-2 PN10/16, ISO 2531 PN10/16.
HALIOSTM and HALIOSTM Premium
DIN Underground Fire Hydrant with Double Shut Off - Type UHAD
Series 0410270
Area of application according to EN14339
Flange DN80 according to EN1092-2 PN10/16, ISO 2531 PN10/PN16.
2 - PRODUCT AND FUNCTIONAL
DESCRIPTION
2.1 Product description and area of application
Series Size
Installation
Depth
RD (m)
PN
Operating
temperature
range
PFA
in bar
PMA
in bar
PEA
in bar
Hydrostatic
test pressure in
bar for
Allowable operating
pressure in bar at
Working
temperature max
of 50°C
DIN EN1092-2 Body Seal
0410250
0410270
80
0.75
1.00
1.25
1.50
16
-10°C
up to
50°C
16 20 25 25 17,6 16
PFA: permissible working pressure
PMA: max. hydrostatic pressure with water hammer which the component can withstand from time to time during operation
PEA: Max. hydrostatic pressure with water hammer which a newly installed component can withstand for a relatively short time, not valid for non-closed valves
Each product is individually tested on the production line before delivery. The strength and tightness of the gate valves are tested in the
manufacturing factory according to DIN EN12266, DIN EN14339 and DIN EN1074-6.
HALIOSTM and HALIOSTM Premium DIN Underground Fire Hydrants are only suitable for “OPEN – CLOSED” duty. Their main purpose is
the access and withdrawal of water in order to extinguish fires.
They comply with European standards DIN EN14339, DIN EN1074-6 and the relevant DVGW requirements W 386 (P), and they have
DVGW approval for drinking water as well as the CE mark according to European Construction Products Directive 89/106/CEE.
These hydrants are designed with a one-piece body. The stem bearing is trapped in the flange bearing without contact with the medium.
A safety interlock prevents ejection of the inner trim during dismantling work for maintenance. The cams at the outlet-claw prevent the
ejection of the standpipe under vibration conditions. The automatic drainaged device, placed on both sides, limits the amount of residual
water to a value below the requirement of the DIN standard.
They are proposed in Single Shut Off version (UHA) or Double Shut Off version (UHAD), and are available in STANDARD or PREMIUM
level of finish.
HALIOSTM HALIOSTM Premium

P6/19
IOM_FIH210201_HALIOS STD-PREM_EN
The technical data and performance may be modified
without prior notice depending on the technical advances.
Item Description N° HALIOSTM
Material
HALIOSTM PREMIUM
Material
1Body 1EN-GJS-400-15 (1) EN-GJS-400-15 (1)
2Operating nut 1Copper alloy
CW617N
Copper alloy
CW617N
3Operating shaft 11.4301 1.4301
4.1 Shut-off cone
insert
1EN-GJS-450-10 EN-GJS-450-10
4.2 Shut-off cone
coating
1EPDM PUR
5Bolt 2A2-70 A2-70
6Nut 2A2-70 A2-70
7Bonnet 1EN-GJS-450-10 (2) EN-GJS-450-10 (2)
8.1 Stuffing nut 1Copper alloy
CW617N
Copper alloy
CW617N
8.2 O-ring (stuffing
nut/stem)
2EPDM EPDM
8.3 O-ring (stuffing
nut/body)
1EPDM EPDM
8.4 Dust guard 1PUR PUR
9Operating stem 11.4021 1.4021
10 Bonnet O-ring 1EPDM EPDM
11 Identity disc 1Polypropylene Polypropylene
12 Washer 4A2 A2
13 Bolt (outlet claw
and bonnet)
4A2-70 A2-70
14 Operating square
cap
1EN-GJS-450-10 (3) EN-GJS-450-10 (3)
15 Bolt 1A2-70 A2-70
16 Square cap plug 1PE-HD PE-HD
17 Foreign matter
deflector
1EPDM EPDM
18 Outlet claw 1EN-GJS-450-10 (2) EN-GJS-450-10 (2)
19 Seat (outlet claw) 11.4301 1.4301
20 Rope 1Nylon Nylon
21 Cap (outlet claw) 1PE-HD PE-HD
22 Drain tube 2PE-HD PE-HD
23.1 Ball insert 1S235JR S235JR
23.2 Ball coating 1EPDM EPDM
24.1 Ball retainer insert 1PA 6.6 PA 6.6
24.2 Ball retainer
coating
1EPDM EPDM
25 Anti-friction
washer
2POM POM
26 O-ring (operating
stem)
1EPDM EPDM
27 Washer 1A2 A2
For HALIOSTM Premium: 1: Dark blue coating with enamel inside/outside. 2: black coating with epoxy 250 microns. 3: black coating
with epoxy 50 microns.
For HALIOSTM: 1: blue coating (Ral 5015) with epoxy 250 microns. 2: black coating with epoxy 250 microns. 3: black coating with
epoxy 50 microns.
4.2
4.1
22
23.1
23.2
24.1
24.2
16
27
8.4
8.1
7
13
10
25
26
2
5
3
6
12
1
15
18
17
13
12
20
21
19
14
11
8.3
8.2
9
Double shut-off (UHAD)
Single shut-off (UHA)

P7/19
IOM_FIH210201_HALIOS STD-PREM_EN
The technical data and performance may be modified
without prior notice depending on the technical advances.
2.2 Functional description and allowable operation
The sintgle shut-off underground fire hydrant is composed of:
• A vertical tubing (7) having in the lower part a horizontal
inlet flange (1) to connect to the water network, and in the
upper part an outlet claw 75 (R. 11).
• A shut-off valve made with of a cone (4) encapsulated in
elastomer, and closing on the coated seat (2) at the bottom
part of the body. This cone (4) is linked to the operating
stem (9) in the upper part by a tube (6) having a nut (8). The
operating system is operated through a square cap (10) .
• A double automatic drainage device located on both side
of the bottom part, above the seating area of the cone (3).
The rotary motion, in the anti-clockwise direction, on the
square cap (10), in the upper part of the hydrant, moves the
shut-off cone (4) in a downward direction in order to release
the passage around the seat. Upon opening, the water passes
around the shut-off cone in the cone chamber (5) and rises
through the vertical tubing (7) to emerge at the outlet claw
(11). During the downward movement of the shut-off cone (4),
its two guiding lugs close the two drainage orifices (3).
The rotary motion in the clockwise direction on the square
cap (10) , in the upper part of the hydrant, moves the shut-off
cone (4) in an upward direction in order to close the passage.
Upon closing, the flow stops. At the end of the upward
movement of the shut-off cone (4), its two guiding lugs open
the two drainage orifices (2) in order to empty the hydrant.
In the case of the double shut-off underground fire hydrant,
there is a floating ball (12) located in the cone chamber (5).
This floating ball follows the movement of the shut-off cone,
and allows secure closing.
Closing/Opening direction are indicated on the products.
Operation of our fire underground hydrants must be
performed with the appropriate operating Key «C» according
to DIN 3223, for square cap 32. The appropriate operating
Key «C» should only be used for the recommended torque
values according to Table 4, otherwise the hydrant might be
damaged.
Double shut-off (UHAD) Single shut-off (UHA)
11
9
8
7
6
4
2
12
3
5
1
10
Single shut-off version (UHA) Double shut-off version (UHAD)
Figure 2: Hydrant closed Figure 4: Hydrant open
Figure 1: Hydrant closed Figure 3: Hydrant open

P8/19
IOM_FIH210201_HALIOS STD-PREM_EN
The technical data and performance may be modified
without prior notice depending on the technical advances.
DN Type
Installation
Depth
RD (m)
H
(mm)
h
(mm)
L
(mm)
l
(mm)
C
(mm)
Outlet Claw Kv Total
No. of
turns for
opening
No. of
turns
before
flow
Weight (kg)
d1
(mm)
d2
(mm)
h1
(mm)
80 UHA 0.75 474 48 243 178 120 108 75 50 110 9 4 23.5
80 UHA 1.00 672 48 243 178 120 108 75 50 110 9 4 26.5
80 UHA 1.25 922 48 243 178 120 108 75 50 110 9 4 30.5
80 UHA 1.50 1172 48 243 178 120 108 75 50 110 9 4 34.5
80 UHAD 0.75 474 48 243 178 120 108 75 50 110 9 4 24
80 UHAD 1.00 672 48 243 178 120 108 75 50 110 9 4 27
80 UHAD 1.25 922 48 243 178 120 108 75 50 110 9 4 31
80 UHAD 1.50 1172 48 243 178 120 108 75 50 110 9 4 35
A special shape under the form of teeth is visible at the top of the body of the product in order to give the
information of the installation depth.
Table 1: Dimensions
1 tooth = 0.75 m 2 teeth = 1.00 m 3 teeth = 1.25 m 4 teeth = 1.50 m
Figure 5: View DN80
INLET FLANGE EN1092-2 DN80 PN10/16

P9/19
IOM_FIH210201_HALIOS STD-PREM_EN
The technical data and performance may be modified
without prior notice depending on the technical advances.
2.4 Intended use
HALIOSTM and HALIOSTM Premium are for "OPEN - CLOSED"
operation only.
By virtue of its design, and its different material options, they
might be used for potable water or raw water.
Before installation, check the configuration of the material in
order to control the compatibility of the hydrant with the fluid
that is going to flow both inside and in the external environment.
If used with technically clean fluids (e.g. drinking water,
depending on allowable operating pressure) flow speeds up to 4
m/s are allowed in permanent conditions of use (see table 2 for
limits), when the wedge is in fully opened position.
In case of fire protection use, maximum flow rate should not
exceed 1.5 times the Kv-value for cavitation safety reason.
Temperature of the medium shall not exceed max. 50°C (see
table 3 for limits).
European Standard DIN EN1074-6
Maximum Temperature 50°C
Maximum Flow Velocity in
permanent conditions of use 4 m/s (PFA16)
Table 2: Maximum temperature and flow velocity
Installation conditions can be outdoors, buried in the ground, in
a valves‘ room.
All deviating operating instructions and deviating fields of
application are subject to the manufacturer’s approval.
As we do not have any control or prior knowledge of the quality
and properties of the water, we recommend the installation of
our hydrant with enamel coating when the water tends to form
deposits or encrustations.
2.5 Unacceptable operation
Do not use the shut-off cone of the hydrant in an intermediate
position to restrict water flow. Continuous operation in a flow-
restricting position can cause cavitation and major wear of the
products that will lead to leakage and malfunctions. This type of
underground fire hydrants is suitable only for “OPEN-CLOSED”
operation.
Negative pressure levels (cavitation) are to be avoided at all costs.
Extending the operating elements, e.g. with levers or similar
devices is not allowed.
Do not exceed temperature limits for the flow media.
Do not exceed permisable operating pressure. The closed valve
may only be loaded up to the allowable operating pressure.
For the version with the cone fully encapsulated in EPDM, the
EPDM parts must not be allowed to come into contact with
any medium containing oil or grease, as EPDM swells in those
circumstances.
Whatever the materials that constitute it, it is absolutely
forbidden to use our underground fire hydrants with gaseous
fluids such as propane, butane, natural gas or with hydrocarbon
fluids like petrol, diesel, etc.
2.6 Marking
The following information is cast into the body:
• Manufacturer name
• DN
• PN
• Cast material
• Installation depth RD
The following information is cast into the bonnet:
• Total number of turns for closing or opening
• DN
• PN
• European standard EN14339
The following information is shown on additional labels:
• Name of the range
• Product number
• Drilling type, if special or different than PN
• Approvals (if any)
• Date of manufacturing
In addition to standard marking and factory labels, each hydrant
is delivered with a corrosion resistant identity disc, located under
the operating square cap, in order to give easy acces to the main
characteristics of the products like type of shut-off, installation
depth, standards, etc, once it has been stored or installed. The
disc is yellow for single-shut off version, and blue for the double
shut-off version.
WARNING
Refer to technical leaflet W331 from
DVGW for deployment, installation,
implementation, operation and
control.

P10/19
IOM_FIH210201_HALIOS STD-PREM_EN
The technical data and performance may be modified
without prior notice depending on the technical advances.
3 -TRANSPORT,
HANDLING AND
LIFTING
The hydrant must be transported in the proper packaging to
guarantee protection against external damage and bad weather.
In case of severe climate conditions, special plastic-sealed
packaging with desiccant products must be used.
Transport must be carried out carefully in order to avoid shock
and any kind of damage, especially to the coating. Careless
handling may cause damage to the hydrant. Prior to mounting,
such damage is to be repaired in an appropriate manner.
During the transport, the hydrant is delivered in the closed
position.
Check the weight of the hydrant, in this document, (table 3)
before commencing any operations. Hydrants too heavy to be
handled manually must be transported by means of a lifting
device suitable for the weight involved (e.g. broad belts). Avoid
use of chains and ropes, in order to protect the hydrants from
coating damage. The lifting device must:
• be placed securely around the body , respecting the center of
gravity,
• using the special lifting lug on the body of the hydrant.
It is forbidden to attach the lifting gear to the square cap, the
outlet claw or in the flange holes, as this would be contrary to the
relevant safety regulations.
WARNING
Follow the applicable safety
regulations and wear the required
personal protective equipment.
WARNING
Failure to use suitable load
carrying devices for transport and
installation of hydrants can be
dangerous to health and safety.
DN Type Installation Depth
RD (m)
Weight
(kg)
80 UHA 0.75 23.5
80 UHA 1.00 26.5
80 UHA 1.25 30.5
80 UHA 1.50 34.5
80 UHAD 0.75 24
80 UHAD 1.00 27
80 UHAD 1.25 31
80 UHAD 1.50 35
Table 3: weight of the hydrants DN80

P11/19
IOM_FIH210201_HALIOS STD-PREM_EN
The technical data and performance may be modified
without prior notice depending on the technical advances.
4 -STORAGE
The Hydrants should be stored in a location that protects them
from any pollution or contamination. Do not store the hydrants
out of doors. During the storage period, the hydrants must be
protected (e.g. by covering them with a tarpaulin) against outside
influences and impurities like:
- Humidity and rain, to avoid corrosion,
- Wind and sand, to avoid the penetration of solid particles that
could damage the guiding area and seat,
- Sunshine and heat, to prevent oxidation of the elastomer and
coating due by ultraviolet light.
Take into account also that long storage under severe conditions
can cause damage to the coating, elastomer and seals.
Leave the shut-off cone in the closed position in order to avoid to
damage it.
Take care to not damage the coating. Ensure that the hydrants
is stored in a stable position. Store hydrants lying in a stable
horizontal position.
If long-time storage is required, the place of storage should be
selected in such a way that the following conditions are met:
frost-protected - cool - dry - dust-free - dark (for elastomer
UV-light is inadmissible). If it is impossible to comply with these
conditions, the hydrants must be packed to meet the above
mentioned requirements (e.g. they must be sealed inside dark
plastic sheets).
The protective flange covers or packing should be kept up to the
assembly phase.
The valves are designed for a storage temperature of – 20°C to
+50°C.
5 - INSTALLATION
INTO THE PIPELINE
WARNING
Before installation, refer to
technical leaflet W331 from DVGW
for deployment, installation and
implementation.
5.1 Location of installation
Warning! After installation, it is important that all around the
hydrant there is free access for operation and maintenance.
5.2 Assembly positions
Our hydrants are designed to be installed and assembled only in
the vertical position.
5.3 Installation
Prior to installation:
• Remove all packing material from the hydrant, as well as
the protective flange covers.
• Check configuration of the material in order to control the
compatibility of the hydrant with the fluid that is going to
flow inside and with the external environment.
• By turning the operating square cap anti-clockwise, and
clockwise open and close the hydrant to check its integrity
and ensure that it works properly. If it does not, or if any
damage is observed, inform us immediately.
• Clean off any dirt which may have settled on the sealing
surface during transport or storage. Check if there are
foreign bodies that could prevent correct operation.
• Check that pipeline is free from impurities and foreign
matter. If necessary flush and clean the pipeline in order to
evacuate all foreign matter. Foreign matter, residue or dirt
might damage the shut-off cone or affect the operation of
the hydrant and even block it.
• Check that the gaskets’ seats on the duck foot bend (N-piece)
and that the gasket of the hydrant flange are perfectly clean
and free from stripes, which may prevent watertight sealing.
If necessary, clean the flange of the duck foot bend (N-piece)
to remove any particles or dirt which may have been deposited
there.
• Check that the flanges of the duck foot bend (N-piece) are
drilled in accordance with the same standards as the hydrants.
• The mating flange of the duck foot bend (N-piece) must be in
the horizontal plan position.
When connecting the hydrant to the pipe, avoid the transmission
of stress from the pipe to the hydrant body. Make sure that the
distance between the top of the operating square cap and the
Ground level is between 90 to 220 mm (as requested in technical
leaflet W331 from DVGW / see figure 5).
As the hydrant is delivered with a built-in inlet flange gasket
(which is reinforced by a composite insert) , do not :
• Use an extra flange gasket to connect the hydrant to the
network.
• Remove the built in inlet flange gasket to replace it by a
standard flange gasket.
It is required to install an isolation valve on the pipe, upstream of
the inlet of the hydrant, in order to isolate it from the network for
maintenance work.
For stability, the duck foot bend (N-piece) must be sufficiently
anchored by means of a concrete block or by any other appropriate
means.
For assembly, 8 bolts with size of M16 are necessary. For each
flange’s hole, washers shall be placed on both sides of the
flange’s assembly:

P12/19
IOM_FIH210201_HALIOS STD-PREM_EN
The technical data and performance may be modified
without prior notice depending on the technical advances.
Draining area
Anchoring system of
the duck foot bend
Upstream
Isolating
valve
• Set up the bolts,
• Tighten them by hand,
• Tighten bolts gradually in a star-shaped pattern (see figure
6 – order from 1 to 8).
• At the end, tighten the connecting bolts evenly, without
distortion and crosswise, under a torque between 100 and
120 Nm. The value must not exceed 70% of the limit of
tightening torque of the bolts used.
Once the hydrant is assembled, the threads of the bolts/rods
should be greased with a brush or spray. MOLYCOTE or a similar
graphite based waterproof grease should be used to prevent
corrosion and facilitate subsequent dismantling operations.
After installation and before backfilling the trench and the
hydrant, perform a pressure test and functionality test (open and
close the hydrant) under pressure.
During backfilling of the hydrant, an adequate and sufficient
draining area must be established directly all around the hydrant
at the level of the two drainage devices, in order to allow the
emptying of its water volume. It may consist for example of an
adequate volume of pebbles, packed gravel, crushed rock or
any other appropriate means. When complete installation of
the hydrant is finished check that the drainage of the hydrant is
working perfectly by verifying that the hydrant empties after an
operation of opening/closing.
6 - COMMISSIONING
AND OPERATION
WARNING
Before installation, refer to technical
leaflet W331 from DVGW for deployment,
installation and implementation.
Before the hydrant is commissioned and installed, it must be
subject to a visual check. After installation, the hydrant must
be checked for movement of the inner valve: turn the square
cap over the total stroke (OPEN-CLOSE).
Each hydrant must be operated in respect of the operating
torque by a key according to DIN 3323-C.
Over-torque on the hydrant is strictly prohibited. According to
DIN standards, you will find in the table below the Maximum
Operating Torque (MOT) and Minimum Strength Torque (MST)
in Nm for gate underground fire hydrants to be operated by
key according to DIN 3323-C (see table 4). Operation by other
means or "Ring key and bar" is strictly prohibited.
Closing or opening operation of the hydrant must be done
under a torque that do not exceed the MOT stated in the table
below. In any case it is recommended to:
- turn 1/4 turn back after a complete opening operation,
- turn 1/4 turn back after a complete closing operation.
DN
Maximum
Operating
Torque (MOT)
according to
DIN EN14339
and DIN
EN1074-6
(in Nm)
Minimum
Strength
Torque (MST)
according to
DIN EN14339
and DIN
EN1074-6
(Nm)
Total number of
turns for
Opening or
Closing
(full stroke)
(Nm)
Number
of turns
before
flow
80 105 210 9 4
Table 4: Torques and number of turns
WARNING
Excessive torque may damage the hydrant body and
result in uncontrolled water leakage of up to 16 bar. In
this case, further work on the hydrant must be stopped
immediately and a safe distance to the hydrant must be
maintained, especially directly above the hydrant. The
isolating valve installed upstream of the hydrant must be
closed immediately in order to stop the supply of water.
If the torque necessary to close the hydrant is above
MOT values, plan a maintenance phase on the hydrant.
In case of over-torque applied to the hydrant, a proper
maintenance must be done including replacement of
the damaged components.
1
5
8
4
3
6
7
2
Figure 6: Flange DN80
Figure 7: Installation example

P13/19
IOM_FIH210201_HALIOS STD-PREM_EN
The technical data and performance may be modified
without prior notice depending on the technical advances.
7 - MAINTENANCE
7.1 Maintenance recommendations
If they are used correctly, our underground fire hydrants are
maintenance-free. However, the performance and operating
conditions of parts of the system must be checked at regular intervals.
Visual and functional inspections and the resulting maintenance
work on the hydrant must only be carried out by qualified persons
(DVGW W400-3 (A)) and must be documented. In accordance with
DVGW leaflet W 392 / W331, monitoring of the functional capability
and tightness at MOT should take place at regular intervals, at least
≤4 years with regard to:
• Visual inspection to the maximum extent (integrity of corrosion
protection, presence of the identity disc, integrity of the claws for
the standpipe insert, complete emptying of the body, the condition
of the foreign matter deflector and / or presence and correct seat
of the cover of the claw, etc).
• Functional inspection by opening and closing the valve over an
entire stroke (easy mobility of the shut-off, complete emptying of
the body, …).
• Check for smooth operation and tightness at MOT values.
If the torque necessary to close or open the hydrant is above MOT
values, a proper maintenance must be done including changes of the
damaged components.
The operating/maintenance visits must be increased to an adapted
frequency if the gate valves are used with raw water or water that
tends to form deposits (limestone, etc) and incrustations, or in the
case of highly abrasive water, strong hydraulic conditions, strong
environmental variations.
Lubricant/grease must be approved for potable water application, and
must be appropriate to the functions it must fulfill. Recommended
lubricants for all types of maintenance (see paragraph 7.3) and for
flow medium water is: Klüber Synth VR 69-252 as unique grease
(silicone-free lubricant).
NOT ALLOWED OPERATION
Continuous operation in throttle position leads to
cavitation damage due to the high flow velocity.
An extension of the operating key by use of a lever
or similar is not allowed.
It is not permitted to open the hydrant against a
closed inspection or revision valve.
Do not exceed operating temperature limits and
operating pressure limits.
Closed valve may only be loaded up to nominal
pressure.
To avoid overpressure in the body and thus damage
to the shut-off cone insert, do not close the hydrant
against a closed standpipe or a closed outlet fitting.
The nominal pressure in the pipeline should not exceed the allowable
operating pressure that the hydrant can support.
On our hydrant, the materials and the corrosion protection are resistant
to the commonly used disinfectant products. Take care not to affect
hydrant materials when using cleaning / disinfecting products.
TO OPEN
• Carry out traffic safety procedure.
• Clean the outside street cap area of road dirt.
• Loosen the tight-fitting cover of the street cap, if necessary use a
suitable cover lifter.
• Take out the cover and swing it sideways.
• Clean the claw and the claw-cover of dirt, then lift the cover, then
rinse it without the standpipe.
• Insert the standpipe with the claw nut screwed down into the claw
and turn it to the right until fixed and tight seating is achieved.
• Fully open the outlet of the standpipe so that the air can escape
when the hydrant is opened.
• Turn the key C (according DIN 3223) slowly, anti clockwise till the
water flushes and clean the hydrant and the standpipe with the
escaping water.
• Close the outlet fitting on the standpipe and connect the hoses.
• Open the outlet fitting on the standpipe in order to get water.
WARNING
If this order is not followed, there is a risk
of polluting the drinking water.
TO CLOSE
• With the outlet fitting slightly open, close the hydrant completely
by turning clockwise till the stop. Then it`s recommended to turn
¼ turn to the left to decock the inner valve. If the outlet fitting
of the standpipe is not open at the closing process, a positive
pressure may build up. If necessary , unscrew the hoses
(uncoupling).
• Once the hydrant is closed, loosen the standpipe by turning to
the left.
• Observe whether the water level in the body drops during
emptying.
• Close the claw with his cover
• Close the street cap
• Remove traffic safety

P14/19
IOM_FIH210201_HALIOS STD-PREM_EN
The technical data and performance may be modified
without prior notice depending on the technical advances.
7.2 Trouble shooting guide
TROUBLE ROOT CAUSE SOLUTION
Leakage at the top of the bonnet around the
stem
Stuffing nut in wrong position Stop to operate the hydrant and change the
complete Bonnet
Defective Stuffing nut Stop to operate the hydrant and change the
complete Bonnet
Defective O-rings Change O-rings
Leakage between the bonnet and the body Defective gasket Change the gasket between body and bonnet
The hydrant is not closing
Upstream isolating valve is closed
Check the opening/or open the upstream
isolating valve and try again to close the
hydrant
Defective operating nut Replace operating nut
Foreign body between the shut-off cone and
seating area
Open the hydrant to make a flush out. If it is
not working: remove the inside trim of the
hydrant and remove the foreign body.
Curved operating stem Replace operating stem
Large deposits and incrustations in the
seating and guiding area
Remove the inside trim of the hydrant and
clean the seating and guiding area
Stuffing nut in wrong position Stop to operate the hydrant and change the
complete Bonnet
Defective Stuffing nut Stop to operate the hydrant and change the
complete Bonnet
The hydrant is not opening
Upstream isolating valve is closed
Check the opening/or open the upstream
isolating valve and try again to close the
hydrant
Defective operating nut Replace operating nut
Foreign body below shut-off cone Remove the inside trim of the hydrant and
remove the foreign body.
Curved operating stem Replace operating stem
Large deposits and incrustations in the
seating and guiding area
Remove the inside trim of the hydrant and
clean the seating and guiding area
Stuffing nut in wrong position Stop to operate the hydrant and change the
complete Bonnet
Defective Stuffing nut Stop to operate the hydrant and change the
complete Bonnet
Hydrant is leaking
Shut-off cone damage Replace shut-off cone or inside trim
Large deposits and incrustations in the
seating area
Remove the inside trim of the hydrant and
clean the seating area. If the seating area is
damaged, the replacement of the complete
hydrant must be carried out.
Table 5: Trouble shooting guide
WARNING
Excessive torque may damage the hydrant body and result in uncontrolled water leakage of up to 16 bar. In this case, further work on
the hydrant must be stopped immediately and a safe distance to the hydrant must be maintained, especially directly above the hydrant.
Isolating valve installed upstream the hydrant must be closed immediately in order to stop the supply of water.
In any case, if the seating area of hydrant is damaged, replacement of the complete hydrant must be carried out.

P15/19
IOM_FIH210201_HALIOS STD-PREM_EN
The technical data and performance may be modified
without prior notice depending on the technical advances.
Our underground fire hydrants are maintenance free.
However, the complete bonnet, the operating inside trim, and
the complete outlet claw (including foreign matter deflector
and cap) can be removed and installed from the road through
the street cap (see section 7.4 for composition of spare parts
set). In the event that it is necessary to replace any part of
the hydrant, follow the instructions below. Replacement of the
shut-off ball, inlet flange gasket or drain tube can be done only
if the hydrant is totally disassembled from the water network.
7.3 Replacement
WARNING
Before carrying out inspection or any repair work on the
hydrant, the pipe section in which the hydrant is installed
must be depressurized and safe, e.g. by closing the gate
valve and emptying. A built-in double shut-off and / or
closed gate valve installed upstream of the hydrant are
no guarantee that the hydrant inside is depressurized.
After maintenance works, when putting back under
pressure, it is essential to operate the hydrant very
slowly when opening because some air under pressure
might have become trapped.
16
27
8.4
8.1
7
13
10
25
26
2
5
3
6
12
1
15
18
17
13
12
20
21
19
14
11
8.3
8.2
9
4.2
4.1
22
23.1
23.2
24.1
24.2
Double shut-off (UHAD) Single shut-off (UHA)
7.3.1 Replacement of the complete bonnet:
1Isolate the network section where the hydrant is installed
(upstream).
2Depressurize the network section where the hydrant is
installed.
3The hydrant should be fully closed by turning the square
cap (14) clockwise.
4Completely unscrew the hexagonal bolts (13) of the bonnet
(7).
5Turn the square cap (14) anti-clockwise until the operating
stem (9) is out of the operating nut (2).
6Remove the complete bonnet (7) including the bonnet
O-ring (10).
7Replace the complete bonnet by a new one (7) including
a new bonnet O-ring (10). Before installation, lubricate the
operating stem (9) and wedge nut (2) and bonnet O-ring
(10) with a small amount of appropriate grease (see in the
paragraph 7.1).
8Re-assemble the complete bonnet (7), repeating these
operations in reverse order.
9Make a full opening and closing of the hydrant without
pressure.
10 Check the correct operation of the product under pressure.
When opening, be careful of the release of air that might have
become trapped under pressure.

P16/19
IOM_FIH210201_HALIOS STD-PREM_EN
The technical data and performance may be modified
without prior notice depending on the technical advances.
7.3.2 Replacement of the complete inside trim:
1Isolate the network section where the hydrant is installed
(upstream).
2Depressurize the network section where the hydrant is
installed.
3The hydrant should be fully closed by turning clockwise
on the square cap (14).
4Unscrew the hexagonal bolts (13) of the bonnet (7), but
not completely, let them screwed at the minimum.
5Turn the square cap (14) anti-clockwise until the gap
between the bonnet (7) and body (1) is around 30mm.
6Remove the 2 hexagonal bolts (13).
7Under location of the two hexagonal bolts (13), insert
adequate resistant shims of 30 mm between the body (1) and
the bonnet (7). See figure 8.
8Turn the square cap (14) clockwise until the operating
stem (9) is out of the operating nut (2).
9Remove the complete bonnet (7) including the bonnet
O-ring (10).
10 Lift complete inside trim (2-3-4) until it stops and unlock
with 30 degrees left turn. Pull the complete inside trim (2-3-
4) completely out of the body.
11 Replace the complete inside trim (2-3-4) by a new one,
including a new bonnet O-ring (10). Before installation,
lubricate the operating stem (9), shut-off cone (4), wedge nut
(2) and bonnet O-ring (10) with a small amount of appropriate
grease (see in the paragraph 7.1). Insert bonnet O-ring (10)
and insert complete inside trim (2-3-4) into the body (1). Turn
operating nut guide tabs by 30 degrees to the right and insert
into the guide grooves of the body (1).
12 Re-assemble the complete bonnet (7). Turn the square
cap (14) clockwise until the gap between the bonnet (7) and
body (1) is around 30 mm. Align the holes of the bonnet with
the threaded holes of the body. Place two special hexagonal
bolts M16 of minimum 70 mm length with their washers M16
and screw them gradually in alternately until the bonnet (7) is
definitely assembled and tightened on the body (1). See figure
9. Once it is done, replace tight the special hexagonal bolts
M16 of minimum 70 mm length and washers by the original
M16 bolts (13) and washers (12) of the product.
13 Make a full opening and closing of the hydrant without
pressure.
14 Check the correct operation of the product under
pressure. When opening, be careful of the release of air that
might have become trapped under pressure.
7.3.3 Replace the complete outlet claw:
1Isolate the network section where the hydrant is installed
(upstream).
2Depressurize the network section where the hydrant is
installed.
3The hydrant should be fully closed by turning on the
square cap (14) clockwise.
4Completly unscrew hexagonal bolts (13) of outlet claw (18).
5Remove the outlet claw (18) with its cap (21) and the
foreign matter deflector (17).
6Replace the outlet claw by a new one (7) including with its
new cap (21) and a new foreign matter deflector (17). Before
installation, lubricate the foreign matter deflector (17) with
a small amount of appropriate grease (see in the paragraph
7.1).
7Re-assemble the complete outlet claw, repeating these
operations in reverse order.
8Make a full opening and closing of the hydrant without
pressure.
9Check the correct operation of the product under
pressure. When opening be careful of the release of air that
might have become trapped under pressure.
30 mm 30 mm
Figure 8: Disassembly of the bonnet with inside trim
30 mm
BoltsM16x70 mm +
washers M16
30 mm
Figure 9: Assembly of the bonnet with inside trim
Figure 10: QR code for the tutorial of the disassembly and
assembly of the bonnet with inside trim.

P17/19
IOM_FIH210201_HALIOS STD-PREM_EN
The technical data and performance may be modified
without prior notice depending on the technical advances.
7.4 Spare parts
PART NUMBER TYPE OF SPARE PART SET TYPE OF PRODUCT CONCERNED ITEMS CONCERNED BY THE SET
SPA00063TS PUR shut-off cone HALIOSTM Premium 4-5-6-10
SPA00064TS Operating inside trim RD0.75 / PUR cone HALIOSTM Premium 2-3-4-5-6-10
SPA00065TS Operating inside trim RD1.00 / PUR cone HALIOSTM Premium 2-3-4-5-6-10
SPA00066TS Operating inside trim RD1.25 / PUR cone HALIOSTM Premium 2-3-4-5-6-10
SPA00067TS Operating inside trim RD1.50 / PUR cone HALIOSTM Premium 2-3-4-5-6-10
SPA00072TS EPDM shut-off cone HALIOSTM 4-5-6-10
SPA00068TS Operating inside trim RD0.75 / EPDM
cone HALIOSTM 2-3-4-5-6-10
SPA00069TS Operating inside trim RD1.00 / EPDM
cone HALIOSTM 2-3-4-5-6-10
SPA00070TS Operating inside trim RD1.25 / EPDM
cone HALIOSTM 2-3-4-5-6-10
SPA00071TS Operating inside trim RD1.50 / EPDM
cone HALIOSTM 2-3-4-5-6-10
SPA00073TS Complete flange bearing HALIOSTM / HALIOSTM Premium 7-8.1-8.2-8.3-8.4-9-10-11 (both
colors)-12-13-14-15-16-25-26-27
SPA00074TS Complete outlet claw with plastic cover HALIOSTM / HALIOSTM Premium 12-13-17-18-19-20-21
SPA00075TS Complete outlet claw with self-closing
cover HALIOSTM / HALIOSTM Premium 12-13-17-18-19-Self-closing cap
SPA00076TS Complete outlet claw with stay-open
cover HALIOSTM / HALIOSTM Premium 12-13-17-18-19-stay-open cap
SPA00077TS Operating square cap HALIOSTM / HALIOSTM Premium 14-15-16-27
SPA00078TS Set of gasket HALIOSTM / HALIOSTM Premium 8.2-8.3-8.4-10-17-25-26
SPA00079TS Set of identity disc HALIOSTM / HALIOSTM Premium 11 (both colors)
SPA00080TS Shut-off ball HALIOSTM / HALIOSTM Premium 23
SPA00081TS Inlet flange gasket HALIOSTM / HALIOSTM Premium 24
SPA00082TS Set of 2 draining tubes HALIOSTM / HALIOSTM Premium 22
16
27
8.4
8.1
7
13
10
25
26
2
5
3
6
12
1
15
18
17
13
12
20
21
19
14
11
8.3
8.2
9
4.2
4
23
24
4.1
22
23.1
23.2
24.1
24.2
Double shut-off (UHAD) Single shut-off (UHA)

P18/19
IOM_FIH210201_HALIOS STD-PREM_EN
The technical data and performance may be modified
without prior notice depending on the technical advances.
8 - HYDRAULIC
CHARACTERISTICS
(1) The curve and Kv value are substantially the same regardless of the height of the product and the shut-
off type (single or double).
The Kv value indicates how much water in m3/h can flow through
the product at a temperature of 20 °C and for a pressure loss of
1 bar.
The Kv values of thet HALIOSTM and HALIOSTM Premium
underground fire hydrant are above the minimum value that
arerequired in the standard DIN EN14339.
9 - CE MARKING
European Construction Products Directive 89/106/CEE must
be respected in all the countries of the European Union for all
undeground fire hydrants. Underground fire hydrants which are
subject to this European directive are the object of a "CE" marking
and also a CE declaration of conformity.
10 -AFTER SALES
SERVICE CONTACT
For technical assistance, or all questions that concerns
the product or IOM manual, please find the details of your
closest contact on www.talis-group.com or send an email to
info@talis-group.com.
TALIS Management Holding
Postfach 1280
D-89502 Heidenheim
Meeboldstraße 22
D-89522 Heidenheim
Telefon: +49 7321 320-0
Telefax: +49 7321 320-491
info@talis-group.com
www.talis-group.com
Type of outlet Kv value (m3/h)(1)
claw 75 110
Head loss curve for HALIOSTM and HALIOSTM Premium underground
hydrant DN80(1)
Flow rate in m3/h
Head loss in bar
0679
BAYARD, 69330 MEYZIEU, FRANCE
07
EN 14339
MOT and mST 105 Nm and 210 Nm
Inlet connection
Outlet connection
DN 80 EN 1092-2
Ф75 mm DVGW W 386 (P)
Kv 110 m3/h
Volume of retained water < 100 ml
Time for draining < 15 min x RD
Direction of closure Clockwise
Opening turns(dead & total) 4 and 9
PN 16
Underground fire hydrant, spheroidal graphite cast iron DN 80
Single or double shut-off version
0679-CPR-0214

TALIS is the undisputed Number One for water transport and water flow
control. TALIS has the best solutions available in the fields of water and
energy management as well as for industrial and communal applications.
We have numerous products for comprehensive solutions for the whole
water cycle – from hydrants, butterfly valves and knife gate valves through
to needle valves. Our experience, innovative technology, global expertise
and individual consultation processes form the basis for developing long-
term solutions for the efficient treatment of the vitally important resource
“water”.
ERHARD GmbH & Co. KG
Postfach 1280
Meeboldstrasse 22
D-89522 Heidenheim
PHONE +49 7321 3200
FAX +49 7321 320-491
EMAIL info@talis-group.com
INTERNET www.erhard.de
www.talis-group.com
Note: Information and specifications may be changed without notification at any time.
Copyright: No copying without express written permission of TALIS
TALIS is a Registered Trademark.
IOM_FIH210201_HALIOS STD-PREM_EN
This manual suits for next models
1
Table of contents
Popular Water Pump manuals by other brands

Dupla MARIN
Dupla MARIN P4 Smart operating instructions

AIRMAC
AIRMAC DBMX100 quick start guide

Rainman
Rainman WM Series quick start guide

Gardena
Gardena 6000/5 automatic operating instructions

Pentair Jung Pumpen
Pentair Jung Pumpen PLANCOFIX LINE instruction manual

Gardena
Gardena 1442 operating instructions

MTM
MTM SDS06-AAT-TATS-02 Operator's manual

Pentair
Pentair DHR Series instruction manual

Xylem
Xylem Bell & Gossett P86108D Assembly instructions

dosatron
dosatron Green Line D90 GL Quick start-up

Clarke
Clarke CVP1000 Assembly and maintenance instructions

Aqua
Aqua HC899 Series Operating and maintenance instructions