FireFlex Systems Inc. TOTALPAC 3 FIRECYCLE III Installation guide

FM-076A-0-12A
Advanced Integrated Fire Protection System
TOTALPAC®3
Owner's Operation
and
Maintenance Manual
DELUGE SYSTEM
FIRECYCLE®III RELEASE

Page ii TOTALPAC®3
Integrated Fire Protection System
OWNER'S OPERATION &MAINTENANCE MANUAL
FM-076A-0-12A
Copyright © 2020 FIREFLEX Systems Inc.
All Rights Reserved
Reproduction or use, without express written permission from FIREFLEX Systems Inc, of any portion of this manual is prohibited.
While all reasonable efforts have been taken in the preparation of this manual to assure its accuracy, FIREFLEX Systems Inc
assumes no liability resulting from any errors or omissions in this manual, or from the use of the information contained herein.
TOTALPAC ®is a registered trademark of FIREFLEX Systems Inc.
FIREFLEX Systems Inc. reserves the right to make changes to this manual and the data sheets herewith at any time, without prior
notification.

TOTALPAC®3Page iii
Integrated Fire Protection System
OWNER'S OPERATION &MAINTENANCE MANUAL
FM-076A-0-12A
Table of Contents
Deluge System - FIRECYCLE®III Release
General Section ..........................................................................................................Section A
1- General description
2- Listings and approvals
3- Applicable standards
4- Environment
5- Features
6- Configuration description
7- System release
Mechanical Section...................................................................................................................... Section B
1- Installation, operation & maintenance instructions
1.1 Installation
1.2 Preliminary inspection before placing the system in service
1.3 Placing the system in service
1.4 System operation
1.5 Emergency instructions
1.6 Placing the system back in service after operation
1.7 Inspections & tests
1.8 Maintenance
2- System trim
2.1 Normal condition
Trim Options.................................................................................................................................Section C
1- Shut-off valve & sight glass
2- Fire department connection
3- Semi and full flanged option
4- OSHPD seismic option
N/A.................................................................................................................................................Section D
Control Section.............................................................................................................................Section E
1- Self-contained unit with integrated release control panel
1.1 Product description
1.2 Self-contained unit with Viking VFR-400 release control panel
1.3 Technical data
1.4 Visual indicators
1.5 Control buttons
1.6 Time & date setting
2- Remotely controlled unit without release control panel
2.1 Product description
2.2 Technical data
Electrical Section..........................................................................................................................Section F
1- Self-contained configurations
2- Optional modules
3- Remotely controlled configuration

Page iv TOTALPAC®3
Integrated Fire Protection System
OWNER'S OPERATION &MAINTENANCE MANUAL
FM-076A-0-12A
Dimensional Data & Cabinet.......................................................................................................Section G
1- Cabinet unit
2- Skid mounted unit
Limited Warranty..........................................................................................................................Section H

TOTALPAC®3FIRECYCLE®III Page 1 of 2
Integrated Fire Protection System
A
General Section - Deluge System - FIRECYCLE®III Release
FM-076A-0-32A
1- General description
This TOTALPAC®3FIRECYCLE ®III integrated fire protection
system by FIREFLEX Systems Inc. consists of a cycling
deluge system trim totally pre-assembled, pre-wired and
factory tested. All electrical and mechanical components
of the system are contained in one single unit.
Note:Skid units include the trim components only and must
be wired by the installing contractor.
The only connections required for installation are the water
supply inlet, the water discharge outlet, the main drain, the
FIRECYCLE®detection network, the electrical trouble,
supervisory and alarm connections, as well as the AC
power line for the release control panel. The discharge
outlet is connected to a fixed piping network. Water is the
extinguishing agent.
Deluge system with FIRECYCLE®III release uses open type
sprinklers and/or spray nozzles on the system piping
network. The FIRECYCLE®rate compensated temperature
detector on detection network is installed in parallel with
the system piping network and is designed to totally flood
an area with pressurized water. Detection system gives
an alarm signal when it operate.
Deluge system is designed so the flow control valve will
open when a FIRECYCLE®detector on the detection
network activates. When the flow control valve opens,
water will flow into the system piping network and out of all
open type sprinklers and/or spray nozzles.
The TOTALPAC®3FIRECYCLE®III deluge system allows the
discharge cycle to stop after a preset delay when all
FIRECYCLE®detectors had returned to their normal
condition.
Note: Every TOTALPAC®3FIRECYCLE®III unit is identified
with its unique serial number. This number is located on
an adhesive label inside the main door panel and is used
to maintain a record in our computerized data base. Have
this serial number handy when calling for information on
your unit (format is TOT3#### or TOTS#### for skid
units).
2- Listings and approvals
In addition to being fabricated under tight ISO-9001
manufacturing and quality control procedures, your
TOTALPAC®3FIRECYCLE®III unit has also been tested and
approved by recognized laboratories.
Here is the list of Listings & Approvals it meets:
- Underwriters Laboratories Inc. (UL): Deluge TOTALPAC®3
systems are UL Listed under "Special System Water
Control Valves - Assembled Units, category
# VKYL.EX4641" and "Assembled Units Certified for
Canada, Category # VKYL7.EX4641 (c-UL)".
- Factory Mutual Research <FM>: Deluge TOTALPAC®3
systems are FM Approved under the heading: "Automatic
Water Control Valves" when installed with specific
components.
- OSHPD pre-approval OSP-0341-10 (optional).
WARNING Any unauthorized modification or addition made
on-site to a factory built Listed unit will void this Listing.
Such modifications or additions may void the unit's
warranty as well. Consult your nearest FIREFLEX Systems
authorized distributor before proceeding with such
modifications or additions.
3- Applicable standards
The TOTALPAC®3FIRECYCLE®III complies with the
following standards:
- NFPA-13 Sprinkler Systems
- NFPA-15 Water Spray Fixed Systems
- NFPA-16 Foam-Water Sprinkler and Foam-Water Spray
Systems
- NFPA-72 Fire Alarm Systems
Before installation, the contractor installing the unit shall
also be familiar with the following documents and
standards:
- Applicable Local & State Building Codes
- Any additional requirements of the Local Authority Having
Jurisdiction
4- Environment
TOTALPAC®3FIRECYCLE®III unit shall be installed in a dry
and clean location. Verify that all equipment is properly
heated and protected to prevent freezing and physical
damage. Refer to section E CONTROL SECTION for
environment data.
The unit and its components must be kept free of foreign
matter, freezing conditions, corrosive atmospheres,
contaminated water supplies, and any condition that could
impair its operation or damage the components.
The frequency of the inspections and maintenance will
vary depending on these environmental conditions as well
as the condition of the air supply to the system. The owner
is responsible for maintaining the fire protection system
and devices in proper operating condition. Refer to
section B MECHANICAL SECTION for maintenance
instructions.

Page 2 of 2 TOTALPAC ®3 FIRECYCLE ® III
A
Integrated Fire Protection System
General Section - Deluge System - FIRECYCLE ® III Release
FM-076A-0-32A
5- Features
The TOTALPAC ®3 FIRECYCLE ® III unit is superior to many
other products which are actually available on the fire
protection market. It is manufactured by FIREFLEX
Systems Inc. which has developed and introduced the
concept of integrated fire protection systems.
Main features are:
Trouble free design for safe and easy application
Available in 6 sizes from 1½" (40 mm) to 8" (200 mm)
diameter
Uses the Viking flow control valve
Unit is available either with or without integrated release
control panel
Skid version available
Compact, aesthetic and easy to move
User-friendly standardized owner's manual with every
unit
Unique serial number on every unit
Uses only c-UL-us Listed and FM Approved components
Designed in accordance with NFPA Standards
Trim is fully assembled and tested at the factory
All trims are galvanized steel, Listed and Approved for
250 PSI (1724 kPa) service maximum
Quick connections to water supply and drain on both
sides, and sprinkler riser on top of unit, all available with
grooved end or flanged fittings
No open drain cup inside unit
Sturdy 14 gauge steel cabinet or skid, painted fire red
with oven baked polyester powder on phosphate base
Textured rust proof finish
Neoprene gasket on all doors to eliminate vibrations
Separate unlocked access hatch to emergency manual
release
Key-alike locks on all cabinet doors
Manufactured under ISO-9001 quality control procedures
Cyclic discharge operation
6- Configuration description
TOTALPAC ®3 FIRECYCLE ® III deluge system is built around
the Viking trim using straight through flow control valve
model J-1 (model J-2 is the Halar ® coated version for use
in corrosive environments).
The valve is rated up to a maximum of 250 PSI WWP
(1724 kPa) and is available in the following diameters:
1½" (40 mm) 3" (80 mm) 6" (150 mm)
2" (50 mm) 4" (100 mm) 8" (200 mm)
TOTALPAC ®3 FIRECYCLE ® III deluge system is supplied with
groove/groove flow control valve. Unit with flange/flange
flow control valve is also available on request.
6.1 Deluge system
The deluge system uses the Viking flow control valve
which opens when a FIRECYCLE ® detector from the
detection network activates, or anytime the handle of the
emergency release valve is pulled.
7- System release
7.1 FIRECYCLE ® III release
Deluge system with FIRECYCLE ® release requires an
electric detection network equipped with FIRECYCLE ®
detectors. Release trim for the flow control valve requires
a normally closed solenoid valve controlled by an approved
releasing control panel (if provided with this system, see
section E CONTROLS SECTION and VFR-400 manual for
details).
In fire condition, the activation of a FIRECYCLE ® detector on
the detection network is required to energize the solenoid
valve, causing the flow control valve to open. Water will
flow from the deluge system through open type sprinklers
and/or spray nozzles.
The fire status is sensed by the FIRECYCLE ® detectors.
When both FIRECYCLE ® detectors had returned to their
normal state, a soak timer cycle starts. At the end of the
soak timer, if the detection condition is still normal, the
normally closed solenoid valve is de-energized, causing
the flow control valve to close, allowing the water flow to
stop automatically.
Should the fire rekindle, FIRECYCLE ® detectors will be
reactivated, and the discharge sequence will be initiated
again. This feature - unique to the TOTALPAC ®3
FIRECYCLE ® III deluge system - will repeat as long as
power is available to the releasing control panel, helping to
minimize water usage or damage, and reduce the danger
of pollution to surrounding areas.

TOTALPAC ®3 FIRECYCLE ® III Page 1 of 8
Integrated Fire Protection System B
Mechanical Section - Deluge System - FIRECYCLE ® III Release
FM-076A-0-52A
1- Installation, operation & maintenance
instructions
Note: Numbers indicated between brackets refer to figure 1
DETAILED SYSTEM TRIM SCHEMATICS from this section.
1.1 Installation
1. Conform to local municipal or other codes regarding
installations of fire protection systems.
2. Install the TOTALPAC ®3 FIRECYCLE ® III unit and connect
the system according to instruction manual and
technical data supplied.
IMPORTANT ! The cabinet must be firmly anchored to the
floor using all four (4) anchoring holes (see section G
CABINET).
Note: The drain collector shall be connected to an open
drain. Do not restrict or reduce drain piping.
3. Install the system piping network in accordance with
applicable standards.
4. Connect supervisory and alarm signals according to
electrical schematics and if applicable, all FIRECYCLE ®
detection and signaling circuits (see section F
ELECTRICAL).
5. If applicable, connect the AC power to the release
control panel on a separate breaker in the electric
distribution panel (see section F ELECTRICAL).
Notes:
AC power connections must be made by a qualified
installer according to national standards and equipment
specifications.
Do not apply AC power to the equipment yet.
6. Perform preliminary inspection prior to put system in
service (see paragraph 1.2 of the current section).
7. Place the system in service (see paragraph 1.3 of the
current section).
8. Perform the annual inspection sequence (see
paragraph 1.8 of the current section) and test each
detection device and alarm unit.
9. If the system does not operate as it should, make the
necessary corrections according to manuals issued or
consult your distributor or FIREFLEX Systems Inc.
10. Make sure that building owner or a delegated
representative has received instructions regarding the
operation of the system.
WARNING ! TOTALPAC ®3 FIRECYCLE ® III unit must be
installed in an area not subject to freezing temperatures or
physical damage.
1.2 Preliminary inspection before placing the system in
service
1. Open door to mechanical section.
a) Main water supply valve (D1) must be CLOSED.
b) Priming valve (B1) must be CLOSED.
c) Flow test valve (B6) and main drain valve (D3) must
be CLOSED.
d) Alarm test valve (B5) must be CLOSED.
e) Gauges (B11 and B12) should show 0 PSI (0 kPa).
f) If applicable, the shut-off valve (D4) must be OPEN.
2. OPEN the manual emergency release valve (B10) and
make sure the flow control valve (A1) is tripped.
3. Using the built-in contractor's hydrostatic test ports (see
figure 1 of this section), fill system piping network with
water and maintain pressure as per NFPA-13
requirements.
WARNING ! Do not subject the pressure gauges and
pressure transducer to hydrostatic pressure above 250 PSI
(1724 kPA). Close gauge valves before proceeding with
hydrostatic test.
4. Correct leaks if any before completing test.
5. Verify that main water supply valve (D1) is still CLOSED.
6. OPEN main drain valve (D3) to completely drain the
system piping network.
7. If applicable, apply AC power to the release control
panel.
8. If applicable, connect the batteries to the release control
panel. Observe battery size and polarity.
For battery capacity calculations, see the VIKING VFR-400
INSTALLATION, OPERATION AND INSTRUCTION MANUAL
provided with the TOTALPAC ®3 FIRECYCLE ® III unit.
Note: Batteries shall be installed with the release control
panel at hanged position. Battery compartment should
always stay closed while rotating the release control panel.
9. Reset the release control panel and silence the alarms
(see section E CONTROLS).

Page 2 of 8TOTALPAC®3FIRECYCLE®III
B
Integrated Fire Protection System
Mechanical Section - Deluge System - FIRECYCLE
®
III Release
FM-076A-0-52A
1.3 Placing the system in service
1. Verify that the main water supply valve (D1) is CLOSED.
Verify that the system has been properly drained.
2. Verify that all system piping auxiliary drain valves are
CLOSED.
3. CLOSE main drain valve (D3). Verify that the manual
emergency release valve (B10) is CLOSED.
4. OPEN priming valve (B1).
5. Reset the release control panel (see section E
CONTROLS). Solenoid valve (F1) should CLOSE. Flow
from solenoid valve to drain should stop. Verify that the
pressure indicated at the priming pressure gauge (B11)
is equal to, or greater than the pressure indicated at the
water supply pressure gauge (B12).
6. OPEN flow test valve (B6). PARTIALLY OPEN main water
supply valve (D1).
7. When full flow develops from the flow test valve (B6),
CLOSE the flow test valve. Verify there is no flow from
drip check valve (B7) when the plunger is pushed.
8. FULLY OPEN the main water supply valve (D1).
9. Verify that the alarm test valve (B5) is CLOSED and that
all other valves are in their "normal" operating position
(see paragraph 2.1 NORMAL CONDITION of the current
section).
10. Reset the release control panel (see section E
CONTROLS).
11. Check and repair all leaks.
12. On new installation, system that has been placed out of
service, or where new equipment has been installed,
trip test the system to verify that all equipment functions
properly (see paragraph 1.7.2 FULL FLOW TRIP TEST of
the current section).
13. Notify the AUTHORITY HAVING JURISDICTION, remote
station alarm monitors, and those in the affected area
that the system is in service.
Note: When a valve has been removed from service and is
subject to freezing or will be out of service for an extended
period of time, all water must be removed from the priming
chamber, trim piping, water supply piping and any other
trapped areas.
1.4 System Operation
1.4.1 In the SET condition
System water supply pressure enters the priming chamber
of the flow control valve (A1) through the priming line which
includes a normally open priming valve (B1), strainer (B2),
restricted orifice (B3) and spring loaded check valve (B4).
Water pressure is trapped in the priming chamber of the
flow control valve (A1) by a spring loaded check
valve (B4), normally closed solenoid valve (F1), normally
open solenoid valve (F2), PORV (B9) (pressure operated
relief valve) and manual emergency release valve (B10).
The pressure in the priming chamber holds the flow control
valve clapper closed, keeping the outlet chamber and
system piping dry.
1.4.2 In a fire condition
When a FIRECYCLE ®detector is activated, the release
control panel activates an alarm and energizes both the
normally closed solenoid valve (F1) and normally open
solenoid valve (F2).
Pressure from the priming chamber of the flow control
valve (A1) is released to the open drain manifold faster
than it is supplied through the restricted orifice (B3). The
flow control valve clapper opens to allow water to flow into
the piping network and alarm devices, causing water flow
alarms connected to the alarm pressure switch (C1) and
the optional water motor alarm (C2) to activate. The
PORV (B9) is pressurized, purging the priming chamber
pressure. Water will flow from all open sprinklers/spray
nozzle on the system piping network.
Note: If the detection system operates due to mechanical
damage or malfunction, the flow control valve (A1) will
open. Alarm devices (C1 and optional C2) will operate.
Water will flow from the system piping network and flood
the protected area.
1.4.3Cycling discharge stop
Water discharges until all FIRECYCLE®detectors have reset
(cooled below their set point). The release control panel
then activates a soak timer, allowing the system to flow
water for a preset period of time (soak timer).
When the soak timer has elapsed, the release control
panel de-energizes the normally closed solenoid
valve (F1), allowing it to close. The normally open
solenoid (F2) remains energized closed.It rebuilds
pressure in the priming chamber of the flow control
valve (A1), allowing it to close and stop discharge.
Should a FIRECYCLE®detector go into alarm, the release
control panel energizes once again the normally closed
solenoid valve (F1), and the entire discharge cycle repeats.

TOTALPAC®3FIRECYCLE®III Page 3 of 8
Integrated Fire Protection System
B
Mechanical Section - Deluge System - FIRECYCLE
®
III Release
FM-076A-0-52A
1.4.4Manual operation
Anytime the handle of the manual emergency release
valve (B10) is triggered, pressure is released from the
priming chamber of the flow control valve (A1) causing
flow control valve to open. Water will flow into the system
piping network and alarm devices (C1 and optional C2) will
operate.Water will flow from all open sprinklers/spray
nozzle on the system piping network.The PORV (B9) will
keep the flow control valve (A1) open.
1.4.5 Fail-safe condition
In case of AC power loss following a cycling discharge
stop, if the main water supply valve (D1) is still open while
the batteries have reached their cycle end, the normally
open solenoid valve (F2) will be de-energized, causing the
flow control valve (A1) to reopen with the help of the
PORV (B9).
1.5 Emergency instructions
To take system out of service
WARNING ! Placing a control valve or detection system out
of service may eliminate the fire protection capabilities of
the system. Prior to proceeding, notify all local
AUTHORITIES HAVING JURISDICTION. Consideration should
be given to employ a fire patrol in the affected areas.
After a fire, verify that the fire is OUT and that placing the
system out of service has been authorized by the
appropriate local AUTHORITY HAVING JURISDICTION.
Sprinklers piping that have been subjected to a fire must
be returned to service as soon as possible. The entire
system must be inspected for damage, and repaired or
replaced as necessary.
1. CLOSE main water supply valve (D1).
2. OPEN main drain valve (D3).
3. If applicable, silence audible devices (see section E
CONTROLS).
Note: Electric alarms controlled by a pressure switch
installed at the ¾"-NPT (20mm) connection (C2) for a non-
interruptible alarm signal cannot be shut-off until the flow
control valve (A1) is reset or taken out of service.
4. OPEN flow test valve (B6).
5. CLOSE priming valve (B1).
6. Replace any detector that have been damaged.
7. Replace any automatic sprinkler that have opened,
been damaged or exposed to fire conditions.
8. Return the system to service as soon as possible (see
paragraph 1.6 PLACING THE SYSTEM BACK IN SERVICE
AFTER OPERATION of the current section).
9. Perform all recommended maintenance procedures
(see paragraph 1.8 MAINTENANCE in the current section).
Note: When a system has been removed from service and
is subject to freezing or will be out of service for an
extended period of time, all water must be removed from
the priming chamber, trim piping, water supply piping and
any other trapped areas.

Page 4 of 8TOTALPAC®3FIRECYCLE®III
B
Integrated Fire Protection System
Mechanical Section - Deluge System - FIRECYCLE
®
III Release
FM-076A-0-52A
1.6 Placing the system back in service after operation
1. Verify that the system has been properly drained.
Verify that all system piping auxiliary drain valves are
CLOSED.
2. Verify that the main water supply valve (D1) is CLOSED,
and that the manual emergency release valve (B10) is
CLOSED. CLOSE main drain valve (D3).
3. OPEN priming valve (B1).
4. Reset the release control panel (see section E
CONTROLS). Solenoid valve (F1) should CLOSE. Flow
from solenoid valve to drain should stop. Verify that the
pressure indicated at the priming pressure gauge (B11)
is equal to, or greater than the pressure indicated at the
water supply pressure gauge (B12).
5. OPEN flow test valve (B6). PARTIALLY OPEN main water
supply valve (D1).
Note: Do not open main water supply valve (D1) until
gauge (B11) shows stabilized pressure.
6. When full flow develops from the flow test valve (B6),
CLOSE the flow test valve. Verify there is no flow from
drip check valve (B7) when the plunger is pushed.
7. FULLY OPEN the main water supply valve (D1).
8. Verify that the alarm test valve (B5) is CLOSED and that
all other valves are in their "normal" operating position
(see paragraph 2.1 NORMAL CONDITION of the current
section).
9. Reset the release control panel (see section E
CONTROLS).
10. Check and repair all leaks.
11. Notify the local AUTHORITY HAVING JURISDICTION, remote
station alarm monitors, and those in the affected area
that the system is back in service.
1.7 Inspections and tests
NOTICE:The owner is responsible for maintaining the fire
protection system and devices in proper operating
condition.
It is imperative that the system be inspected and tested on
a regular basis in accordance with NFPA-25. Refer to
Inspections and Tests recommended in Viking technical
data describing individual components of the deluge
system used.
The frequency of the inspections may vary due to
contaminated or corrosive water supply or corrosive
atmospheres. For minimum maintenance and inspection
requirements, refer to NFPA-25. In addition, the
AUTHORITY HAVING JURISDICTION may have additional
maintenance, testing, and inspection requirements that
must be followed.
WARNING ! Any system maintenance that involves placing
a control valve or detection system out of service may
eliminate the fire protection capabilities of that system.
Prior to proceeding any testing, notify all local AUTHORITIES
HAVING JURISDICTION. Consideration should be given to
employment of a fire patrol in the affected areas.

TOTALPAC®3FIRECYCLE®III Page 5 of 8
Integrated Fire Protection System
B
Mechanical Section - Deluge System - FIRECYCLE
®
III Release
FM-076A-0-52A
1.7.1Full flow trip test
Performance of a full flow trip test is recommended
annually during warm weather. Consider coordinating this
test with operation testing of the releasing devices.
Caution ! Performance of this test will cause the flow
control valve (A1) to open and the water to flow through all
open sprinklers/spray nozzle from the system piping
network.If it is not required to have water flow from the
system piping network, use the shut-off valve (if
applicable) (see paragraph 1.7.3 OPERATION OF THE SHUT-
OFF VALVE of the current section).
To trip test the electric release system
1. Trip the flow control valve (A1) by performing the
following paragraph “a” or “b”.
a) Activate a FIRECYCLE®detector according to the
manufacturer's instructions.
b) Open the door of the manual emergency release
valve (B10) and trigger the handle.
2. The flow control valve (A1) should open. Alarm
devices (C1 and optional C2) should operate. Water
will flow from all open sprinklers/spray nozzle on the
system piping network.
3. If applicable, once the FIRECYCLE®detector has reset,
verify that the flow control valve (A1) closes and water
flow stops at the end of the soak timer delay.
When trip testing is complete
1. Perform steps 1 through 5 of paragraph 1.5 EMERGENCY
INSTRUCTIONS to take the system out of service.
2. Perform steps of paragraph 1.6 PLACING THE SYSTEM
BACK IN SERVICE AFTER OPERATION.
1.7.2Main drain test
A main drain test shall be conducted to determine whether
there has been a change in the condition of the water
supply piping and control valves.
Test procedure
1. Record the pressure indicated by the water supply
gauge (B12).
2. If applicable, CLOSE the alarm control valve.
3. FULLY OPEN the flow test valve (B6).
4. Record residual pressure.
5. CLOSE the flow test valve (B6) slowly.
6. Record the time taken for supply water pressure to
return to the original pressure.
Note: A main drain test shall be conducted any time the
main water supply valve (D1) is closed and reopened at
the system.
1.7.3Operation of the optional shut-off valve
Inspection of the system can be implemented without filling
the system piping network with water. The use of shut-off
valve (D4) and sight glass assembly (D5) allows to verify
the operation of the system and prevents water from
reaching the piping network.
1. CLOSE the shut-off valve (D4) to isolate the system
piping network.
2. Execute the full flow trip test (see paragraph 1.7.2 of the
current section). The flow control valve (A1) should
open.
3. Using a flashlight in one of the sight glasses, verify that
water flows through the sight glass assembly (D5).
When trip testing is complete
1. Perform steps 1 through 5 of paragraph 1.5 EMERGENCY
INSTRUCTIONS to take the system out of service.
2. Perform steps of paragraph 1.6 PLACING THE SYSTEM
BACK IN SERVICE AFTER OPERATION.

Page 6 of 8TOTALPAC®3FIRECYCLE®III
B
Integrated Fire Protection System
Mechanical Section - Deluge System - FIRECYCLE
®
III Release
FM-076A-0-52A
1.8 Maintenance
NOTICE:The owner is responsible for maintaining the fire
protection system and devices in proper operating
condition.
The system shall be maintained in full operation condition
at all times.
All troubles or impairments shall be corrected promptly
consistent with the hazard being protected.
Refer to MAINTENANCE INSTRUCTIONS provided in Viking
Technical Data describing individual components of the
system used.
The following requirements are based upon NFPA-25.
Records
Records of inspections, tests and maintenance of the
system and its components shall be made available to the
AUTHORITY HAVING JURISDICTION upon request. Typical
records include, but are not limited to: valves inspection;
flow, drain, and pump tests, and trip test of the flow control
valves.
Acceptance test records should be retained for the life of
the system or its special components. Subsequent test
records should be retained for a period of one (1) year
after the next test. The comparison determines
deterioration of system performance or condition and the
need for further testing or maintenance.
1.8.1 Monthly
1. Inspection of gauges (water supply (B12) and priming
chamber (B11) pressure) to ensure good condition and
normal water supply pressure.
2. Control valve shall be externally inspected. The valve
inspection shall verify the following:
a) The gauges indicate that normal supply water
pressure is being maintained.
b) The valve is free of physical damage.
c) All valves are in the appropriate open or closed
position (see paragraph 2.1 of the current section).
d) There is no leakage from the alarm drains.
1.8.2 Quarterly
1. Check alarm pressure switch (C1)and optional water
motor gong (C2)by opening the alarm test valve (B5).
1.8.3 Semi-annually
1. Main water supply valve (D1) switch shall be operated
to verify the switch actuation upon movement of the
hand wheel.
2. Check alarm pressure switch (C1)and optional water
motor gong (C2)by opening the alarm test valve (B5).
3. Perform functional test of all components of the system.
1.8.4 Annually
1. Perform full flow trip test (see paragraph 1.7.1 of the
current section).
2. Record indicating the date of the last trip, tripping time
and name of the organization conducting the test shall
be maintained at a location available for review by the
AUTHORITY HAVING JURISDICTION.
3. Perform main drain test (see paragraph 1.7.2 of the
current section).
1.8.5 Every 5 years
1. Test on gauge (gauge precision required: less than 3%
of the full scale).
2. Perform test on control valve operation.
3. Flow control valve (A1) and their associated strainers,
filters and restriction orifices shall be inspected
internally.
4. Perform main drain test (see paragraph 1.7.2 of the
current section).

TOTALPAC®3FIRECYCLE®III Page 7 of 8
Integrated Fire Protection System
B
Mechanical Section - Deluge System - FIRECYCLE
®
III Release
FM-076A-0-52A
2- Deluge system with FIRECYCLE®III release
Note: Numbers indicated between brackets refer to figure 1
DETAILED SYSTEM TRIM SCHEMATICS from this section.
2.1 Normal condition
1. Release control panel of the TOTALPAC®3
FIRECYCLE®III system (if applicable)
a) Green lamp identified AC POWER lights up.
b) All other lamps are off.
c) Green lamp for disable switch lights up.
2. Valves
a) Main water supply valve (D1) is OPEN.
b) All upstream water supply valves are OPEN.
c) Priming valve (B1) is OPEN.
d) Flow test valve (B6) is CLOSED.
e) Main drain valve (D3) is CLOSED.
f) Alarm test valve (B5) is CLOSED.
g) Manual emergency release valve (B10) is CLOSED
(handle in vertical position).
h) All gauge valves are OPEN.
i) Shut-off valve (D4) is OPEN (if applicable).
3. Gauges
a) Water supply pressure (B12) shall not exceed
250 PSI (1724 kPa).
b) Priming chamber pressure (B11) should be equal to,
or higher than, water supply pressure (B12).
4. Pressure switches & settings (factory set)
a) Alarm pressure switch (C1) should activate when
pressurized higher than 5 PSI (34 kPa).

Page 8 of 8TOTALPAC®3FIRECYCLE®III
B
Integrated Fire Protection System
Mechanical Section - Deluge System - FIRECYCLE
®
III Release
FM-076A-0-52A
Figure 1 - Detailed system trim schematic
Typical deluge system with FIRECYCLE®III release (3" (80 mm) system shown)
CONTRACTOR'S HYDROSTATIC
TEST PORT (system side)
T
OTAL
P
AC
3Base
(shown without enclosure)
B9
F1
F2
C1
D1
D3
B6
B11
B2
C2
FIELD CONNECTION TO
SPRINKLER PIPING NETWORK
B3
FIELD CONNECTION
TO WATER SUPPLY
(on both sides)
B10
B8
CONTRACTOR'S
HYDROSTATIC TEST PORT
(water supply side)
B7
B1
B4
FIELD CONNECTION
TO OPEN DRAIN
(on both sides)
B12
A1
B5
B13
FM-061H-0-109D
Trim components
A1 Flow control valve
B1 Priming valve (N.O.)
B2 Strainer
B3 1/16" (1.6 mm) Restricted orifice
B4 Spring loaded check valve
B5 Alarm test valve (N.C.)
B6 Flow test valve (N.C.)
B7 Drip check valve (N.O.)
B8 Drain check valve
B9 PORV (pressure operated relief valve)
B10 Manual emergency release valve (N.C.) (shown in
closed position)
B11 Priming pressure water gauge & valve (N.O.)
B12 Water supply pressure gauge & valve (N.O.)
B13 Clapper check valve
C1 Alarm pressure switch (PS10-1)
C2 ¾"-NPT (20 mm) connection to optional water motor
gong (strainer to be supplied by contractor)
D1 Main water supply valve (N.O.)
D3 Main drain valve (N.C.)
F1 24VDC solenoid valve (N.C.)
F2 24VDC solenoid valve (N.O.)

TOTALPAC®3Page 1 of 2
Integrated Fire Protection System
C
Trim Options
FM-076A-0-82B
Deluge trim options
1. Shut-off valve & sight glass
The shut-off valve & sight glass option is intended to be
used for applications where testing of the system operation
without filling the sprinkler piping network is desirable and
where it is critical that all functions of the preaction system
be tested under actual discharge conditions. Examples of
such applications are freezers, ovens, museums, data
processing and other hazards where the possibility of
water leaking from the piping system is to be avoided at all
costs.
Operation of the shut-off valve
Inspection of the system can be implemented without filling
the sprinkler piping network with water.
1. CLOSE the sprinkler piping network shut-off valve (D4);
the valve is supervised on the same circuit as the main
water supply valve (D1).
2. OPEN the main drain valve (D3).
3. Simulate the operation of the system to open the deluge
valve (A1); see annual test under section B
INSPECTION AND MAINTENANCE. Using a flashlight in the
sight glasses, verify that water flows through the sight
glass assembly (D5).
4. Once tests are completed, make sure the main drain
valve (D3) is completely CLOSED. Return the system in
service as per section B PLACING THE SYSTEM BACK IN
SERVICE.
5. Fully OPEN the shut-off valve (D4). Reset the release
control panel as per section E CONTROL BUTTONS.
Figure 1 – Shut-off valve & sight glass
(figure is shown without cabinet for clarity)
Supervised
shut-off valve (D4)
Point flash
light here
Main drain
valve (D3)
Sight glass
assembly (D5)
Supervised
main water
supply valve (D1)
FM-061H-0-78B
2. Fire department connection
The fire department connection option consists of a
grooved tee fitting installed at the outlet of the deluge
valve (A1). An access hole of the proper diameter is
factory pre-drilled on the right side of the TOTALPAC®3
enclosure for connection going to the fire department
connection.
Note : The fire department connection hardware itself
(drain, siamese, etc.) is not provided with this option and
shall be provided by the installing contractor. Refer to
NFPA-13 Standards for additional information about the
equipment layout and installation.
Warning : The fire department connection is not available
on 8" (200 mm) system.
Figure 2 – Fire department connection
(figure is shown without cabinet for clarity)
FM-061H-0-79B
Towards fire department
connection (hardware by
contractor)
Grooved tee fitting
with coupling & cap

Page 2 of 2TOTALPAC®3
C
Integrated Fire Protection System
Trim Options
FM-076A-0-82B
3. Semi and full-flanged option
When required by the user, TOTALPAC®3unit can be
provided in either a semi-flanged of full flanged
configuration.
The semi flanged option provides flanged fittings only on
the water inlet pipe (side needs to be specified at the time
of order) and on the system riser outlet. The drain
manifold is then provided with a threaded end that also
needs to have its side specified (left or right). The rest of
the fittings are the same as usual with the main
components being provided in the standard flanged/
grooved configuration.
The full flanged option is the same as above but goes a
step further with the main components being also provided
with a flanged-flanged configuration.
When provided, the face of the flanges will always be
located 6 inches from the outside face of the mounting
base or cabinet surface. On skid unit, the surface of the
flange on the outlet riser will always be 6 inches above the
dimension shown on the dimensional data of the system
ordered.
Figure 3 – Semi-flanged unit typical detail
(figure is shown without cabinet for clarity)
FM-061H-0-208B
Flanged fitting outside cabinet
(when provided)
Threaded end
Flanged fitting outside cabinet
(when provided)
Field connection
to water supply
(specify side)
Field connection
to open drain
(specify side)
4. OSHPD seismic option
Pre-approved construction, under OSP-0341-10, using
specific requirements.

TOTALPAC®3Page 1 of 8
Integrated Fire Protection System
E
Control Section
FM-076A-0-97A
1. Self-contained unit with integrated release
control panel
1.1Product description
The release control panel of the TOTALPAC®3system is an
add-on unit that is installed inside the cabinet at the
factory.
Once the left door is opened, the locked control panel door
can be opened to give access to the control panel, the
emergency battery compartment, and other related
equipment.
A releasing circuit disconnect switch is located at left of the
release control panel.
The control panel can be easily flipped once unlatched
from the right side, giving access to electrical junction's
box of the unit.
1.2Self-contained unit with Viking VFR-400 release
control panel
The Viking release control panel model VFR-400 is a listed
and approved, microprocessor based fire control/releasing
panel. The battery compartment can hold two 12 volt
batteries which are charged by an internal battery charger.
Batteries are available to provide up to 90 hours of backup
power during AC power failure.
The VFR-400 panel can be used with a wide range of
compatible initiating devices such as pull stations, heat
detectors (including linear heat detectors), photo-electric
and ionization smoke detectors.
For complete compatibility list, please see the Viking
VFR-400 Installation, operation and instruction manual
provided with the TOTALPAC®3unit.
Pre-configured programs allow field programming for one
of ten possible input/output combinations that are available
and listed for use with the TOTALPAC®3system.
A field wiring electrical junction boxes is integrated with the
cabinet for connection of detection system, auxiliary
contacts and signaling devices. All supply, inputs &
outputs are factory wired from the control panel to terminal
strips (TBA, TBB & TBC) for contractor's field wiring (see
figure 4 and the section F ELECTRICAL).
Gauges to indicate water supply pressure and priming
water pressure are all visible through clear Lexan windows
on the left door.
1.3Technical Data
Cabinet
Steel enclosure:Refer to section G CABINET SECTION for
further details.
Temperature: 39°F (4°C) to 120°F (48°C)
Humidity: 85% relative humidity (non-condensing) at
90°F (32°C) maximum
AC Power
Releasing control panel AC power shall be supplied by a
dedicated circuit breaker, as per NFPA 70, Section 760
and Canadian Electrical Code, Section 32.
The panel is available for use with either 120VAC, 60Hz or
220/240VAC, 50/60Hz power supply.
1.4Visual Indicators
Red LED’s:
- Initiating device circuit active (4)
- Notification/Release circuit active (4)
- Common alarm
Green LED:
- AC power
Yellow LED’s:
- Initiating device circuit trouble (4)
- Output circuit trouble (4)
- Supervisory initiating zone (4)
- Supervisory bell output active (4)
- Supervisory 1
- Supervisory 2
- Power trouble
- Supervisory trouble
- System trouble
- Ground fault
- Discharging/Pre-Discharge
- Alarm silenced

Page 2 of 8TOTALPAC®3
E
Integrated Fire Protection System
Control Section
FM-076A-0-97A
1.5Control buttons
SCROLL UP / BUZZER SILENCE and
SCROLL DOWN / BUZZER SILENCE:
When a trouble or supervisory event occurs, a press of this
button will acknowledge each viewed event and the
appropriate output will silence, as well as the applicable
LED. The applicable TROUBLE or SUPERVISORY input LED
will change from flashing to steady. The message of the
first line on the display will be terminated with ACK for each
acknowledged event input. Once all events in trouble or
supervisory state have been viewed, the panel buzzer will
silence. A subsequent trouble or supervisory event will
resume the panel buzzer. Trouble events are self-
restoring. Supervisory events latch and require a reset to
be cleared.
SIGNAL SILENCE:
By pressing SIGNAL SILENCE button, all silenceable outputs
will de-activate, as well as the applicable LED. A trouble
condition will be created, the TROUBLE contact will be
activated and the yellow ALARM SILENCE LED will light.
WARNING ! Alarms initiated from a WATERFLOW signal
cannot be silenced. The panel must be reset to silence
audible devices.
SYSTEM RESET:
The RESET button breaks power to all initiating circuits,
4-wire smoke detectors power and will clear any activated
output circuits. If any alarm, supervisory or trouble still
exists after reset, they will reactivate the control panel.
1.6Time & date settings
1. Slide the program switch down to PROGRAM position.
2. Press on FUNCTION button until the following is
displayed.
SET TIME?
3. Press the SELECT button to get to the MINUTES sub-
menu.
01/21/2000
MINUTES 02:58:04
Use SELECT button to increase the minutes, or use SET
button to decrease minutes.
4. Press the FUNCTION button to get to the HOURS sub-
menu.
01/21/2000
HOURS 02:58:04
Use SELECT button to increase the hours, or use SET
button to decrease hours.
5. Press the FUNCTION button to get to the DAY sub-menu.
DAY 01/21/2000
02:58:04
Use SELECT button to increase day, or use SET button to
decrease day.
6. Press the FUNCTION button to get to the MONTH sub-
menu.
MONTH 01/21/2000
02:58:04
Use SELECT button to increase month, or use SET button
to decrease month.
7. Press the FUNCTION button to get to the YEAR sub-menu.
YEAR 01/21/2000
02:58:04
Use SELECT button to increase year, or use SET button
to decrease year.
8. Slide the program switch up to RUN position.

TOTALPAC®3Page 3 of 8
Integrated Fire Protection System
E
Control Section
FM-076A-0-97A
Figure 1 – Cabinet layout
FM-061H-0-126A-3
WATER INLET
PRESSURE
PRIMING
PRESSURE
MANUAL
EMERGENCY
RELEASE
CONTROL
PANEL

Page 4 of 8TOTALPAC®3
E
Integrated Fire Protection System
Control Section
FM-076A-0-97A
Figure 2 - Control equipment layout
RELEASING CIRCUIT
DISCONNECT SWITCH
VFR-400
ZONE 4
AC POWER SUP1 / ABORT
STEADY: DISCHARGED
ALARM SILENCE
COMMON ALARM
FLASHING: PRE-
SUPERVISORY 2POWER TBL
SYSTEM TBL
GROUND
FAULT
PROGRAM
VIEWING ANGLE
BUZZER SILENCE
SCROLL-UP
BUZZER SILENCE
SCROLL-DOWN
SELECT
FUNCTION
MODE
PROGRAM MODE
SIGNAL SILENCE
SYSTEM RESET
RUN
DISCHARGE
RED OUTPUT LED STEADY: ABORT
SUPV TBL
TB102 TB103
TB101TB1TB201
LN
AC IN
CONNECTOR
S
24VDC
NON-RESETTABLE
RS485 AUX
24VDC
SUP 1 SUP 2
VALVE
TAMPER
SUPERVISORY
LOW AIR
ZONE 1
HEAT / SMOKE
DETECTORS
ZONE 2
HEAT / SMOKE
DETECTORS
ZONE 3
WATER FLOW
SWITCH
ZONE 4
MANUAL
STATION
GENERAL
ALARM
OUTPUT 1
WATER FLOW
BELL
OUTPUT 2
RELEASE
CIRCUIT
OUTPUT 3
SUPERVISORY
BELL
OUTPUT 4
BATT
NON-POWER LIMITED
SUPERVISED COM NO NC
TROUBLE
COM NO NC
ALARM
COM NO
SUPV
COM NO
WTRFLW
RUN
SET
ZONE 3
ZONE 2
ZONE 1
OUTPUT 2
OUTPUT 1
OUTPUT 3
OUTPUT 4
RESETTABLE
POWER
SW5
5
DISABLE SWITCH
SYSTEM DISABLED
SYSTEM NORMAL
RELEASING CIRCUIT
UNLATCH TO OPEN
THE RIGHT DOOR
(or rotate the control panel)
12VDC BATTERY SET
AIR COMPRESSOR
ISOLATING SWITCH (E15)
CONTROL PANEL
(shown with door open)
UNLATCH TO ROTATE
THE CONTROL PANEL
JUNCTIONS BOX
(behind control panel)
FM-061H-0-144A
Figure 3 - Detail of VFR-400 User interface
VFR-400
ZONE 4
AC POWER SUP1 / ABORT
STEADY: DISCHARGED
ALARM SILENCE
COMMON ALARM
FLASHING: PRE-
SUPERVISORY 2POWER TBL
SYSTEM TBL
GROUND
FAULT
PROGRAM
VIEWING ANGLE
BUZZER SILENCE
SCROLL-UP
BUZZER SILENCE
SCROLL-DOWN
SELECT
FUNCTION
MODE
PROGRAM MODE
SIGNAL SILENCE
SYSTEM RESET
RUN
DISCHARGE
RED OUTPUT LED STEADY: ABORT
SUPV TBL
RUN
SET
ZONE 3
ZONE 2
ZONE 1
OUTPUT 2
OUTPUT 1
OUTPUT 3
OUTPUT 4
LAMP TEST
FM-061H-0-143A
Other manuals for TOTALPAC 3 FIRECYCLE III
2
This manual suits for next models
1
Table of contents