
Oper ting Instructions — Type 321A
Ac Mode
Ac-mode triggering is obtained by setting the AC-DC
switch to the AC position. This mode provides stable trig
gering on virtually all types of waveforms. As a general
rule, however, the ac mode is unsatisfactory for triggering
with low amplitude waveforms at frequencies below approxi
mately 15 cycles. This figure will vary depending upon the
amplitude and shape of the triggering waveform and should
not therefore be set as an absolute standard. Triggering at
frequencies below 15 cycles can be accomplished when
higher amplitude triggering signals are used.
In the ac mode, the triggering point depends on the
average voltage level of the triggering signals. If the trig
gering signals occur at random, the average voltage level
will vary causing the triggering point to vary also. This shift
of the triggering point may be enough so that it is impossible
to maintain a stable display. In such cases you should use
the dc mode,
Dc Mode
Dc mode triggering is obtained by setting the AC-DC
switch to the DC position. This mode of triggering is par
ticularly useful in triggering from waveforms which are not
adaptable to the ac mode, such as random pulse trains or
very low-frequency waveforms. Random pulse trains pose
a special problem in the ac mode since the random occur
rence of the input waveforms causes the average voltage
level to shift. This in turn may cause the triggering level to
shift to an unstable point. This problem is not encountered
in the dc mode since the triggering point is determined only
by instantaneous voltages.
In the dc mode, when the triggering signal is obtained
from the Vertical Amplifier, varying the VERTICAL POSITION
control will change the triggering point. For this reason,
you may find it necessary to readjust the LEVEL control when
you change the vertical position of the trace. To eliminate
this effect, you can use the ac mode provided the triggering
signal is otherwise suitable for this mode of operation. In
the dc mode, the dc level of the external triggering signals
will olso effect the triggering point. Generally, when the
triggering signal is smoll compared to its dc level, the oc
mode should be used.
How to Set the Triggering Level
In the ac and dc triggering modes, the LEVEL control
determines the voltage level on the triggering waveform at
which the sweep is triggered. Using this control, the sweep
can be continuously triggered at any point on the waveform
so long as the slope of the waveform is great enough to
provide stoble triggering. In the dc mode, the sweep cannot
be triggered with any degree of stability at the top of a
square wove, for example, because the time that the voltage
remains constant is comparatively long. As a result, the
sweep triggers at random points along the fop of the square
wave, producing considerable trace jitter.
You can use the same metnod to set the LEVEL control for
either the ac or dc mode. After selecting the triggering
slope, rotate the LEVEL control fully counterclockwise to the
AUTO position. Then rotate the LEVEL control clockwise
until the sweep no longer triggers. Continue to rotate the
control in the clockwise direction until the sweep again trig
gers and a stable display is obtained. Further rotation of the
control in the clockwise direction causes the sweep to trigger
at more positive points on the triggering waveform. In the
fully clockwise direction the trace will free run (Fig. 3-5).
FREE-RUNNING OPERATION
With the Type 321 A, you can get o periodic, free-running
sweep, independent of any external triggering or synchroniz
ing signal, by rotating the LEVEL control fully clockwise to
the FREE RUN position. This permits you to observe the trace
without an input signal. This trace con then be used to posi
tion the sweep or to establish a voltage reference line. The
difference between the traces produced in the AUTO position
and the FREE RUN position is the repetition rate. The repeti
tion rate in the FREE RUN position is dependent upon the
setting of the timing switch. The repetition rate in the AUTO
position is fixed at approximately 50 cycles. At the faster
sweep rates, the trace in the AUTO position will appear to
be dim. In the FREE RUN position the trace intensity remains
essentially constant for all sweep rates.
VERTICAL DEFLECTION SYSTEM
Input Coupling
Input signals to the Vertical Amplifier can be either ac- or
dc-coupled by placing the AC-DC-GND switch in the ap
propriate AC or DC position. Dc coupling applies both the
ac and dc components of the input signal to the vertical
amplifier circuit. This permits measurement of the dc voltage
level as well as the amplitude of the ac component. It is
sometimes neither necessary nor desirable to display the dc
component, however, and in such cases as coupling should
be used. This is accomplished by setting the AC-DC-GND
switch to AC. With ac coupling, a capacitor is placed in
series with the input connector to block the dc component
while allowing the ac component to be displayed.
Placing the AC-DC-GND switch to the GND position
grounds the input circuit of the vertical amplifier to provide
a dc zero reference. In this position the switch internally dis
connects, but does not ground, the applied signal to the
input connector. Thus, the GND position eliminates the usual
need for externally grounding the (Vertical Amplifier) INPUT
connector of the Type 321A or the probe tip to establish a
ground reference.
Deflection Factor
The elecfricol waveform to be observed is applied to the
(Vertical Amplifier) INPUT connector. The waveform is then
applied through the vertical-deflection system to cause the
spot to be deflected vertically to trace out the waveform on
the screen of the crt. The VOLTS/DIV switch controls the
vertical deflection factor in accurately calibrated steps. The
VARIABLE control provides uncalibrated variable deflection
factors between the fixed steps of the VOLTS/DIV switch.
The VARIABLE control has 360° rotation range and a detent
position when the control is set to CALIB.
3-6