Teleco TVRSP868E02 User guide

Product:
TVRSP868E02
Doc:
T899.01
Date:
19/03/2021
Control system for garage doors
Installer’s instruction manual

2
INDEX
1. Product description--------------------------------page 3
2. Installation-------------------------------------------pages 4 - 6
2.1 Mounting the product
2.2 Control Unit diagram
2.3 Electrical connections
2.4 Wired safety device connections
3. Preliminary check and initial start-up-----------pages 6 - 8
3.1 Limit switch configuration and direction check
3.2 Functioning mode
3.3 Exclusion of the safety edge
4. Transmitters & memorization---------------------pages 9 - 11
4.1 Memorization programming mode
4.2 Radio codes memorization
4.3 Single channel: door status request (ask)
4.4 Remote memorization of the first transmitter
4.5 Remote memorization of further transmitters
5. Transmitters deletion-----------------------pages 12 - 13
5.1 Remote deletion of a transmitter
6. Time setting----------------------------------page 13
6.1 Auto close time setting
7. Reset ------------------------------------------page 14
7.1 Control unit reset
8. Technical specification---------------------page 14
9. Troubleshooting------------------------------page 15
The above mentioned product must be installed only by qualified technical personnel in compliance with the standards of automatic openings. All connections must
be rated for a single-phase power supply of 240Vac. For the disconnection from the power line, use an all-pole switch with contact with an opening of at least 3.5
mm. Only suitable materials for the connections must be used to guarantee insulation that complies with current standards on the subject of electrical safety. All the
necessary safety devices are to be seen separately. Incorrect wiring will cause incorrect functioning impairing the safety purpose for which the product has been
designed so that people injuries could occur; failure to follow instructions can cause personal injury and/or property damage. The correct functioning of the product
must be checked once a year. Keep the 240Vac wires separately from the low voltage safety wires. The earth-wires must be fixed with an additional fastening on
the terminals; this fastening has to be done by qualified technical personnel during the installation phase. The appliance has been tested with a power supply wire
type H05VV-F; the power supply wires for outdoor use have not to be lighter than the ordinary wires type H05RN-F. The safety devices have to be in conformity with
EN12978. The installation of the control unit has to be done by fixing the box vertically with the cable glands downwards. The product is in conformity with the RAEE
and RoHS directive.
The earth wire must be longer than the other wires because it must be the last to break off if the cable clamps are slack. Remember that there are specific standards
that must be complied with both as regarding the safety of the electrical systems and as regarding the remote control of tubular motors for roller blind.
In the view of a constant development of their products, the manufacturer reserves the right for changing technical data and features without prior notice.
The connection between the control unit and the auxiliary device must be done using double insulated cables. The auxiliary device connected must be a Class II device.
In case of an external aerial is connected the connections must be done using double insuleted cables.
WARNINGS

3
PRODUCT DESCRIPTION
1
TVRSP868E02
Control unit with integrated radio receiver for the remote control of tubular motors up to 700W, with built-in limit switch, for rolling shutters and rolling doors.
FEATURES
Compact plastic case with easy fixing
Front cover with buttons for programming and up/stop/down commands
Wireless control via radio transmitters
Bidirectional communication: door status is shown by the transmitter LED
with different colour
CONNECTIONS & FUNCTIONING
Wired inputs for safety edge (both resistive 8K2 and infrared)
Wired inputs for command push-button and emergency STOP push-button
2 Functioning modes: semi-automatic (automatic opening + hold-to-run closing) and automatic
Automatic closing with programmable pause time
Exclusion of the safety edge in the last part of the closure, in case of bumpy floor
S
a
f
e
t
y
e
x
c
l
u
s
i
o
n
Max.
5 cm
F
r
o
n
t
c
o
v
e
r
w
i
t
h
u
p
/
s
t
o
p
/
d
o
w
n
b
u
t
t
o
n
s

4
Basic installation Complete installation
INSTALLATION
2
1 - RSP control unit
2 - Tubular motor (240Vac)
3 - Hand transmitter
1
2
3
4
1
2
3
1 - RSP control unit
2 - Tubular motor (240Vac)
3 - Hand transmitter
4 - Wireless security keypad

5
BOX DIMENSIONS
OPENING THE COVER
75 mm
145 mm
180mm
80 mm
95 mm
120 mm
MOUNTING SIDE
MOUNTING THE PRODUCT
2.1
1
4
5
2
3
6
7
9
10
11
3 4 5 6 7 16 17 18 19 20 21 22
P2
P1
L2
L1
CONTROL UNIT DIAGRAM
2.2
1 - High voltage terminals
2 - Low voltage terminals
3 - 5A fuse
4 - Aerial connection
5 - Programming/command buttons
6 - Dip switches
7 - Status/alarm LED
8 - Manoeuvre relays
9 - Common relay
10 - Transformer
11 - Earth terminal
8 8

6
ELECTRICAL CONNECTIONS
2.3
High voltage terminals
Open COM Close
MOTOR
240Vac
Line IN
GND
Via dell'Artigianato, 16 - 31014 Colle Umberto (TV) ITALY
Tel. +39.0438.388511 Fax +39.0438.388536
Web site: www.telecoautomation.com
DATE: 02/03/17 REV: 1.0
ETI-MORS-RDSB02
Da stampare a colori
L N
Wired infrared/
8K2safety edge
Emergency
STOP (TB)
TB COM
COM TD
Via dell'Artigianato, 16 - 31014 Colle Umberto (TV) ITALY
Tel. +39.0438.388511 Fax +39.0438.388536
Web site: www.telecoautomation.com
DATE: 02/03/17 REV: 1.0
ETI-MORS-RDSB02
Da stampare a colori
Low voltage terminals
Push-
button (TD)
see pag. 8 for
connections
# CONNECTION
1 Motor Earth
2 240Vac Power supply - Earth
3 240Vac Power supply IN - LIVE
4 240Vac Power supply IN - NEUTRAL
# CONNECTION
16 Infrared/8K2 safety edge input (brown)
17 Infrared/8K2 safety edge input (green)
18 Infrared/8K2 safety edge input (white)
19 Push-button common (COM)
WIRED SAFETY DEVICE CONNECTIONS
2.4
12 13 14 15 16 17 18 19 20 21 22 23
16- BROWN
17- GREEN
18- WHITE
12 13 14 15 16 17 18 19 20 21 22 23
8K2
0V
12V
24V
N.O.
COM
N.C.
0V
12V
24V
12 13 14 15 16 17 18 19 20 21 22 23 12 13 14 15 16 17 18 19 20 21 22 23
RX FTC010
TX FTC010
REFLEX
+
-
COM
N.C.
12Vdc - 15Vdc
12 13 14 15 16 17 18 19 20 21 22 23
8K2
Infrared (IR) safety edge 8.2 Kohm resistive safety edge
12 13 14 15 16 17 18 19 20 21 22 23
16- BROWN
17- GREEN
18- WHITE
12 13 14 15 16 17 18 19 20 21 22 23
8K2
0V
12V
24V
N.O.
COM
N.C.
0V
12V
24V
12 13 14 15 16 17 18 19 20 21 22 23 12 13 14 15 16 17 18 19 20 21 22 23
RX FTC010
TX FTC010
REFLEX
+
-
COM
N.C.
12Vdc - 15Vdc
12 13 14 15 16 17 18 19 20 21 22 23
8K2
Connect a 8K2 resistor between terminals 16 and 17. Terminals 21 and 22
must be closed by a jumper.
No wired safety device connected
If no wired safety edge is used, connect a 8K2 resistor between
terminals 16 and 17.
# CONNECTION
5 Motor - OPEN
6 Motor - COMMON
7 Motor - CLOSE
# CONNECTION
20 Push-button (step-by-step, N.O.)
21 Emergency STOP push-button (N.C.)
22 Emergency STOP push-button common
A proper connection box should be used to set the limit switch before wiring the motor in the control unit or follow the procedure described on par. 3.1.
Start the system up, the buzzer emits 3 quick sounds if the memory is empty or 1 long sound if the memory has radio codes in. After the power-on, the
control unit executes only opening commands until the door is fully opened. Check the direction of the door. In case of any problem, refer to the paragraph “Troubleshooting” (par. 9).
WARNING: the control unit executes an inversion of the movement untill a complete opening if any error occurs. In case that the safety devices (except for TB
input) are defective or they have been activated, it is possible to operate the door anyway, keeping pressed the command button for more than 5 seconds. The
control unit will automatically switch to hold-to-run mode.
PRELIMINARY CHECK AND INITIAL START-UP
3

7
LIMIT SWITCHES CONFIGURATION AND DIRECTION CHECK
3.1
P1+P2
Procedure only with hold to run commands. Warning: The safety devices are excluded!
ACTIVATION
5 SECONDS TIMEOUT
x3
Within 5s from power ON (L1 and L2 are ON) Press together P1 and P2 for 3 times and keep them pressed for 1s The buzzer makes a long beep L1 and L2 turn OFF after 5s L1 and L2 flashes slowly
P2
P1
+
P2
P1
+
...
ON
L1 L2 L1 L2+
keep it
pressed
for 1s
DEACTIVATION
x3
Press together P1 and P2 for 3 times and keep them pressed for 1s. The buzzer makes a long beep L1 and L2 turn OFF after 5s
P2
P1
+
P2
P1
+
...
keep it
pressed
for 1s
L1 L2
DIP1 OFF: SEMI-AUTOMATIC mode. Automatic opening and hold-to-run closing.The
automatic closure function is deactivated. DIP1 ON: AUTOMATIC mode.
DIP1 + DIP2 ON: Automatic closure function activated (only if DIP1=ON). Default
time is 30 sec.This function has effect only when the door is totally open
DIP2 OFF: Automatic closure function deactivated (default
setting)
FUNCTIONING MODE
3.2
L1 L2
Open the door (in
hold-to-run mode)
in order to set up the
upper limit switch. If the door is moving in the wrong direction:
1- STOP the manoeuvre
2- Switch the control unit off
3- Swap BLACK and BROWN motor wires over - terminals 5 & 7
4- Power the board up again
Close the door (in
hold-to-run mode)
in order to set up the
down limit switch.
hold-to-run
hold-to-run
1 2
ON
1 2
ON
1 2
ON
1 2
ON

8
In case of uneven floors, it could be necessary deactivating the safety edge in the last part of the closure (not more than 5 cm to comply with the
standards) in order to avoid any accidental activation of the safety edge.
This procedure must be performed by qualified installer only, who will take charge of its correct application.
WARNING: this procedure can be used only for doors which require more than 10 seconds each manoeuvre. The exclusion of the safety edge is applied only if the
closure starts from the upper limit switch and it is not stopped.
EXCLUSION OF SAFETY EDGE IN THE LAST 5 CM OF THE CLOSURE
3.3
P1+P2
1. Open the door completely by means of a memorized transmitter. The buzzer
emits a long beep when the upper limit switch is reached.
2. Put on the floor, exactely under the door, a sturdy object not more than 5 cm high.
3. Close the door (in hold-to-run mode), with no interruption. The door will stop at
the obstacle and the control unit will make a long beep.
4. Open the door completely and remove the object. Close the door to verify the
correct application of the procedure.
hold-to-run
max. 5 cm
X
1. 2.
3. 4.
ACTIVATION
30 SECONDS TIMEOUT
x1 x10
Within 30s from power
ON
L1 and L2 are ON
for 5s
L1 and L2 turn OFF Press P1 and P2 1 time and keep
it pressed for 1s
L1 and L2 flash
quickly
Press P2 buttons 10 times and keep it
pressed for 5s
The buzzer emits 3 beeps
P2P1
+
ON
L1 L2+
keep it
pressed
for 1s
P2
... ( 5 s)
keep it
pressed
for 5s
L1 L2 L1 L2
DEACTIVATION
30 SECONDS TIMEOUT
X1 X11
Within 30s from
power ON
L1 and L2 are ON
for 5s
L1 and L2 turn
OFF
Press P1 and P2 1 time and keep
it pressed for 1s
L1 and L2 flash
quickly
Press P2 buttons 11 times and keep it
pressed for 5s
The buzzer emits 5
beeps
P2
P1
+
ON
L1 L2+
keep it
pressed
for 1s
P2
... ( 5 s)
keep it
pressed
for 5s
L1 L2 L1 L2

9
TRANSMITTERS & MEMORIZATION
4
T
R
A
S
M
I
T
T
E
R
S
7 channel
CH1
CH2
CH3
CH4
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH5
CH6
CH7
CH1
CH1
CH2
4 channel 3 channel 2 channel 1 channel
CH1
CH2
CH3
CH4
OPEN
CLOSE
STOP
CH1
CH2
CH3
CH4
CH5
CH6
CH7
OPEN (STOP)
CLOSE (STOP)
OPEN (STOP)
CLOSE (STOP)
OPEN
STOP
CLOSE
CH1
CH2
CH3
CH4
CH5
CH6
CH7
OPEN/STOP/CLOSE
OPEN/STOP/CLOSE
OPEN/STOP/CLOSE
OPEN/STOP/CLOSE
OPEN/STOP/CLOSE
OPEN/STOP/CLOSE
OPEN/STOP/CLOSE
TYPE “C”
TYPE “B”
TYPE “A”
TRANSMITTERS
MEMORIZATION
Only for a 7-CH and 4-CH transmitter
MEMORIZATION PROGRAMMING MODE
4.1
P1+P2
This operation should be done using the button P1+P2. Please refer to the schematic diagram on capter 2.2 in order to localize the position on the board. In order to
carry the transmitter memorization it is necessary use the P1+P2 buttons of the front cover, entering the “programming mode” first.
WARNING: always check that L1 and L2 are flashing
before carry the following memorizations out!
If no further button is pressed within 10 seconds the
control unit exits automatically the programming mode.
ENTERING THE PROGRAMMING MODE
X1
Press P1 and P2 1 time and keep it pressed for 1s L1 and L2 flashes quickly
P2
P1
+
keep it
pressed
for 1s
L1 L2

10
* The buzzer will make a beep each time the button is pressed. No more than a second should pass between one press to another one.
TYPE OF MEMORIZATION P2
AOpen-Stop-Close *
x1
Press the button of the transmitter
relative to the code to memorize.
BOpen (Stop)/Close (Stop) *
x2
COpen/Close/Stop/ *
x6
keep it
pressed
continuous sound
intermittent sound
...
RADIO CODES MEMORIZATION
4.2
P2
(CH4)
In case of using bidirectional transmitters it’s possible to receive a feedback about the door status, shown
by means of the transmitter’s LED:
- Red led: open door
- Blue led: closed door
- Flashing led: missing feedback
Warning: the remaining free buttons of the transmitter should be memorized using the procedure 4.2.
TRTXI868xx04
TRTXP868x04
DOOR STATUS REQUEST (“ASK”)
ASK
SINGLE CHANNEL: DOOR STATUS REQUEST (ASK)
4.3
P2
TYPE OF MEMORIZATION P2
ASK function *
x7
Press any button of TRTXP or
CH4 of TRTXI transmitter to
memorize.
keep it
pressed
continuous sound
intermittent sound
...

11
Warning: The memory must to be empty in order to perform this procedure.
The added transmitter will have the double-channel function (TYPE B).
30 SECONDS TIMEOUT 5 SECONDS TIMEOUT
Press 1 time P3 button for 2s The buzzer emits a
continuous sound.
Press any button of the pair to memorize The buzzer emits a fast
intermittent sound
REMOTE MEMORIZATION OF THE FIRST TRANSMITTER
4.4
...
ON
( x1)
P3
new
3x
* P3 button is located inside the transmitter. Every time P3 is pressed the lights switch ON.
REMOTE MEMORIZATION OF FURTHER TRANSMITTERS
4.5
The added transmitter will have the same functions of the transmitter used for the memorization.
This procedure is compatible with any type of transmitter.
5 SECONDS TIMEOUT 5 SECONDS TIMEOUT
Press 1 time P3 button (twice if
within 30 seconds from power on) of
a memorized transmitter for 2 sec.
The buzzer emits a
continuous sound.
Press the button of
a transmitter already
memorized.
The buzzer stops
for 1s
The buzzer emits a
continuous sound.
Press the button of a new transmitter
to memorize with the same functions.
The buzzer emits a fast
intermittent sound
1 s
...
( x1)
memorized new
P3
memorized
3x

12
Press 5 times P1 button and hold it for at least 10 seconds. The buzzer emits an intermittent sound. Release the button once the sound becomes continuous.
TYPE OF DELETION P1
ALL THE RADIO CODES *
x5
Press 4 times P1 button and holt it. The buzzer emits an intermittent sound. Press the button of the transmitter to delete. Once the deletion is successfully completed, the buzzer
emits a continuous sound.
TYPE OF DELETION P1
SINGLE RADIO CODE *
x4
Press the button of the transmitter
relative to the code to memorize.
5
P1+P2
continuos
sound
keep it
pressed
... intermittent sound
continuos
sound
... intermittent sound
(10 s)
This operation should be done using the button P1+P2. Please refer to the schematic diagram on capter 3 in order to localize the position on the board. In order to
carry the transmitter memorization it is necessary use the P1+P2 buttons of the front cover, entering the “programming mode” first.
WARNING: always check that L1 and L2 are flashing before
carry the following memorizations out!
If no further button is pressed within 10 seconds the control
unit exits automatically the programming mode.
ENTERING THE PROGRAMMING MODE
X1
Press P1 and P2 1 time and keep it pressed for 1s L1 and L2 flashes quickly
P2
P1
+
keep it
pressed
for 1s
L1 L2
*The buzzer will make a beep each time the button is pressed. No more than a second should pass between one press to another one.
TRANSMITTERS DELETION

13
5 SECONDS TIMEOUT
Press 3 time P3 button of a memorized
transmitter and hold it for 2s
The buzzer emits an
intermittent sound
Press the button of the transmitter to delete
within 5 sec.
The buzzer emits a
continuous sound
...
to delete
P3
memorized
3x
REMOTE DELETION OF A TRANSMITTER
5.1
( x3)
AUTO - CLOSE TIME SETTING
6.1
This procedure configures the time lapse between complete opening and the automatic closure (if enabled).
The default time is 30 seconds. It is possible to set the time from 5 seconds to 180 seconds.
30 seconds timeout 5 seconds timeout
Press P3 button of a memorized transmitter and hold it for 5s, the
buzzer sounds 1 beep
Release and press it again 8 times within 5 seconds
and hold it for 2s, the buzzer sounds 2 beeps
Press once P3 to start the counting
of time. The buzzer sounds 1 beep.
Press again P3 to stop the counting
after the desired lapse. The value will
be memorized by the control unit
In case of time-out, the control unit will sound four beeps and exit the procedure automatically.
8x
( x1)
P3
memorized P3
memorized P3
memorized P3
memorized
( x8)
ON START STOP
keep it
pressed
for 5s
keep it
pressed
for 2s
* P3 button is located inside the transmitter. Every time P3 is pressed the lights switch ON.

14
The following procedure configure all the parameters back to the factory settings. The reset doesn’t include the radio code deletion.
Switch the control unit off. Press together P1 and P2, keep them pressed and switch the unit ON The buzzer makes one beep after 10s. Release P1 and P2.
P2
P1 +P2
P1 +
CONTROL UNIT RESET
7.1
Power supply 240Vac ÷ 50Hz
Operating temperature range -20°C ÷ +50°C
IP rating IP20
Reception frequency 868.3MHz
Radio memory capatibility (transmitters) 32
TECHNICAL SPECIFICATIONS
8
Motor characteristics:
Voltage 240Vac
Maximum power 700W
P1+P2

15
TROUBLESHOOTING (WHAT TO DO IF...)
9
Acoustic signals from the control unit
Sequence Meaning Solution
1 costant beep (continuous or intermittent) Faulty control unit Replace the control unit
2 beeps Motor problem
- Set the limit switches
- The thermal protection could be activated. Wait while the motor cools down.
- Check the motor connection
- Test the motor separately by means of a proper tool
3 beeps at startup Radio receiver is empty Memorize at least one transmitter
4 beeps Radio receiver is full Max. number of transmitter exceeded
5 beeps (L1 = ON) Safety test failure: wireless safety edge system - Check the rubber profile general condition
- Check photocells alignment and the connections
6 beeps (L2 = ON) Safety test failure: emergency STOP (TB) Check the safety device connected and the connections
8 beeps Limit switch error: the manoeuvre exceeded the working
time. Check the limit switches and, in case, set them again
9/10 beeps One of the relay is defective (see par. 2.2) Replace the control unit
Other possible issues
Problem Solution
None of the previous signals, but the door doesn’t move downward Command an opening manoeuvre until the top limit has reached.
In the closure, the door hits the floor and opens again
- The bottom limit could be too low, adjust it upwards
- In case of uneven floor use the procedure 3.3 to deactivate the safety edge in the last part of the closure.
It is necessary to command the closure starting from the upper limit switch in order to be effective.
The door can be operated but the safety systems don’t activate Check the motor direction. If wrong, swap brown and black motor wires over (terminals 5 & 7)
The control units responds to the commands sent by transmitters, but the
front cover is not functioning If L5 led flashes, the “holiday mode” is activated
The fuse blows while operating the door Check again the wirings
WARNING: in case that the safety devices (except for TB input) are defective or they have been activated, it is possible to operate the door anyway, keeping
pressed the command button for more than 5 seconds. The control unit will automatically switch to hold-to-run mode.

TELECO AUTOMATION S.R.L.
ITALY
Tel. +39.0438.388511
info@telecoautomation.com
TELECO AUTOMATION FRANCE
FRANCE
Tel. +33.(0)472.145080
info@telecofrance.com
TELECO AUTOMATION GMBH
GERMANY
Tel. +49.(0)8122.9563024
info.[email protected]
TELECO AUTOMATION OCEANIA PTY LTD
AUSTRALIA
Tel. +61.(07)5502.7801
info@telecoautomation.com.au
This document is the property of Teleco Automation Srl, which reserves all reproduction and copyrights
TELECO AUTOMATION BENELUX SPRL
BELGIUM
Tel. +32.(0)67561967
info@telecoautomation.be
Table of contents
Popular Garage Door Opener manuals by other brands

Chamberlain
Chamberlain LM50EVFF Assembly and operating instructions

Automatic Technology
Automatic Technology GDO-7v2 SecuraLift installation instructions

Dormakaba
Dormakaba CS 80 MAGNEO Installation and troubleshooting manual

Beam Labs
Beam Labs beamUP Series product manual

Chamberlain
Chamberlain Power Drive 182638D owner's manual

Chamberlain
Chamberlain LiftMaster Professional Security+ 3245M owner's manual

Automatic Technology
Automatic Technology SECURALIFT Installation instructions and owner's manual

B&D
B&D Easylifter manual

Chamberlain
Chamberlain Infinity B manual

KROFTMAN
KROFTMAN EM-20 installation manual

Genie
Genie INTELLIG 4024H Operation and maintenance manual

B&D
B&D Controll-A-Door Diamond PD & Roll-A-Pro owner's manual