TECO TMM-20 User manual

TMM-20
Multifunction Power Meter
Operation Manual

:
..
TMM-20
:
:
Enter Key/
Shift Key
Up Key
Down Key
TMM-20
The TMM-20 series Multifunction Power Meter provide high accuracy measurement, display and
communication(Modbus RTU) of all electrical and power quality parameters, including harmonic
measurement THD(Total Harmonic distortion)
Provides electricity bill ratio (Cost) and carbon dioxide ratio (Co2) set can show cumulative electricity
bills and carbon emissions, and suitable for the installation in the power management of remote
communication, such as the use of demand.
TMM-20 Operation Manual
1
Operation Manual
Description
Application
Control panels and Motor, Generator monitoring Switchgear distribution systems , Energy
Management Power quality analysis
Front Panel
Voltage /Current display page
Control button:
Main electric parameters display page
Electric parameters display page
Energy parameters display page
Passwords : 4 digits passwords;Range:0000~9999
( Default 1000)
Display:LCD65(W)x58(H)mm;White backlight;Blue wording
Visible under direct sunlight
LCD LED:Backlight on time1~15Min (“0” is always light)
Upper row 20 digits:Display date. time
4 Digitsx 4 rows, Display value
8 Digits x 1 row, Display Energy parameters
Rs485 communication status;2 square status icons
Display Master and Slave status;
Load status indication: IND:load is inductive CAP:load is capacitive
LOAD%:Display load percentage :Display load quadrant
Display load quadrant
:When on ,value showing Line-Line
:When on ,value showing in Phase
:When on ,value showing in Neutral
:When on ,value showing Total value
:When on ,value showing Average
:When on ,value showing Total harmonics distortion
:LED-16 byte display parameters Unit

[:]
SET SET
[
SET
[
SET
[
:]
:]
L
N
G
L
N
G
1AFuse
DC100~300 V
AC85~264 V
14151617 18 2324192021 22
G L N
RS485 Por t
11121314 1516171819
A+ B-
:
90. 0+0. 8
90. 0+0. 8
PANELCUT- O UT
Un i t : mm
16. 0
55. 0
96. 0
96. 0
Power
Harmonic
ENTER
Energy
Volt/Amp
Tot al
2012 07-03-13-50 - 4 0-
FIX HOLDERS
1.0~18.0 mm
PAN EL CUT OUT_ :
90 (W)x90 (H) mm
+0.8 +0.8
+
-
TMM-20
TMM-20
V2V3
V1Vn
1 2 3 4 5 6 7 8 9 10
SOURCE
LOAD
B
C
N
A
I11 I12 I21 I22 I31 I32
20
21
22
23
24
16
17
18
19
11
12
13
14
15
A+
11
B-
12
L / +
22
N / -
24
RS -485
Aux. Power
20
1
2
3
4
5
6
7
8
9
10
SOURCE
LOAD
B
C
N
A
I21
I22
I11
I12
I31
I32
V2
V3
V1
Vn
V2
V3
V1
Vn
1
2
3
4
5
6
7
8
9
10
SOURCE
LOAD
B
C
N
A
I11
I12
I21
I22
I31
I32
V2
V3
V1
Vn
1
2
3
4
5
6
7
8
9
10
SOURCE
LOAD
B
C
N
A
I11
I12
I21
I22
I31
I32
2
TMM-20 Operation Manual
Dimensions Installation
Connection diagram
RS485 / (Terminal Block 2)
Terminal block 2
RS485
Fliter or isolated transformer
Dist ance Max. : 12 00M
: 120~300 / 0.25WTe rmi nator Ω
( : 150 )Standard Ω
3P4W-Direct Voltage NO PT/3CT
3P4W-3PT/3CT
3P3W(Balanced load)-3PT/1CT 3P4W(Balanced load)-Direct Voltage NO PT/1CT

[ SET
[ SET
[ SET
[ SET
[ SET
:]: ]
:]
:]
:]
- 3-
:]
:]
1 2 3 4 5 6 7 8 9 10
SOURCE
LOAD
B
C
A
V2V3V1VnI21 I22I11 I12 I31 I32
1 2 3 4 5 6 7 8 9 10
SOURCE
LOAD
B
C
A
V2V3V1VnI11 I12 I3 1 I32I21 I22
1 2 3 4 5 6 7 8 9 10
SOURCE
LOAD
B
C
A
V2V3V1VnI21 I22I11 I12 I31 I32
1 2 3 4 5 6 7 8 9 10
SOURCE
LOAD
N
A
V2V3V1VnI21 I22I11 I12 I31 I32
1 2 3 4 5 6 7 8 9 10
SOURCE
LO AD
B
C
A
V2V3
V1VnI21 I22I11 I12 I31 I32
1 2 3 4 5 6 7 8 9 10
SOURCE
LOAD
B
C
A
V2V3V1VnI21 I22I11 I12 I31 I32
1 2 3 4 5 6 7 8 9 10
SOURCE
LOAD
N
B
A
V2V3V1VnI21 I2 2I11 I12 I31 I32
TMM-20
操作手冊
3
Connection diagram
3P3W-2PT/2CT 3P3W-Direct Voltage NO PT/2CT
3P3W-Direct Voltage NO PT/1CT
3P3W-NO PT/3CT
3P3W(Balanced load)-2PT/3CT
1P2W- [ SET [ SET
1P3W-
TMM-20 Operation Manual

2 0 1 2 0 7 - 0 3-13-50-4 0-
NO
YES
A1 A Input group
Energy group
6~
G1 G3~
201 2 07-03- 1 3 - 5 0-4 0-
c
a
2 0 1 2 0 7 - 0 3-13-50-4 0-
l -
E1~E 3 RS485 group
F1 F2~
H1
G1
▲▼
▲▼
▲▼
▲▼
▲▼
4
TMM-20 Operation Manual
Operational processes
Confirm wiring
Power transmission
Display
Models and versions
Permanent Mission
of the screen display
Press
Press
Key
Press
Key
Press
Key
Key
Key
Key
Key
Key
Key
Key
Key
Key
Key
Press
Key
Press
Key
Press
Key
1 sec
The permanent screen Please
refer to the H-1 set Item
P.COD
Default:1000
Password
Correct
Parameter settingGeneral operating
Time group
Permanent screen
INIT group
Key definition:
ENT : Enter /volt.(Voltage)/AMP.(current)
Shift : Shift left /Total(Comprehensive)
Up : Move Up/Power
Down : Move Down /Energy
1 Sec back operation display
Phase A voltage
Phase B voltage
Phase C voltage
Average Phase voltage
Effective energy
Phase voltage and the Average
Voltage, Current, Total harmonic
display group
Integrated display group
(3P3W/3P3W.B/3P3W3 No such
function)
Power display group
Electricity, Time display group

2 0 1 2 0 7 - 0 3-13-50-4 0-
c - a
a -
c
2 0 1 2 0 7 - 0 3-13-50-4 0-
c
a
%
2 0 1 2 0 7 - 0 3-13-50-4 0-
c
a
201 2 07- 0 3 -13-50-4 0-
c
N
a
201 2 07- 0 3 -13-50-4 0-
%
a
c
2 0 1 2 0 7 - 0 3-13-50 - 4 0-
c
a
..
..
.
.
5
Press KEY
Press KEY
Press KEY
Press KEY
Phase voltage and the Average
Phase A voltage
Phase B voltage
Phase C voltage
Average Phase voltage
Effective energy
A-B Line Voltage
B-C Line Voltage
C-A Line Voltage
Average line voltage
Effective energy
THDU/ Phase A THD
THDU/ Phase B THD
THDU/ Phase C THD
Average line voltage THD
Effective energy
1.1.3-Phase current values and
the average
Phase A current
Phase B current
Phase C current
Average current
Effective energy
TMM-20 Operation Manual
Press ENT Key (Voltage and Current harmonics screen)
Normal screen 1 seconds,
first showed off the voltage value As follows
1.1.4-Phase Current and
Neutral Current
Phase A current
Phase B current
Phase C current
Neutral Current(N)
Effective energy
1.1.5-Current harmonic
distortion rate
THDI/Phase A Current THD
THDI/Phase B Current THD
THDI/Phase C Current THD
Average Current THD
Effective energy
Press Key1 Sec Back to
Measurement screen
Press Key
Press Key
1.1.1-The Value of the Line
voltage and the Average Line voltage
1.1.2-Voltage total harmonic distortion
Phase voltage total harmonic

2 0 1 2 0 7 -03-13- 5 0 - 4 0-
c
a
2 0 1 2 0 7 - 0 3-13-50- 4 0-
c
a
2 0 1 2 0 7-03-13-50- 4 0-
a
c
201 2 07- 0 3 -13-50-4 0-
a
c
201 2 07- 0 3 -13-50-4 0-
a
c
2 0 1 2 0 7-03-13-50- 4 0-
a
c
2 0 1 2 0 7 - 0 3-13-50-4 0-
l -
2 0 1 2 0 7 - 0 3-13-50-4 0-
l - l
2 0 1 2 0 7 - 0 3-13-50-4 0-
Tota lTota l
Fr eq
Tota l
2 0 1 20 7 - 0 3-13-50-4 0-
- 6 -
(3P3W/3P3W.B/3P3W3 No such function)
6
Press Shift KEY (Comprehensive screen)
Normal screen 1 seconds,
first showed off the voltage value As follows
Phase voltage and the Average
Phase A voltage
Phase B voltage
Phase C voltage
Average Phase voltage
Effective energy
Press KEY
Press KEY
Press KEY
Press KEY
Press KEY Press KEY
Press KEY
Press KEY
Press KEY
Press KEY
TMM-20 Operation Manual
1.2.1-3-phase integrated
display-1
Average Phase voltage
Average current
Total Effective power
Average power factor
Effective energy
1.2.3-3-phase integrated
display-3
Total Apparent Power
Total Reactive Power
Total Effective power
Average power factor
Effective energy
1.2.2-3-phase integrated
display-2
Average Line voltage
Average current
Total Effective power
Average power factor
Effective energy
1.2.4-3-phase integrated
display-4
Total Apparent Power
Total Reactive Power
Total Effective power
Frequency
Effective energy
Normal screen 1 seconds,
first showed off the voltage value As follows
Phase voltage and the
Average
Phase A voltage
Phase B voltage
Phase C voltage
Average Phase voltage
Effective energy
1.3.1-Effective power display
Phase A active power
Phase B active power
Phase C active power
Total Effective power
Effective energy
1.3.2-Reactive power display
Phase A reactive power
Phase B reactive power
Phase C reactive power
Total reactive power
Invalid electricity
1.3.3-Apparent power display
Phase A apparent power
Phase B apparent power
Phase C apparent power
Total Apparent Power
Effective energy
1.3.4-Power Factor display
Phase A power factor
Phase B power factor
Phase C power factor
Average Power factor
Effective energy
Press Key1 Sec Back to
Measurement screen
Press Key1 Sec Back to
Measurement screen
Press Up KEY (Power Parameters)

2 0 1 2 0 7 -03-13-50- 4 0-
Tot al
2 0 1 2 0 7 - 0 3-13-50-4 0-
Tota l
2 0 1 2 0 7 - 0 3-13-5 0 - 4 0-
c
a
2 0 1 2 0 7 - 0 3-13-50-4 0-
Tot al
7
TMM-20 Operation Manual
Press Down KEY (Power parameters)
Normal screen 1 seconds,
first showed off the voltage value As follows
Phase voltage and the Average
Phase A voltage
Phase B voltage
Phase C voltage
Average Phase voltage
Effective energy
1.4.1-Power display-1
Total apparent power
Total reactive power
Total effective power
Average power factor
Total Effective energy
1.4.2-Power display-2
Total apparent power
Total reactive power
Total effective power
Average power factor
Total invalid electricity
1.4.3-Total electricity bills display
Total apparent power
Total reactive power
Total effective power
Average power factor
Total electricity bill
1.4.4-Carbon emissions
Total apparent power
Total reactive power
Total effective power
Average power factor
Total carbon dioxide
Press KEY
Press KEY
Press KEY
Press KEY
Press KEY
Press Key1 Sec Back to
Measurement screen

: 600
: 600
: 5
: 2100
: 1000
INPUT Group
2 0 1 2 0 7 - 0 3-13-50-4 0-
2 0 1 2 0 7 - 0 3-13-50-4 0-
2 0 1 2 0 7 - 0 3-13-50-4 0-
2 0 1 2 0 7 - 0 3-13-50-4 0-
2 0 1 2 0 7-03-13-50- 4 0-
2 0 1 2 0 7-03-13-50- 4 0-
:1
201 2 07- 0 3 -13-50-4 0-
: 9 006
201 2 07- 0 3 -13-50-4 0-
:n. 8. 2
2 0 1 2 0 7-03-13-50- 4 0-
2 0 1 2 0 7-03-13-50 - 40-
0000 9999~
:1000
▼
▲
▲
▲
▲
▲
▲
▲
▲
▲
8
TMM-20 Operation Manual
Engineers set class, non-personnel do not arbitrarily enter the change, in order to avoid abnormal.
Operation
Press Key Enter the setup menus
Press Key : SET
Press Key : SHIFT
Press Key : MOVE/INCREASE
Press Key : DOWN/DECREASE
Press Key : CONFIRM
Password
Default
Default
Default
Default
Default
A-1 Voltage Phase line set
Set range is as follows:
1P2W/1P3W/3P3W/
3P3W.B(Balanced)/3P3W3/
3P4W/3P4W.B (Balanced)
Default:3P4W
Key
Key Key Key Key
Key Key
Key Key
Key Key
Key Key Key Key
Key Key
Key Key
A-2 Primary-side voltage (PT)
Set range:100~500000V
Default
Default
Default
A-3 Secondary-side voltage(PT)
Set range:100~600V
A-4 Primary current (CT)
Set range:5~10000A
A-5 Watt-h / Var Clear
Clear Passwords:
0000~9999
Zero password please call
the company to ask.
Default
A-6 P.COD
Set range:
0000~9999
E-1 Communication
station No.
Set range:001~255
Rs485 Group
E-2 Communications
transmission rate
Set range:
1200、2400、4800、9600、
19200、38400
E-3 Parity Check
Set range:n.8.1、n.8.2、
o.8.1、e.8.1

:1
:1
2 0 1 2 0 7 -03-13-5 0 - 4 0-
201 2 0 7 - 0 3-13-50-4 0-
2 0 1 2 0 7 -03-13-5 0 - 4 0-
201 2 07- 0 3 -13-50-4 0-
:2.30
2 0 1 2 0 7 - 0 3-13-50-4 0-
2 0 1 2 0 7 - 0 3-13-50-4 0-
:0. 638 :0
201 2 07- 0 3 -13-50-4 0-
▲
▲
▲
▲
▲
▲
9
TMM-20 Operation Manual
ENEGY Group
F-1 Cost rates
Set range:
00.00~99.99 (Rates per kWh)
F-2 CO2 Carbon ratio
Set range:
0.000~9.999(kg/kWh)
Default
Default
TIME Group
G-1 Backlight time
Set range:0~15(Minute)
Set 0 for Always
G-2 Date set
Set range:
2000.01.01~2099.12.31
G-3-Time set
Set range:
00.00.00~23.59.59
Key Key
Key Key Key Key
Key Key
Key Key
Key Key
Press KEY
The first
The
second
The third
The
fourth
H-1 Permanent screen
selection
Set range:1~4
Schedule Description
DefaultDefault
Default
I-1 INIT Restore Default
Set range:0000~9999
set:7170,restore
Press Key1 Sec Back to
Measurement screen
Schedule : The Permanent screen instructions
Average Phase voltage
Average current
Total Effective
Average power fector
Effective energy
Average Line voltage
Average current
Total Effective power
Average power fector (PF/IND/Avg)
Effective energy
Total Apparent Power
Total Reactive Power
Total Effective Power
Average power fector (PF/IND/Avg)
Effective energy
Total Apparent Power
Total Reactive Power
Total Effective Power
Frequency
Effective energy
1.2.4-3 phase integrated display-4
1.2.3-3 phase integrated display-3
1.2.2-3 phase integrated display-2
1.2.1-3 phase integrated display-1
Back To A-1 Display or

General class information
10
TMM-20 Operation Manual
RS485 communication parameters address table (Function code: 03h, 06h, 10h)

Input group setting class
General class information
RS485 communication group settings class
Cost group setting class
TMM-20 Operation Manual
11

Time group settings class
Permanent screen group settings class
Client Custom class
12
TMM-20 Operation Manual

GM-31-00 2015-03-18
Table of contents
Popular Measuring Instrument manuals by other brands

PCE Instruments
PCE Instruments PCE-RT 10 manual

Shinyei
Shinyei OMX-ADM Operation manual

HACH LANGE
HACH LANGE Pocket Colorimeter II user manual

ICM Controls
ICM Controls ICM450 Installation, operation & application guide

Sensit
Sensit ULTRA-TRAC APL Quick start instructions

Mitsubishi Electric
Mitsubishi Electric EcoMonitorPro EMU2-RD3-F instruction manual