
SET ALUE RECALL
While TX2 is running/ waiting for inputs, set value/
values can be recalled (viewed) without disturbing the
ti ing process.
Briefly press the button on the TX2 ti er.
1. If the configured ode is
or the display
will show the set value for one second.
2.
If the configured ode is or the display will
show
and its set value followed by and
its set value.
CONFIGURATION RECALL
While TX2 is running/ waiting for inputs pressing the
button for 3 seconds causes to display to show
the configuration setting of para eters 1 to 6 one
after the other.
CONFIGURATION
TX2 is a ultifunctional ti er. To ake it function in
the desired way it has to be configured.
Configuration can be done through the front panel
buttons.
To enter into the configuration ode.
1. Re ove power to the instru ent.
2. Keep the button pressed
3. Apply power.
4. Leave the button when the display shows .
5. Navigate the configuration para eters using
and buttons.
To change parameter value
6. Press the button to enter that para eter.
7. The display shows the value of that para eter.
8. Using and buttons change to the
desired value.
9. Using button exit that para eter.
10. Si ilarly other para eters can be changed.
To save the changes and exit the configuration
mode
11. Navigate using and buttons (to the
para eter) when the display shows .
12. Press the button.
13.
The TIMER is now updated with the new
configuration and is ready to be used.
Configuration Parameters
#
Name. Setting range for parameter
Seconds
Minutes
1
Ti e
Units Hours
9.99 When Time units is set
to seconds
9.59 When Time units is set
to Minutes or Hours.
99.9
2
Range
999
UP: Once the ti er starts
the display increases fro 0
to Set value.
3
Directio
n
DOWN: Once the ti er
starts the display decreases
fro Set value to 0.
On delay
Interval
Cyclic with ON ti e first.
4
Mode
Cyclic with OFF ti e first.
Reset by front panel Enable.
5
Front
Reset
Reset by front panel
Disable.
Output 2 follows Output 1.
Output 2 pulses on for
750 s when START input is
given.
6
Output
2
Output 2 is opposite off
Output 1.
Normal: To start a new
cycle a RESET input has to
be given.
7
Reset
Auto: A new cycle can be
started without first giving a
RESET signal.
Level: The START input can
be closed per anently and
the ti er will always read it
as start input present.
Gate: When
START
is open
the relay state does not
change but the time
counting stops. On ake
of START contact ti e
counting starts fro the last
ti e count.
8
Start
type
Edge: Ti ing starts on
application of START input
(Open to Close).
Exit
Config
On pressing
button
at this
para eter configuration is saved and
ti er goes into nor al operation.