Task Force Tips PRO/pak Installation instructions

©Copyright Task Force Tips LLC 2003-2020 1 LIU-030 August 24, 2020 Rev10
TASK FORCE TIPS LLC
MADE IN USA · tft.com
3701 Innovation Way, Valparaiso, IN 46383-9327 USA
800-348-2686 · 219-462-6161 · Fax 219-464-7155
INSTRUCTIONS FOR OPERATION, AND MAINTENANCE
PRO/pak®
Portable Multi-Purpose Foam System
WARNING
Understand manual before use. Operation of this device without understanding the manual and
receiving proper training is a misuse of this equipment. Obtain safety information at tft.com/serial-
number.
This equipment is intended for use by trained and qualified emergency services personnel for
firefighting. All personnel using this equipment shall have completed a course of education
approved by the Authority Having Jurisdiction (AHJ).
This instruction manual is intended to familiarize firefighters and maintenance personnel with the
operation, servicing, and safety procedures associated with this product. This manual should be
kept available to all operating and maintenance personnel.
k
a
p
/
O
R
Pk
a
p
/
O
R
P
PORTABLE MULTI PURPOSE FOAM SYSTEM
PATENT PENDING ó MODEL UM12
RATED FLOW
12 GPM at 100 PSI
45 L/MIN at 7.0 BAR
Minimum Operating Condition
7 GPM at 40 PSI
30 L/MIN at 3 BAR
Maximum Operating Condition
27 GPM at 500 PSI
100 L/MIN at 40 BAR
ADDITIVE SETTINGS
CLASS A RANGE: OFF, 0.1% TO 1.0% continuously adjustable
CLASS B RANGE: OFF, 1%, 3%, 6%

©Copyright Task Force Tips LLC 2003-2020 2 LIU-030 August 24, 2020 Rev10
TABLE OF CONTENTS
1.0 MEANING OF SAFETY SIGNAL WORDS
2.0 SAFETY
3.0 GENERAL INFORMATION
3.1 SPECIFICATIONS
3.2 PART IDENTIFICATION
3.3 LEFT OR RIGHT HAND OPERATION
3.4 DILUTION EQUIVALENTS
4.0 FLOW CHARACTERISTICS
5.0 FOAM SELECTION
5.1 USING FOAM
5.2 AGENT COMPATIBILITY
6.0 NOZZLE SELECTION
7.0 OPERATION
7.1 HOSE CONNECTION
7.2 FILLING THE TANK
7.3 CONNECTING DISCHARGE HOSE AND NOZZLE
7.4 SETTING CONCENTRATION
7.5 CONTROLLING FLOW
7.6 FOAM QUALITY
7.7 SHUT DOWN AFTER USE (FLUSHING)
7.8 STORAGE
8.0 WARRANTY
9.0 TROUBLESHOOTING
10.0 CLEAN UP AND MAINTENANCE
10.1 DRAIN HOLE
11.0 DRAWINGS AND PART LISTS
This Operator Manual is not intended as a substitute for proper training in the use of equipment as taught from credible
sources such as the National Fire Protection Association (NFPA), The International Fire Service Training Association (IFSTA),
or sources approved by the Authority Having Jurisdiction (AHJ).
Examples of recent publications:
NFPA 1145 - Guide for the Use of
Class A Foams in Fire Fighting
IFSTA Principles of
Foam Fire Fighting
DANGER
PERSONAL RESPONSIBILITY CODE
The member companies of FEMSA that provide emergency response
equipment and services want responders to know and understand the
following:
1. Fire¿ghting and Emergency Response are inherently dangerous activities
requiring proper training in their hazards and the use of extreme caution
at all times.
2. It is your responsibility to read and understand any user’s instructions,
including purpose and limitations, provided with any piece of equipment
you may be called upon to use.
3. It is your responsibility to know that you have been properly trained in
Fire¿ghting and /or Emergency Response and in the use, precautions, and
care of any equipment you may be called upon to use.
4. It is your responsibility to be in proper physical condition and to maintain
the personal skill level required to operate any equipment you may be
called upon to use.
5. It is your responsibility to know that your equipment is in operable
condition and has been maintained in accordance with the manufacturer’s
instructions.
6. Failure to follow these guidelines may result in death, burns or other
severe injury.
FEMSA
Fire and Emergency Manufacturers and Service Association
P.O. Box 147, Lynn¿eld, MA 01940 • www.FEMSA.org

©Copyright Task Force Tips LLC 2003-2020 3 LIU-030 August 24, 2020 Rev10
1.0 MEANING OF SAFETY SIGNAL WORDS
A safety related message is identified by a safety alert symbol and a signal word to indicate the level of risk involved with a particular
hazard. Per ANSI Z535.6, the definitions of the four signal words are as follows:
2.0 SAFETY
This portable decontamination system can be used in potentially dangerous situations. The following must be observed at all times:
3.0 GENERAL INFORMATION
The PRO/pak Portable Foam System is a very versatile eductor-type foam application appliance. It can be used with 0.1%-1% Class A
foam concentrates for wildland, rural and urban fire suppression on Class A fuels (wood, paper, combustible materials). On Class A
materials the PRO/pak is intended to be used for direct extinguishment, overhaul, and wetting of fuels. Some foam concentrates are
corrosive, we recommend using only Class A concentrates that have received USDA and USFS approval.
On Class B materials, the PRO/pak is primarily intended to be used for vapor suppression. It can be used with 1% and 3% AFFF Class
B concentrates on flammable liquids that do not contain alcohol. It can be used with 3% and 6% Alcohol Resistant AFFF Class B
concentrates on flammable liquids containing polar solvents. It can also be used with 3% X 6% or 6% Class B foam concentrates.
Whenever possible, back up the PRO/pak with additional water/foam capabilities for added safety.
The Pro/pak can be used on ignited liquid fuels, but its foam application rate is very limited. Based on NFPA 11 this unit should not be
used on ignited Class B fuels with an area greater than 120 square feet (10 x 12 feet) or 11 square meters. The PRO/pak should not be
used on burning Polar Solvents with an area greater than 60 square feet (6 x 10 feet) or 5.5 square meters.
The PRO/pak is designed for Class A and Class B foam concentrates, but it has been used with other concentrates for other uses. If you
intend to use the PRO/pak for liquids other than Class A and Class B concentrates and water, we urge you to contact the Task Force
Tips Engineering Department. The use of other liquids may void the warranty and subject the user to hazards not addressed in this
manual. The user assumes all risks for non-intended uses.
3.1 SPECIFICATIONS
Figure 3.1
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in death or serious
injury.
CAUTION CAUTION indicates a potentially hazardous situation which, if not avoided, could result in minor
or moderate injury.
NOTICE
NOTICE is used to address practices not related to physical injury.
DANGER
Lack of foam can place operator at risk of injury or death. Establish foam flow and adequate supply
of concentrate for the task before advancing into hazardous situations.
WARNING
Improper use of agent could result in death or serious injury, including damage to the eyes. To
reduce the risk of injury, avoid directing agent onto the faces of yourself and other personnel.
Always wear PPE, including eye protection, as directed by the AHJ.
WARNING
Improper use of foam or using the wrong type of foam can result in illness, injury, or damage to the
environment. Follow foam manufacturer’s instructions and fire service training as directed by the
AHJ.
US Units Metric Units
Tank Capacity (to bottom of fill port) 2.5 gal 9.5 liters
Nominal Flow (all nozzles) 12 gpm @ 100 psi 45 l/min @ 7.0 bar
Weight Empty 11.5 lb 5.2 kg
Weight Full 30.1 lb 13.6 kg
Length x Width x Height 13.5” x 10.75” x 17” 345mm x 275mm x 430mm
Operating Pressure Max/Min 500/40 psi 40/3 bar
Straight Stream Nozzle Reach 50 feet @ 100 psi 15 meters @ 7.0 bar
Low Expansion Nozzle Reach 37 feet @ 100 psi 11 meters @ 7.0 bar
Medium Expansion Nozzle Reach 9 feet @ 100 psi 3 meters @ 7.0 bar

©Copyright Task Force Tips LLC 2003-2020 4 LIU-030 August 24, 2020 Rev10
3.2 PART IDENTIFICATION
Figure 3.2
3.3 LEFT OR RIGHT HAND OPERATION
The Control Block and Valve Assembly can be mounted on the Tank for right or left hand operation. To switch hands, remove the
Shoulder Strap from the Pull Pins. Remove the Circle Cotters from the Pull Pins and remove the Pull Pins themselves. Pull the Control
Assembly straight up and out of the tank. Turn the Control Unit around and reinstall the Pull Pins, the Circle Cotters, and the Shoulder
Strap.
3.4 DILUTION EQUIVALENTS
Agents used in the PRO/pak are to be diluted according to the manufacturer’s specifications. The following chart describes percentages
and dilution ratios.
Table 3.4
Percentage ml/l Oz/gal or Ratio
0.23% 2.3 0.3 2 US teaspoons 1:427
0.39% 3.9 0.5 1 US tablespoon 1:256
0.50% 5.0 0.64 1-1/4 US tablespoons 1:200
0.78% 7.8 1 2 US tablespoons 1:128
1.0% 10 1.3 2-1/2 US tablespoons 1:100
1.6% 16 2 1/4 US cup 1:64
2.3% 23 3 1/3 US cup 1:43
3.1% 31 4 1/2 US cup 1:32
4.7% 43 6 3/4 US cup 1:21
6.3% 67 8 1 US cup 1:16
7.8% 78 10 1-1/4 US cup 1:13
KEY- Metering setting not compatible with PRO/pak
WARNING
Agent concentrates can be ineffective if not used at the correct concentration ratio. Ineffective
agents can increase the potential for injury or death. Ensure that the Percentage Knob is set to the
correct concentration ratio for the type of agent being used prior to flowing.
OUTLET HOSE
U-HS 2.7' HOSE
(82 cm)
(supplied)
or
U-HS6 6' HOSE / (1.8 m)
U-HS12 12' HOSE / (3.6 m)
U-HS25 25' HOSE / (7.5 m)
(optional)
LOW EXPANSION
NOZZLE
PIERCING NOZZLE (optional)
MEDIUM EXPANSION
NOZZLE
TWIST GRIP
FLOW CONTROL
PULL PIN
TANK
STRAIGHT STREAM
NOZZLE
PERCENTAGE KNOB
(TURN)
U-MX12
U-SS12
U-LX12
U-PN12

©Copyright Task Force Tips LLC 2003-2020 5 LIU-030 August 24, 2020 Rev10
4.0 FLOW CHARACTERISTICS
Figure 4.0A
Figure 4.0B
5.0 FOAM SELECTION
In any eductor type system the accuracy of the foam concentrate to water ratio will depend upon the viscosity (thickness) of the foam
concentrate. The more viscous, or thick, the foam concentrate, the greater the amount of energy required to draw the concentrate into
the eductor. The viscosity of most foam concentrates changes with temperature, with some thickening to a gel at temperatures of 40ºF
(4ºC).
The PRO/pak percentage knob has two sides, the green Class A side was calibrated for 20 Centipoise Class A foam concentrates and
the red, Class B, side was calibrated with National Foam’s Universal Gold® AFFF concentrate.
Actual foam concentrations may vary with changes in water flow, foam concentrate temperature, and viscosity. The user must verify that
the performance of the concentrate is suitable for the application. In all cases, follow the concentrate manufacturer’s recommendation.
WARNING
Agent concentrates can be ineffective if not used at the correct concentration ratio. Ineffective
agents can increase the potential for injury or death. Ensure that the Percentage Knob is set to the
correct concentration ratio for the type of agent being used prior to flowing.
0
0
FLOW (GPM)
PRO/pak FLOW CHARACTERISTICS (with valve fully open)
INLET PRESSURE (PSI)
201826 1614
12
104242622828
50
150
350
250
450
100
300
200
400
500 MAXIMUM OPERATING
PRESSURE = 500 PSI
MINIMUM OPERATING
PRESSURE = 40 PSI
0
0
FLOW (L/MIN)
50
40
30
10 6020 70 80 10090
2
6
14
10
18
4
12
8
16
22
20
24
26
28
30
PRO/pak FLOW CHARACTERISTICS (with valve fully open)
MAXIMUM OPERATING PRESSURE = 40 BAR
MINIMUM OPERATING PRESSURE = 3 BAR
INLET PRESSURE (BAR) 100
MINUTES TO USE 2-1/2 GALLONS OF
CONCENTRATE AT 12 GPM
PERCENT MINUTES
0.1 208
0.2 104
0.3 69
0.4 52
0.5 42
1 21
3 7
6 3.5
MINUTES TO USE 10 LITRES OF
CONCENTRATE AT 45 l/min
PERCENT MINUTES
0.1 208
0.2 104
0.3 69
0.4 52
0.5 42
1 21
3 7
6 3.5

©Copyright Task Force Tips LLC 2003-2020 6 LIU-030 August 24, 2020 Rev10
5.1 USING FOAM
It is recommended that the Class A foam used meets USDA Forest Service 5100-307A “Specification for Fire Suppressant Foam foe
Wildland Firefighting (Class A Foam)”, or NFPA 1150 “Foam Chemicals for Fires in Class A Fuels”.
5.2 AGENT COMPATIBILITY
WARNING
Improper use of foam or using the wrong type of foam can result in illness, injury, or damage to the
environment. Follow foam manufacturer’s instructions and fire service training as directed by the
AHJ.
WARNING
For Class B fires, lack of foam or interruption in the foam stream can cause a break in the foam
blanket and greatly increase the risk of injury or death. Follow procedures established by the AHJ
for the specific fuel and conditions.
DANGER
Mixing different types of agent concentrates or agents of the same type from different
manufacturers can cause the contents of the agent reservoir to gel and produce unpredictable
results, increasing risk of serious injury or death. To reduce the risk:
• Clean tank and agent passages thoroughly when changing agent types.
• Check agent manufacturer’s documentation for recommendations.
• Always identify the contents of the reservoir per the agent manufacturer’s Technical data Sheet.
NOTICE
Components of the PRO/pak may be subject to degradation, including corrosion, by harsh
chemicals such as sodium hypochlorite (Bleach), D-limonene, and other strong solvents. To reduce
the risk of equipment damage:
• Avoid long-term storage of agents that may damage the tank, lid, or other components.
• Empty and rinse the reservoir between use.
It is the responsibility of the end user to determine the chemical compatibility between the PRO/pak
and any solutions to be stored in it. Effects of corrosion by bleach and other disinfecting
concentrates are not covered under warranty.
NOTICE
Actual mix ratio may differ from label setting. Disinfecting concentrates have significantly lower
viscosity than firefighting foams resulting in stronger solutions. Mix ratio INCREASES at pressures
below 100 PSI (7bar), and DECREASES as pressure is increased above 100 PSI (7 bar). Verify
concentration is appropriate for the intended use.

©Copyright Task Force Tips LLC 2003-2020 7 LIU-030 August 24, 2020 Rev10
6.0 NOZZLE SELECTION
Straight Stream Nozzle - is for Class A foam solutions. Foam expansion will be negligible. It should be used where maximum reach or
penetration is desired.
Low Expansion Nozzle - can be used with either Class A or B foam solutions. Reach is slightly less than the smooth bore. It should be
used on Class B fires for extinguishment and Class A fuels to soak the fuel with a wet foam solution.
Medium Expansion Nozzle - produces the greatest expansion ratios. It should be used on Class B fuels for vapor suppression and
Class A fuels when a longer lasting insulating layer of drier foam is desired.
Figure 6.0A
Piercing Nozzle - is for use with Class A foam solutions in deep-seated fires. Foam expansion will be negligible. It can be used where
an application of solution is needed but the location is inaccessible. The piercing nozzle is not designed to pierce metal and other hard
objects. To use behind hard surfaces, punch a hole first.
Figure 6.0B
Figure 6.0C
Straight Stream
Low Expansion
Reach: 37 ft @ 100 psi
11 m @ 6.8 bar
Reach: 50 ft @ 100 psi
15 m @ 6.8 bar
Medium Expansion
Reach: 9 ft @ 100 psi
3 m @ 6.8 bar
Straight Stream Nozzle
U-SS12
Low Expansion Nozzle
U-LX12
Medium Expansion Nozzle
U-MX12
Piercing Nozzle (optional)
U-PN12
2.7' Hose / U-HS
(82 cm Hose)
6' Hose / U-HS6
(1.8 m Hose)
12' Hose / U-HS12
(3.6 m Hose)
25' Hose / U-HS25
(7.5 m Hose)
(optional)
k
a
p
/
O
R
Pk
a
p
/
O
R
P
PORTABLE MULTI PURPOSE FOAM SYSTEM
PATENTPENDING ó MODEL UM12

©Copyright Task Force Tips LLC 2003-2020 8 LIU-030 August 24, 2020 Rev10
7.0 OPERATION
Figure 7.0
7.1 HOSE CONNECTION
Attach inlet fire hose to the coupling on the inlet end of the PRO/pak. Larger hoses may be used with an adapter. For maximum
maneuverability, we recommend attaching 1” hose to the PRO/pak itself.
7.2 FILLING THE TANK
Unscrew the fill port lid by turning counterclockwise. Fill tank to bottom of fill port. Agent may seep out the vents if overfilled. Close the fill
port lid by turning clockwise.
7.3 CONNECTING DISCHARGE HOSE AND NOZZLE
The nozzle may be attached directly to the quick-connect fitting on the control block or to the end of the outlet hose which is then
attached to the control block.
1. Align the marks on the quick-connect male fitting with the marks on the female fitting and push the two pieces together.
2. Twist the nozzle or hose one quarter turn to the right to latch the quick-connect fitting.
3. To remove fan nozzle, remove set screw.
4. Hose lengths available. TFT part U-HS6, U-HS12, and U-HS25.
7.4 SETTING CONCENTRATION
Remove the nut on top of the percentage knob and lift the knob to select the proper foam concentrate type. Replace the knob nut. Turn
the knob to the desired concentrate percentage. The percentage knob may be turned to the OFF position for water only use. Be sure to
use the foam manufacturer’s recommended concentrate ratio.
7.5 CONTROLLING FLOW
Pressurize the hose line. Turn the flow control valve to start water flowing through the PRO/pak. Flow may be reduced by partially
closing the control valve.
CAUTION The PRO/pak’s eductor will not function if the back pressure from the outlet hose or nozzle is too
high. To reduce the risk of injury or death due to a non-functioning unit:
• Never use hose longer than the 25’ (7.5m) U-HS25 optional hose.
• Never add additional hose, or use other manufacturer’s hose assemblies and nozzles.
CAUTION There is no check valve in the PRO/pak eductor system. Installing a shut off valve between the
PRO/pak and the fan nozzle can cause the agent tank to fill with water and dilute the agent
concentrate resulting in ineffective agent. Never install a shut off valve between the PRO/pak and
the fan nozzle.
k
a
p
/
O
R
Pk
a
p
/
O
R
P
PORTABLE MULTI PURPOSE FOAM SYSTEM
PATENT PENDING ó MODEL UM12
PUSH & TURN
TO ATTACH
CONTROL
FLOW
FILL
2.5 GAL
SELECTOR
WHEEL
CONNECT
SUPPLY
ADJUST %
START UP PROCEDURE
To Make Foam - Connect water supply. Attach the desired nozzle to
the Quick-Connect. Turn the Percentage Knob to the desired
percentage. Twist the Valve Handle to start water flow.

©Copyright Task Force Tips LLC 2003-2020 9 LIU-030 August 24, 2020 Rev10
7.6 FOAM QUALITY
Foam quality with the Medium Expansion Nozzle will depend upon the velocity of the foam solution exiting the nozzle. When pumping
high pressures to the PRO/pak, it may be necessary to partially close the flow control valve to make good foam with the Medium
Expansion Nozzle. If the foam exiting the Medium Expansion Nozzle is not a coherent continuous stream, close the flow control valve
slightly until the foam becomes a coherent continuous rope-like stream.
TO SHUT DOWN
To prevent concentrate from drying in the agent passages the following
is recommended. While still connected to water supply, remove Circle
Cotters and Pull Pins. Remove Control Unit from tank. Attach the Cap
directly to the Quick-Connect on the Control Block. Turn the valve
halfway on until the discharge is agent free. This will backflush a small
amount of water through the agent passage. Rotate the Percentage
Knob back and forth to make sure all agent passages are flushed.
TO CLEAN OUT IF PLUGGED
Remove screw #2, spring #3, and knob #4. Inspect the underside
of the knob. Make sure the agent passages are clear. Do not
scratch the flat face of the knob. Inspect the 2 holes in the top of
the Control Block #5. If they are plugged, pull pins #1, remove
Block Assembly and clean out Pickup Tube and holes.
Figure 7.6A
INSTALL CAP
ROTATE
OPEN SLIGHTLY
Figure 7.6B
PULL
CLEAN
UNSCREW
#1
#2
#3
#4
#5

©Copyright Task Force Tips LLC 2003-2020 10 LIU-030 August 24, 2020 Rev10
7.7 SHUT DOWN AFTER USE (FLUSHING)
PRO/pak should be flushed with water after each use to prevent agent concentrate from drying out inside of the Control Block and
Percentage Knob.
1. Reduce pump pressure to 100 psi or less.
2. Remove the nozzle and/or hose from the quick-connect on the front of the Control Block.
3. Remove the Circle Cotters and pull out the two Pull Pins that hold the Control Unit to the tank.
4. Pull straight up to remove the Control Unit and Pickup Tube from the tank.
5. Make sure the Percentage Knob is NOT in the RINSE position.
6. Install the Cap on the outlet of the Control Block.
7. Turn the Flow Control valve until a trickle of clean water is flowing from the end of the Pickup Tube.
8. Turn the Percentage Knob back and forth to make sure all agent passages are flushed.
9. Shut off water and reinstall the Control Unit on the tank and insert the Pull Pins and circle cotters.
10. Remove the Cap.
The exterior of the PRO/pak can be washed off with the hose or straight stream nozzle, with the percentage knob in the OFF position.
7.8 STORAGE
The PRO/pak can be stored with agent concentrate in it. Make sure the
control block and valve assembly is mounted on the tank and the fill
port is securely closed to prevent evaporation. Storage in the upright
position is recommended to avoid agent leaking when the PRO/pak is
not in use.
Figure 7.8

©Copyright Task Force Tips LLC 2003-2020 11 LIU-030 August 24, 2020 Rev10
8.0 WARRANTY
Task Force Tips LLC, 3701 Innovation Way, Valparaiso, Indiana 46383-9327 USA (“TFT”) warrants to the original purchaser of its
products (“equipment”), and to anyone to whom it is transferred, that the equipment shall be free from defects in material and
workmanship during the five (5) year period from the date of purchase. TFT’s obligation under this warranty is specifically limited to
replacing or repairing the equipment (or its parts) which are shown by TFT’s examination to be in a defective condition attributable to
TFT. To qualify for this limited warranty, the claimant must return the equipment to TFT, at 3701 Innovation Way, Valparaiso, Indiana
46383-9327 USA, within a reasonable time after discovery of the defect. TFT will examine the equipment. If TFT determines that there is
a defect attributable to it, TFT will correct the problem within a reasonable time. If the equipment is covered by this limited warranty, TFT
will assume the expenses of repair.
If any defect attributable to TFT under this limited warranty cannot be reasonably cured by repair or replacement, TFT may elect to
refund the purchase price of the equipment, less reasonable depreciation, in complete discharge of its obligations under this limited
warranty. If TFT makes this election, claimant shall return the equipment to TFT free and clear of any liens and encumbrances.
This is a limited warranty. The original purchaser of the equipment, any person to whom it is transferred, and any person who is an
intended or unintended beneficiary of the equipment, shall not be entitled to recover from TFT any consequential or incidental damages
for injury to person and/or property resulting from any defective equipment manufactured or assembled by TFT.
It is agreed and understood that the price stated for the equipment is in part consideration for limiting TFT’s liability. Some states do not
allow the exclusion or limitation of incidental or consequential damages, so the above may not apply to you.
TFT shall have no obligation under this limited warranty if the equipment is, or has been, misused or neglected (including failure to
provide reasonable maintenance) or if there have been accidents to the equipment or if it has been repaired or altered by someone else.
THIS IS A LIMITED EXPRESS WARRANTY ONLY. TFT EXPRESSLY DISCLAIMS WITH RESPECT TO THE EQUIPMENT ALL
IMPLIED WARRANTIES OF MERCHANTABILITY AND ALL IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE.
THERE IS NO WARRANTY OF ANY NATURE MADE BY TFT BEYOND THAT STATED IN THIS DOCUMENT.
This limited warranty gives you specific legal rights, and you may also have other rights which vary from state to state.

©Copyright Task Force Tips LLC 2003-2020 12 LIU-030 August 24, 2020 Rev10
TASK FORCE TIPS LLC
MADE IN USA · tft.com
3701 Innovation Way, Valparaiso, IN 46383-9327 USA
800-348-2686 · 219-462-6161 · Fax 219-464-7155
9.0 TROUBLESHOOTING
Table 9.0
10.0 CLEAN UP AND MAINTENANCE
Turn the percentage knob to the RINSE position. Use the hose, or
hose and nozzle, to rinse off the PRO/pak. Reset percentage knob to
proper percentage when finished. For years of service, periodically
inspect your PRO/pak. Make sure the hose and fan nozzle are in place.
Look for debris in the bottom of the tank and flush if necessary.
10.1 DRAIN HOLE
If the PRO/pak is often used for different agent concentrates, it may be
helpful to install a drain to aid in emptying the tank. Drill and tap the left
front ear of the tank and install a ¼” NPT Pipe plug. Plastic or Brass
preferred.
11.0 DRAWINGS AND PART LISTS
Exploded View Drawings and Part Lists available at tft.com/serial-number.
SYMPTOM POSSIBLE CAUSE REMEDY
PRO/pak will not make foam Out of agent Refill tank
Percentage knob is in RINSE Select desired percentage
Percentage know is plugged Remove screw on Percentage Knob,
inspect and clean holes in top of
control block and agent passages in
bottom of Percentage Knob
Non-standard outlet hose being used
which is too long or too small in
diameter
Order other hose option TFT part
U-HS, U-HS6 or U-HS25b
Foam tank is nearly empty Refill tank
Foam delivery is intermittent PRO/pak is tilted Keep twist grip horizontal
Air vents are plugged Make sure that the small black rubber
valve on the inside of the agent tank
lid is not stuck down with dried agent
concentrate
Poor quality foam Debris in nozzle Inspect nozzle, look for plugged holes
Debris under knob Unscrew knob, inspect and clean
Foam solution velocity too high Partially close flow control
Foam gets thick when cold Select a different foam
Figure 10.0
DRILL 7/16" HOLE
TAP 1/4" NPT
LEFT FRONT ONLY!
Other manuals for PRO/pak
1
Table of contents
Other Task Force Tips Safety Equipment manuals
Popular Safety Equipment manuals by other brands

Guardian Fall Protection
Guardian Fall Protection Halo Web SRL instruction manual

ABS Safety
ABS Safety SG2-FL-ANSCHLUSS-K installation manual

Respirex
Respirex CHEMPROTEX 300 SPLASHMASTER User information

LintAlert
LintAlert ALRT31 installation manual

DBI SALA
DBI SALA ROLLGLISS R550 User instruction manual

Zero
Zero HTP1679 instruction manual