Tamas Snow Melt Series User manual

4516 112 Ave S.E. Calgary, Alberta • Tel: (403) 279 0020 • Fax: (403) 279 0747
www.tamashydronic.com
Tamas Hydronic Panels
User Guide
Snow Melt Series
50K BTU - 350K BTU Installaon Guide
Version 1.0

4516 112 Ave S.E. Calgary, Alberta • Tel: (403) 279 0020 • Fax: (403) 279 0747
www.tamashydronic.com Page 2
Tamas Hydronic Panels
Snow Melt Series
Table of Contents
Introduction................................................................................................................................ 3
Components................................................................................................................................4
Operation.................................................................................................................................... 5
Technical Data............................................................................................................................ 6-9
Snow Sensor Installation.......................................................................................................... 10-11
Wiring...........................................................................................................................................12
Modular Expansion Panels.......................................................................................................13
Warranty......................................................................................................................................14
* Note:
The following parts lists and applicaon drawings are general samplings. Each panel conguraon dictates the required components, including
pump type. See the Technical Data secon of the manual for specic informaon on each part in your parcular variaon of the Tamas I.B.C. Boiler
Board.
This User Guide is Applicable to:
Tamas Snow Melt Panels
T-SM-HBX-50HX 50, 000 BTU Snow Melt Panel with HBX SNO-0550, SNO-0110, SNO-0111
T-SM-HBX-100HX 100, 000 BTU Snow Melt Panel with HBX SNO-0550, SNO-0110, SNO-0111
T-SM-HBX-150HX 150, 000 BTU Snow Melt Panel with HBX SNO-0550, SNO-0110, SNO-0111
T-SM-HBX-200HX 200, 000 BTU Snow Melt Panel with HBX SNO-0550, SNO-0110, SNO-0111
T-SM-HBX-250HX 250, 000 BTU Snow Melt Panel with HBX SNO-0550, SNO-0110, SNO-0111
T-SM-HBX-300HX 300, 000 BTU Snow Melt Panel with HBX SNO-0550, SNO-0110, SNO-0111
T-SM-HBX-350HX 350, 000 BTU Snow Melt Panel with HBX SNO-0550, SNO-0110, SNO-0111
Safety Procautions
Only suitably qualied individuals with formal training in electrical controls and hydronic systems
should aempt the installaon of this panel. Incorrect installaon will aect the warranty provided
with this panel.
During installaon and operaon, avoid injury from touching the hot surface of the pipe.
Please follow all warning signs on the panel for your own safety while dealing with the installaon
and service of this panel.

4516 112 Ave S.E. Calgary, Alberta • Tel: (403) 279 0020 • Fax: (403) 279 0747
www.tamashydronic.com Page 3
Tamas Hydronic Panels
Snow Melt Series
Overview, Options and Dimensions
Description
The Tamas Snow Melt Panel provides mixing and
distribuon for outdoor snow and ice melng applicaons.
The adopted conguraon is an innovave variant with the
use of the injecon pump, and an automac balancing of
the primary ow parcularly praccal and reliable.
The snowmelt system pump is piped independently from
the boiler loop so that the only head loss that needs to be
calculated in the system is the piping from the panel to the
manifold, and the loops in the slab. This feature allows for
higher ow rates and head losses if needed, which in turn
expands the range of pumping ability for the system pump.
The control on the panel measures slab temperature,
return temperature, as well as boiler loop temperature to
ensure the return water going back to the boiler does not
shock the boiler heat exchanger.
Main Features
• Stainless steel back plate and lockable stainless steel
cover
• Brazed heat exchanger
• 3/4“connecons.
• Dynamic balancing valve
• ETL approved
Technical Data
• Max. Operang Temperature: 93°C/200°F
• Max. Ambient Temperature: 49°C/120°F
• Max. Operang Pressure: 10 Bar/145 PSI
T-SM-HBX-150HX Model Shown
SNO-0550
CentralProcessing Unit
Relays:
240VAC 5A Max
Input:
120VAC 15A Max
ENTER
STATUS
SLAB INT
SUPPLY
RETURN
OUTDOOR
BLR
ON
MLT TARGET
SNOW
NONE
SYS P
ON
FL UP
OFF
FL DN
ON
20°F
95°F
75°F
10°F
25°F
120°F
Introduction

4516 112 Ave S.E. Calgary, Alberta • Tel: (403) 279 0020 • Fax: (403) 279 0747
www.tamashydronic.com Page 4
Tamas Hydronic Panels
Snow Melt Series
SNO-0550
CentralProcessing Unit
Relays:
240VAC 5A Max
Input:
120VAC 15A Max
ENTER
STATUS
SLAB INT
SUPPLY
RETURN
OUTDOOR
BLR
ON
MLT TARGET
SNOW
NONE
SYS P
ON
FL UP
OFF
FL DN
ON
20°F
95°F
75°F
10°F
25°F
120°F
1
7
10
8
3
6
4
11
5
12
9
2
Components
1Stainless Steel Back Plate
2Lockable Stainless Steel Cover (Oponal)
3Tamas Control Box
4Temperature Gauge
524V Transformer
6Injecon Pump UPS 15-58
7Brazed Plate Heat Exchanger LA14-30
8HBX Controls SNO-0550
911/4” Air Eliminator
10 11/4” Balancing Valve
11 System Pump
12 Boiler Pump
Components
T-SM-HBX-150HX Model Shown
UPS 15-58 on 50K BTU Models
UPS 26-99 on 100K-300K BTU Models
UPS 26-150 on 350K BTU Models
UPS 15-58 on 50K BTU Models
UPS 26-99 on 100K-300K BTU Models
UPS 26-150 on 350K BTU Models

4516 112 Ave S.E. Calgary, Alberta • Tel: (403) 279 0020 • Fax: (403) 279 0747
www.tamashydronic.com Page 5
Tamas Hydronic Panels
Snow Melt Series
Operation
SNO-0550
CentralProcessing Unit
Relays:
240VAC5A Max
Input:
120VAC15A Max
ENTER
STATUS
SLAB INT
SUPPLY
RETURN
OUTDOOR
BLR
ON
MLT TARGET
SNOW
NONE
SYS P
ON
FLUP
OFF
FLDN
ON
20°F
95°F
75°F
10°F
25°F
120°F
From
Boiler
To
Boiler
System
Return
System
Supply
Operation of the Primary
The primary circuit is composed of a dynamic balancing valve, an automac air separator and a boiler pump. The water
coming from the boiler pass through the air separator who connuously removes the air contained in the water. The
circulaon of fully de-aerated water enables the panel to operate under opmum condions, free from noise, corrosion,
localized or mechanical damage. The water is pumped into the primary circuit, through the boiler pump and at the same
me the balancing valve creates a consistent output pressure to the system.
The mixing part of the panel has a brazed heat exchanger and a mixing pump. The heat exchanger allows heat from the
primary circuit (water) to pass to the secondary circuit (glycol) without the two uids having to mix together. The mixing
pump injects a mix of warm water (glycol) from the return of the secondary circuit with hot water (glycol) from the heat
exchanger.
The secondary circuit is composed of a system pump and air separator. The system pump will recirculate the glycol
through the pipes embedded in the slab and the air separator will connuously remove the water from the circuit.

4516 112 Ave S.E. Calgary, Alberta • Tel: (403) 279 0020 • Fax: (403) 279 0747
www.tamashydronic.com Page 6
Tamas Hydronic Panels
Snow Melt Series
Technical Data
Max Stac Working Pressure 290 psi (20 Bar)
Temperature Range -4°F to 250°F (-20°C to 120°C)
Connecon Female NPT and Female Solder
Pressure Tappings P/T Plugs
Allowable Fluid 100% water, max 50% glycol mixture
Seng Flow Coefficient Values(Cv value=GPM@1psi ∆P)
Number of Turns
Size 1 2 3 4 5 6 7 8 9 10
Cv
Values
1” 0.56 0.89 1.19 1.74 2.67 4.18 5.80 7.54 9.16 10.20
2” 2.32 4.18 6.03 8.82 13.80 19.4 24.60 29.00 33.20 36.50
Based upon the ow or dierential pressures required within the system, the ow can be determined by using the equation:
Q = Cv .
Δp
Q
= Flow
Cv
= Flow coecient
Δp=Dierential pressure
For correction of uids other than water, the following equation applies provided the viscosity of the uid is the same for water, which is the
case for most glycol and brine solutions:
QM
δ
QR
QR
= Real ow
=
QM
= Measured ow
δ
= Specic density of uid
Balancing Valve
Technical Data

4516 112 Ave S.E. Calgary, Alberta • Tel: (403) 279 0020 • Fax: (403) 279 0747
www.tamashydronic.com Page 7
Tamas Hydronic Panels
Snow Melt Series
0
5
10
15
20
25
30
0 5 10 15 20 25 30 35
Flow (GPM)
Head (ft.)
HI
MED
LOW
Without Check Valve
With Check Valve
Performance
HI
MED
LOW
HI
MED
LOW
20
18
16
14
12
10
8
6
4
2
0
80
70
60
50
40
30
20
0
0 2 4 6 8 10 12
2 4 6
GPM
Ft
GPM
Was
8 10 12
Technical Data
UPS 26-99FC/BFC Superbrute
UPS 15-58 3 Speed Pump

4516 112 Ave S.E. Calgary, Alberta • Tel: (403) 279 0020 • Fax: (403) 279 0747
www.tamashydronic.com Page 8
Tamas Hydronic Panels
Snow Melt Series
Technical Data
UPS 26-150 F
H
[ft]
0
5
10
15
20
25
30
35
40
45
Q [US gpm]0 5 10 15 20 25 30 35 40 45
eta
[%]
0
10
20
30
40
50
60
70
80
90
UPS 26-150 F, 60Hz
Pumped liquid = Water
Liquid temperature = 140 °F
Density = 61.35 lb/ft³
P1
[W]
0
50
100
150
200
250
300
350
6 1/2"
3 1/8"
3 7/8"
3 3/4"
5 7/8"
7 1/8"
Description Value
Technical:
Speed Number: 3
Max flow: 52 US gpm
Head max: 45.3 ft
Approvals on nameplate: ETL, CSA
UPS 26-150 Pump Specifications

4516 112 Ave S.E. Calgary, Alberta • Tel: (403) 279 0020 • Fax: (403) 279 0747
www.tamashydronic.com Page 9
Tamas Hydronic Panels
Snow Melt Series
Panel Dimensions
Technical Data
24.291
35.957
9.134
13.459
27.425
33.035
13.515
NOTE: Dimensions are in inches. Includes Oponal Lockable Enclosure.

4516 112 Ave S.E. Calgary, Alberta • Tel: (403) 279 0020 • Fax: (403) 279 0747
www.tamashydronic.com Page 10
Tamas Hydronic Panels
Snow Melt Series
Installation:
1. Slab Sensor Location
Installing the sensor at the correct locaon in the slab is crical
for a properly funconing snow/ice melng system. The sensor
should be located where snowfall is normal and not aected by
surrounding buildings. Also, the sensor must not be installed
where standing water could accumulate on its surface.
The sensor locaon should also be halfway between the two
heang pipes that are installed in the slab (see FIG. 1). There is a
thermistor built into the sensor that senses the slab temperature
at all mes. Keeping the sensor away from pipes in the slab
ensures the accurate operaon of your snow/ice melng system.
a) Mounting the Socket and cover plate
When mounng the socket and cover plate in the snowmelt slab
use rebar mounted in the soil below to level the socket and cover
plate so that the cover plate is level with the nished grade of the
snow melng surface (see FIG. 2).
When the socket and cover plate are level, use a screw to ghten
the socket onto the rebar (see FIG. 3).
Failure to mount the socket properly may result in incorrect or
faulty sensor readings.
i) Ramp Mounting
The socket and cover plate can also be mounted on a ramp. Make
sure to locate the socket and cover plate near the boom of the
ramp. This will allow for proper ice melng when the melted snow
ows down (see FIG. 4).
ii) Brass Plugs
On the socket there are 4 brass plugs. These plugs are designed to
make contact with the brass ring on the sensor so the sensor can
get proper slab temperatures. Take care not to press these plugs
in or out as they are properly set at the factory. Manipulaon of
the plugs may result in the sensor not ng properly in the socket
(see FIG. 5).
Take special care to clean the brass surfaces on the inside of
the socket, making sure to clean any concrete that may have
accumulated on them. Failure to do so may result in the sensor
not making proper contact and not reading the slab temperature
properly.
Snowment sensor location (FIG. 1)
Leveling the socket and cover plate (FIG. 2)
Tightening the socket onto the rebar (FIG. 3)
Top of Slab
Heating Pipe
Rebar
Underslab
Insulation
Compact
Base
Snow Sensor Installation

4516 112 Ave S.E. Calgary, Alberta • Tel: (403) 279 0020 • Fax: (403) 279 0747
www.tamashydronic.com Page 11
Tamas Hydronic Panels
Snow Melt Series
Snow Sensor Installation
82 mm
140 mm
140 mm
140 mm
103 mm
100 mm
Side ViewTop View
Brass
Plug
Ramp Mounting (FIG. 4)
Brass Plug (FIG. 5)
DRILL
HERE
Drilling the socket (FIG. 6)
82 mm
140 mm
100 mm
Side View
b) Placing Concrete
A plasc cover is provided with the socket to prevent it from being
accidentally lled with concrete. The plasc cover is the same
thickness as the sensor ange.
This allows the nished surface of the concrete to be troweled ush
with the cover. The cover must be installed prior to placing the
concrete. Also insure that the mounng plate drainage hole remains
unplugged once the concrete has cured.
Install the socket directly on top of gravel in order to provide good
drainage. If that is not possible, please ensure that you drill a hole
through the boom of the socket for proper drainage of water for
the opcal snow sensor to funcon. If this is not done, it will void the
warranty of the snow sensor (see FIG. 6).
Never use the wire conduit as drainage. This can damage the
sensor wire resulng in damage to the control and/or sensor.
c) Installing the Sensor
Once the snow melng surface is nished you can install the snow/
ice sensor. Clean any excess debris from inside the socket. Fish the
snow/ice sensor wire through the pre-installed pipe. Make sure to
leave a lile bit of slack in the wire.
Once the snow/ice sensor is properly inserted into the socket put the
four screws back in place to secure it.
Take special care to align the screw holes from the snow/ice sensor
to those on the socket. Once the sensor is pressed into place prying
up the sensor to line up the holes will result in damage to the sensor
and, potenally, the socket.
2. Remote Sensor Location
The opcal nature of the snow/ice sensor allows for mounng
somewhere other than the slab (i.e. a roof or fence post). This is
possible, but take special care that it is not mounted in an area
where the surroundings cause an abnormal amount of snow fall.
Paving stones or equivalent should be installed with a remote sensor.
When remote mounng the sensor an external slab sensor
must be used in order for the control to be able to read the slab
temperature. The temperature sensor on the snow/ice sensor will no
longer be used.

4516 112 Ave S.E. Calgary, Alberta • Tel: (403) 279 0020 • Fax: (403) 279 0747
www.tamashydronic.com Page 12
Tamas Hydronic Panels
Snow Melt Series
Wiring
Wiring Diagram
All electrical wiring to the panel (including grounding) must conform to local electrical codes and/or Naonal Electrical
Code, ANS/NFPA No. 70-latest edion, or the Canadian Electrical Code, C22.1- Part 1.
Snow Melt Sensor
Take special care that the sensor wire is not run with any high voltage wiring as this may result in faulty readings. The
sensor is supplied with 100 feet of 22 AWG shield cable. If the sensor is more than 100 feet from the control extend the
wire from the end of the sensor wire. Do not shorten the original sensor wire then extend its length over 100 feet. When
extending the cable (to a maximum of 200 feet) use 18 AWG shielded cable. If possible two pair shields 18 AWG for best
results. You must also extend the shield wire and aach it to the same point as the black wire on the terminal block.
Do not cut the wire. All 100 . should always be le intact as the wire has an ohm rang. If you cut the wire the sensor
will be hoer than normal and void the warranty.
Outdoor Sensor
The outdoor sensor should be installed in the north face locaon and has to be connected to the HBX snow melt control
SNO-0550
Boiler
Boiler output to connect to the TT contact in the boiler
Power
Connect a 120 VAC/15 Amp supplies to the “AC IN” tagged leads in the wiring box.
L
N
120 V AC
Boiler
Outdoor Sensor
Snowmelt Sensor
Injection
Pump
Boiler
Pump
System
Pump
Heat Demand
System
Sensor
5 A 5 A
Central Processing Unit
SNO-0550
HBX
5 A
RL
1
RL
1817
1
RL
2
RL
2019
2
GR
120
16
N
L
1514
TM
32
11
TM TM
10 12 13
BL
1
BL
9
8
1
15
SG
2
2
PW TM
1 3 4
24 VAC MAX
RL
3
RL
2221
3
FD
1
FD
76
1
5
S
4
3C
1
2 A
DO NOT
CONNECT
POWER HERE
DO NOT
CONNECT
POWER HERE
Return
Sensor
8
4
1
5
9
12
14
13
TAM-R2-120V AC

4516 112 Ave S.E. Calgary, Alberta • Tel: (403) 279 0020 • Fax: (403) 279 0747
www.tamashydronic.com Page 13
Tamas Hydronic Panels
Snow Melt Series
Maintenance
Have your panel checked and serviced by a licensed contractor at least once a year, preferably before the heang season
begins.
Complete the following checklist:
• Check the level of the system anfreeze soluon required for the snow melt system
• Check controls of the system to ensure proper and safe operaon (see instrucons below- HBX Manual page 12)
Maintenance
Testing
SETUP MENU
1) SNOW RATE SETUP
2) DESIGN TEMPS
3) SLAB SETUP
4) SYSTEM SETUP
5) TESTING
6) °C OR °F °F
TESTING
1) CONTROL INFO
2) FUNCTION TEST
3) RELAY 1
4) RELAY 2
5) RELAY 3
6) RELAY 4
ON
OFF
OFF
OFF
OFF
TESTING
1) CONTROL INFO
2) FUNCTION TEST
3) RELAY 1
4) RELAY 2
5) RELAY 3
6) RELAY 4
ON
OFF
OFF
OFF
OFF
TESTING
1) CONTROL INFO
2) FUNCTION TEST
3) RELAY 1
4) RELAY 2
5) RELAY 3
6) RELAY 4
ON
OFF
OFF
ON
OFF
SETUP MENU
1) SNOW RATE SETUP
2) DESIGN TEMPS
3) SLAB SETUP
4) SYSTEM SETUP
5) TESTING
6) °C OR °F °F
TESTING
1) CONTROL INFO
2) FUNCTION TEST
3) RELAY 1
4) RELAY 2
5) RELAY 3
6) RELAY 4
ON
OFF
OFF
OFF
OFF
TESTING
1) CONTROL INFO
2) FUNCTION TEST
3) RELAY 1
4) RELAY 2
5) RELAY 3
6) RELAY 4
ON
OFF
OFF
OFF
OFF
TESTING
1) CONTROL INFO
2) FUNCTION TEST
3) RELAY 1
4) RELAY 2
5) RELAY 3
6) RELAY 4
ON
OFF
OFF
ON
OFF
TESTING SETUP
Control Informaon
This seng will display processing informaon about the control.
Funcon Test
This seng will allow the user to pre-test the control during setup. It will set the outdoor temperature
to 10 °F and the system temperature to 70 °F so the system will test in warmer months.
Relay Test
These sengs will test each relay in the control in order to ensure correct operaon. The user is able
to test each relay individually. In order to test, select the desired relay by pressing ENTER. The relay
can be toggled on and o by pressing the ▼or ▲ buons.
Tesng Setup
This seng is used to test and view funconality of the control.

4516 112 Ave S.E. Calgary, Alberta • Tel: (403) 279 0020 • Fax: (403) 279 0747
www.tamashydronic.com Page 14
Tamas Hydronic Panels
Snow Melt Series
Modular Expansion Panels
Tamas Hydronics Modular Panels
The Tamas Modular Panel line contains a series of
expandable hydronic panels suited for a variety of
applicaons and building sizes.
The comprehensive system provides a versale method
of distribung heat to a multude of applicaons. Indoor/
outdoor reset controls are ulized to improve system
eciency and management. Specic panels allow for system
expansion, mulple boiler management , injecon mixing
and domesc hot water.
Available panels: Boiler, Staging, Expansion, Low
Temperature Injecon (Pump, Valve, TMV)

4516 112 Ave S.E. Calgary, Alberta • Tel: (403) 279 0020 • Fax: (403) 279 0747
www.tamashydronic.com Page 15
Tamas Hydronic Panels
Snow Melt Series
Limited Warranty
Limited Warranty
Tamas Hydronic Systems Inc. warrants each of its products to be free from defects in workmanship and materials under normal use and service for a
period of 24 months from date of purchase from a Tamas Hydronic Systems inc. authorized Dealer.
If the product proves to be defecve within the applicable warranty period, Tamas Hydronic Systems inc. on its sole discreon will repair or
replace said product. Replacement product may be new or refurbished of equivalent or beer specicaons, relave to the defecve product.
Replacement product need not be of idencal design or model. Any repair or replacement product pursuant to this warranty shall be warranted for
not less than 90 days from date of such repair, irrespecve of any earlier expiraon of original warranty period. When Tamas Hydronic Systems Inc.
Provides replacement, the defecve product becomes the property of Tamas Hydronic Systems Inc.
Warranty Service, within the applicable warranty period, may be obtained by contacng your nearest Tamas Hydronics Systems inc. oce via the
original Authorized Agent and requesng a Return Material Authorizaon Number (RMA #). Proof of purchase in the form a dated invoice/receipt
must be provided to expedite the issuance of a Factory RMA.
Aer an RMA number has been issued, the defecve product must be packaged securely in the original or other suitable shipping package to ensure
that it will not be damaged in transit. The RMA number must be visible on the outside of the package and a copy included inside the package. The
package must be mailed or otherwise shipped back to Tamas Hydronic Systems Inc. with all costs of mailing/shipping/insurance prepaid by the
warranty claimant.
Any package/s returned to Tamas Hydronic Systems Inc. without an approved and visible RMA number will be rejected and shipped back to
purchaser at purchaser’s expense. Tamas Hydronic Systems Inc. Reserves the right, if deemed necessary, to charge a reasonable levy for costs
incurred, addional to mailing or shipping costs.
Limitation of Warranties.
If the Tamas Hydronic Systems Inc. product does not operate as warranted above the purchasers sole remedy shall be, at Tamas Hydronic Systems
Inc.’ s opon, repair or replacement. The foregoing warranes and remedies are exclusive and in lieu of all other warranes, expressed or implied,
either in fact or by operaon of law, statutory or otherwise, including warranes of merchantability and tness for a parcular purpose/applicaon.
Tamas Hydronic Systems Inc. neither assumes nor authorizes any other person to assume for it any other liability in connecon with the sale,
installaon maintenance or use of Tamas Hydronic Systems Inc. products.
Tamas Hydronic Systems Inc. shall not be liable under this warranty; if its tesng and examinaon discloses that the alleged defect in the product
does not exist or was caused by the purchasers or third persons misuse, neglect, improper installaon or tesng, unauthorized aempts to repair or
any other cause beyond the range of intended use, or by accident, re, lightning or other hazard.
Limitation of Liability.
In no event will Tamas Hydronic Systems Inc. be liable for any damages, including loss of data, loss of prots, costs of cover or other incidental,
consequenal or indirect damages arising out of the installaon, maintenance, commissioning, performance, failure or interrupon of a Tamas
Hydronic Systems Inc. product, however caused and on any theory of liability. This limitaon will apply even if Tamas Hydronic Systems Inc. has
been advised of the possibility of such damage.
Local Law.
This limited warranty statement gives the purchaser specic legal rights. The purchaser may also have other rights which vary from state to state in
the United States, from Province to Province in Canada and from Country to Country elsewhere in the world.
To the extent this Limited Warranty Statement is inconsistent with local law, this statement shall be deemed modied to be consistent with such
local law. Under such local law, certain disclaimers and limitaons of this statement may not apply to the purchaser. For example, some states in
the United States, as well as some governments outside the United States (including Canadian Provinces), may:
Preclude the disclaimers and limitaons in this statement from liming the statutory rights of a consumer (e.g. United Kingdom);
Otherwise restrict the ability of a manufacturer to enforce such disclaimers or limitaons; or
Grant the purchaser addional warranty rights which the manufacturer cannot disclaim, or not allow limitaons on the duraon of implied
warranes.
Warranty

Custom, Reliable Hydronic Systems
Tamas Hydronic Systems Inc. Phone: 1 (403) 279 0020
4516 112 Avenue SE Fax: 1 (403) 279 0747
Calgary, Alberta T2C 2K2 info@tamashydronic.com
/TamasHydronicSystems
/TamasHydronic
/company/tamas-hydronic-systems
4516 112 Ave S.E. Calgary, Alberta • Tel: (403) 279 0020 • Fax: (403) 279 0747
www.tamashydronic.com
This manual suits for next models
7
Table of contents